2. Control Output
0%
100%
20 mA
4 mA
Output
Normal output
0%
100%
Output
Reverse output
20 mA
4 mA
Output Data vs. Output Current
Output value
Process temperature
Output amount
Normal
Reverse
Normal
Reverse
20 mA to 4 mA
to
to
100.0 to 0.0%
0.0 to 100.0%
Note 1. The upper limit of the set value is expressed by
8
and the lower limit of
it is expressed by
.
2. In the case of A/D error, memory error, or abnormal input, 1 mA (safety
side) is output in the same manner as the Electrical Current Output Unit.
3. If the process temperature exceeds either edge of the set limit, the trans-
feroutput will rither be 4 mA or 20 mA.
(
Section 5--2