Installation

 Connection

H3Y-2

H3Y-4

Connect the DC power supply to
terminals 13 and 14 according
to the polarity marks.

Connect the DC power supply to
terminals 13 and 14 according to
the polarity marks.

Precautions

When selecting a control output, use the H3Y-2 for switching ON
and OFF the power and the H3Y-4 for switching ON and OFF the
minute load.

The operating voltage will increase when using the H3Y in any place
where the ambient temperature is more than 50

°

C. Supply 90% to

110% of the rated voltages (at 12 VDC: 95% to 110%) when operat-
ing at 50

°

C or higher.

Do not leave the H3Y in time-up condition for a long period of time
(for example, more than one month in any place where the ambient
temperature is high), otherwise the internal parts (aluminum elec-
trolytic capacitor) may become damaged. Therefore, the use of the
H3Y with a relay as shown in the following circuit diagram is recom-
mended to extend the service life of the H3Y.

MY Relay

H3Y

Do not connect the H3Y as shown in the following circuit diagram on
the right hand side, otherwise the H3Y’s internal contacts different
from each other in polarity may become short-circuited.

Correct

Incorrect

Use the following safety circuit when building a self-holding or self-
resetting circuit with the H3Y and an auxiliary relay, such as an MY
Relay, in combination.

: H3Y

Auxiliary relay: 
MY Relay

Do not use the H3Y in places where there is excessive dust, corro-
sive gas, or direct sunlight.

Do not mount more than one H3Y closely together, otherwise the
internal parts may become damaged. Make sure that there is a
space of 5 mm or more between any H3Y Models next to each other
to allow heat radiation.

The internal parts may become damaged if a supply voltage other
than the rated ones is imposed on the H3Y. When more than 100 V is
applied to 12 or 24 VDC, the internal element (varistor) may break.

OMRON Corporation

Supervisory Control Devices Division
28th Fl., Crystal Tower Bldg.,
1-2-27, Shiromi, Chuo-ku,
Osaka 540-6028 Japan
Phone: (81)6-949-6035 Fax: (81)6-949-6069

ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.

To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.

Cat. No. L097-E1-1

In the interest of product improvement, specifications are subject to change without notice.

Printed in Japan
0597-2M (0597) 

a

Limited issue for Southeast Asian countries

Содержание H3Y -

Страница 1: ...cket Time limit operation lf tti DPDT 0 1 s to 30 min 110 VAC H3Y 2 e o e a o self resetting 0 s o 30 220 VAC 3 24 VDC 4PDT 110 VAC H3Y 4 220 VAC 3 24 VDC Note Specify the model number supply voltage and rated time when ordering Ex H3Y 2 110 VAC 1 s Rated time Supply voltage Accessories Track mounted socket see note Back connecting socket ac ou ed soc e see o e Solder terminal Wire wrap terminal P...

Страница 2: ...del see note 1 500 VAC 50 60 Hz for 1 min between different pole contacts 4 pole model 1 000 VAC 50 60 Hz for 1 min between non continuous contacts Vibration resistance Destruction 10 to 55 Hz with 1 0 mm double amplitude Malfunction 10 to 55 Hz with 1 0 mm double amplitude Shock resistance Destruction 1 000 m s2 approx 100G Malfunction 100 m s2 approx 10G Ambient temperature Operating 10 C to 50 ...

Страница 3: ...of 0 6 A can be switched at 125 VDC cosφ 1 Maximum current of 0 2 A can be switched if L R is 7 ms In both cases a life of 100 000 operations can be expected The minimum applicable load is 1 mA at 5 VDC P reference value Reference A maximum current of 0 5 A can be switched at 125 VDC cosφ 1 Maximum current of 0 2 A can be switched if L R is 7 ms In both cases a life of 100 000 operations can be ex...

Страница 4: ...ny one of these sockets replace j with 08 or 14 Terminal Arrangement Top View Track Mounting Front Connecting Sockets PYF08A Eight M3 8 sems Two 4 2 5 mounting holes Two 4 5 dia M4 or M3 Mounting Holes 6 72 max 23 max 30 max 16 5 35 4 3 4 4 6 59 0 3 15 0 2 PYFjA 90 5 86 6 H3Y Series Terminal Arrangement Top View PYF14A Mounting Holes Fourteen M3 8 sems Two 4 2 5 mounting holes Two 4 5 dia M4 or M3...

Страница 5: ...14 14 13 20 8 Two 3 5 dia 30 max 4 42 3 32 2 22 1 12 8 44 7 34 6 24 5 14 41 12 31 11 21 10 11 9 A1 13 A2 14 A2 14 66 5 max PYF 14A N 29 5 max 42 32 22 12 44 34 24 14 41 31 21 11 A2 A2 A1 PYF14A N Terminal Arrangement Mounting Holes for Surface Mounting PYF08A E 31 max 72 max 23 max Top View PYF14A E 31 max 72 max 29 5 max Top View Eight M3 8 sems Two 4 2 5 mounting holes Two 4 5 dia M4 or M3 Two 4...

Страница 6: ...te Note With PYjQN 2 dimension should read 20 max and dimension 36 5 max 29 5 max 25 5 max 24 max 0 3 2 7 7 7 20 max 2 6 2 7 29 5 max 41 5 max see note 25 max 24 max 22 max H3Y Series PYj PYj 02 PYjQN 2 29 5 max 25 5 max 22 max 0 3 2 7 4 3 16 5 max 2 PY08 02 PY14 02 59 3 21 4 0 2 0 Terminal Arrangement Bottom View Terminal Arrangement Bottom View PY08QN PY08QN 2 PY14QN PY14QN 2 PY08 PY14 25 8 0 2 ...

Страница 7: ... 2 PY14QN 2 PYP 1 PYP 18 Note PYP 18 may be cut to any desired length PYP 1 Two 3 4 dia holes PYP 18 Relay Hold down Clips Y92H 3 for PYFjA Socket Y92H 4 for PYj Socket Mounting Track PFP 100N PFP 50N see note 1 End Plate PFP M 1000 500 See note 2 Note 1 Meets DIN EN50022 2 This dimension applies to PFP 50N Spacer PFP S ...

Страница 8: ... contacts different from each other in polarity may become short circuited Correct Incorrect Use the following safety circuit when building a self holding or self resetting circuit with the H3Y and an auxiliary relay such as an MY Relay in combination H3Y Auxiliary relay MY Relay Do not use the H3Y in places where there is excessive dust corro sive gas or direct sunlight Do not mount more than one...

Отзывы: