G9SP
Safety Light Curtain Application
Application Overview
The power supply to the motor is turned OFF when light is intercepted in the safety light curtain and the safety
limit switch turns OFF simultaneously.
The output also goes OFF when emergency switch S1 is pressed.
Wiring Example
Program
PL/Safety Category
Model
Stop category
Reset
PLe/4 equivalent
•
Emergency stop pushbutton
A165E/A22E
•
Safety light curtain
F3SJ-E
@@@@
P25
•
Safety Limit Switch
D4N/D4F
0
Manual
S1
S2
S3
S4
E1 and E2:
24-VDC power supplies
S1:
Emergency stop switch
S2:
Safety light curtain
S3:
Safety limit Switch
S4:
Reset switch
KM1 and KM2: Contactors
M:
Motor
Note:
Refer to page 20 for the terminal arrangement.
Timing Chart
Hazard
approaches.
S2 detects a
h
u
man
b
ody.
Reset O
N
E-Stop S1
Safety light c
u
rtain
S2
Safety Limit S
w
itch
S3
Reset S4
EDM feed
b
ack
KM1, KM2
Idle
→
R
u
n
More than
350 ms
More than
350 ms
S2 detects a h
u
man
b
ody and S3
detects the ro
b
ot arm.
E-Stop released
E-Stop pressed
S3 detects the
ro
b
ot arm.
Hazard (e.g., ro
b
ot arm) is
interr
u
pting light to S3 and stopped.
Safety I/O Terminal Settings
Input Terminals
Output Terminals
Light c
u
rtain
Light c
u
rtain
Limit S
w
itch
Limit S
w
itch
Precautions for Safe Use
• Perform a function test every six months to
detect contact welding failures on contactors.
• It is the user's responsibility to make sure that
the entire system complies with standards.
• For safety reasons, two electrical switching
elements and two relays or contactors are
always necessary to detect electrical faults and
mechanical faults.
12