20
Setting Procedure:
Once the unit is powered up, Press and hold both the
L
Level Key and the
M
Mode key for three
seconds. This will get the unit to Protect Level.
1.
The first parameter is the Operation Level Protect/Adjustment Level Protect (
oapt
). Verify that
this is
set to 0. Use the Up/Down arrow keys to adjust the value.
2.
Tap on the
M
Mode key to get to the next parameter Initial Setting/Communication Level Protect
(
icpt
). This needs to be changed to 0. Use the Up/Down arrow keys to adjust the value.
Press and hold both the
L
Level Key and the
M
Mode key for three seconds to get back to the
Operation Level.
Press and hold the
L
Level key for three seconds. This will get the unit into the Initial Setting level.
1.
Tap on the
M
Mode key several times until the (
amov
) parameter is displayed. Enter -169 using
the
down arrow key. Allow the unit to sit for a couple of seconds and it will automatically switch to
the
Advanced Function Level. The first parameter shown should be (
init
).
2.
Tap on the
M
Mode key several times until the (
sb1n
) parameter is displayed. This needs to be
changed from (
n-o
) to (
n-c
). Use the Up/Down arrow keys to adjust the value. This changes the
output from normally open to normally close.
3.
Tap on the
M
Mode key several times until the (
out1
) parameter is displayed. This needs to be
changed from (
o
) to (
none
). Use the Up/Down arrow keys to adjust the value. This will reassign
the
control output to
no function
.
4.
Tap on the
M
Mode key once to get to the next parameter (
sub1
). This needs to be changed to
(
alm1
). Use the Up/Down arrow keys to adjust the value. This will assign the sub1 output for the
Limit Alarm.
5.
Tap on the
M
Mode key several times until the (
a1lt
) parameter is displayed. This needs to be
changed from (
off
) to (
on
). Use the Up/Down arrow keys to adjust the value. This will latch the
alarm if an alarm condition is reached.
6.
Note:
I
f the PF key will be used to reset the alarm condition set this next parameter:
Tap on the
M
Mode key several times until the (
pf
) parameter is displayed. This needs to be
changed from (
shft
) to (
lat
). Use the Up/Down arrow keys to adjust the value. This will
reassign
the PF key to Alarm Latch Cancel.
Appearance:
E5GC-600