6
1-10
Click the
OK
Button.
Set
ITEMs
for
Function
Blocks
Thermoc
Input Un
Creating Simple Function Block Data for
the Loop Controller
6-1-4.
Set ITEM 010 (Input Range)
to 1.
Double-click
ITEM 010
to use Input 1.
Next, because a type K thermocouple
is being used and the input range is
0.0 to 500.0
°
C, change
Data
to 1 and
click the
OK
Button.
6-2.
Setting the Function Block for Analog Output
Note:
The input type setting (i.e., parameter) for the
CJ1W-PTS51 Isolated-type Thermocouple
Input Unit must be set to a type K
thermocouple (decimal point) = 0001 hex as
given below:
DM Area Word Allocated in the CPU Unit
D20019 = 0001 hex
(When the unit number is 0.)
(It is not necessary to know the address if the setting
is made by editing parameters by double-clicking
CJ1W-PTS51 in the I/O tables in the CX-
Programmer.)
The ITEM Setting Window will close.
Confirm that the settings have
changed.
Next, double-click 902. Ao 4-point
(DA041) in the tree in the window on
the left. Change the unit number in the
same way as above.
Double-click
ITEM 007
in the window
on the right.
6-2-1.
Double-click 902. Ao 4-point
(DA041).
6-2-2.
Double-click ITEM 007.
The uni
"95." Se
(01) an
Note:
An
Th
CJ
20
(It is not
is made
CJ1W-DA
Program
An out
system
as the
press t
close.
This co
blocks,
and set