47
Installation
Section 2-2
2-2
Installation
Use the DIN Track (35 mm wide) to install the DST1-series Safety I/O Termi-
nals in the control panel.
* Refer to the descriptions of individual DST1 models (
Section 5
) for dimen-
sions.
IMPORTANT
• Use the DST1 in an environment that is within the general specifications.
• Use the DST1 in an enclosure rated IP54 (IEC 60529) or higher.
• Use DIN Track (35 mm wide) to mount the DST1 in the control
panel.
• Always use an End Plate on each end of the DST1 to secure it.
• Allow a minimum of 50 mm above and below the DST1 for ventila-
tion.
Wiring ducts
Wiring ducts
End Plate
(PFP-M)
End Plate
(PFP-M)
50 mm min.
50 mm min.
35 mm DIN Track