116
Troubleshooting
Section 7-2
7-2-2
Test Output Errors
Explicit Message for Reading the Cause of the Error
Note
The instance numbers for test outputs 0 to 3 are 1 to 4 (01 to 04 hex), respec-
tively.
Code
Error
Probable cause
Countermeasure
01 hex
Configuration invalid
The configuration is invalid.
Configure the DST1 correctly.
02 hex
Overload detected
1. Ground fault or short-circuit of an out-
put signal line
2. Trouble with the connected device
1. Check the wiring.
2. Replace the connected device.
05 hex
Stuck-at-high detected
1. The power source (positive side) is in
contact with the output signal line.
2. Trouble with the internal circuit
1. Check the wiring.
2. Replace the DST1.
06 hex
Under current was detected
using muting lamp
1. The output signal line is broken or dis-
connected.
2. Trouble with the connected device
1. Check the wiring.
2. Replace the connected device.
Explicit
message
Read/
write
Function
Command
Response
Service
code
Class
ID
Instance
ID
Attribute
ID
Data
size
Test Output
Cause of Error
Information
Read
Read
Reads the cause
for the normal flag
(1 to 4) specified
by the instance ID
turning OFF.
(See note.)
0E hex
09 hex 01 to 04
hex
76 hex
-
0 = No error
Or error code
Содержание DST1-ID12SL-1
Страница 1: ...OPERATION MANUAL Cat No Z904 E1 06 DeviceNet Safety DST1 series Safety I O Terminals...
Страница 2: ......
Страница 3: ...DST1 series Safety I O Terminals Operation Manual Revised June 2011...
Страница 4: ...iv...
Страница 10: ...x...
Страница 14: ...xiv...
Страница 110: ...86 Remote I O Allocations Section 3 2...
Страница 116: ...92 Indicators Section 4 2...
Страница 134: ...110 DST1 XD0808SL 1 Section 5 4...
Страница 146: ...122 Maintenance Section 7 4...
Страница 159: ...135 Logic Terminal Wiring Examples Section 8 3...
Страница 160: ...136 Logic Terminal Wiring Examples Section 8 3...
Страница 178: ...154 Index...
Страница 181: ...157 Revision History...