Names and Functions of Parts
Section 3-1
Programming Device
Connection Switch
Turn ON this switch to enable Programming Device servicing at the peripheral
port and turn it OFF to disable it. Operational errors related to the connection
of a Programming Device (such as changes in the operating mode) can be
prevented by turning OFF this switch.
Note
1.
If the switch is turned OFF, Programming Device servicing is not performed
and so the scan time is shorter.
2.
This switch can also be used as a restart switch for connection with the
Programming Device.
Peripheral Port
The peripheral port is used for connecting to a Programming Device (i.e., a
Support Software installed on a computer or a Programming Console).
Note
The Unit automatically recognizes the serial communications mode (i.e., Pro-
gramming Console bus, peripheral bus).
I/O Connector
(All Units)
The I/O connector is for contact I/O. Make a cable for this connector with the
24-pin connector provided with the Unit. (For details, refer to
3-3 Wiring
.)
Special I/O Connector
(CS1W-HCP22-V1/HCA22-
V1/HCA12-V1 Only)
The special I/O connector is for special I/O: Pulse inputs and pulse outputs for
the CS1W-HCP22-V1, pulse inputs and analog outputs for the CS1W-HCA22-
V1, and pulse inputs, analog input and analog outputs for the CS1W-HCA12-
V1. Either make a cable for this connector with the 40-pin connector provided
with the Unit, or using a special OMRON cable, connect to an OMRON Con-
nector Terminal Conversion Unit. (For details, refer to
3-3 Wiring
.)
Indicators
Programming Device connection
switch
Programming Device
Connection enabled
(The switch must be turned ON to use a
Programming Device.)
Connection disabled
(Turn OFF the switch to prevent
operational errors.)
Set to ON:
TOOL
ON
OFF
Set to OFF:
TOOL
ON
OFF
HCP22-V1
Indicator
Name
Color
Status
Meaning
RUN
Running
Green
Lit
The Unit is operating normally.
Not lit
One of the following:
• The system in the Unit is stopped.
• The Unit is performing initialization processing.
• There is a hardware error at the Unit.
• There is no power supply from the Power Supply Unit.
• Unit WDT error.
• Unit recognition error (recognized as CPU Bus Unit)
• Unit not recognized (The data for this Unit in the registered
I/O table does not correspond with the mounted Unit.)
• CPU bus error
• Unit number error
• Unit RAM error
OPN
Program execu-
tion
Green
Lit
The Unit’s program is being executed.
Not lit
The Unit’s program is stopped.
Содержание CS1W-HCA12-V1
Страница 2: ......
Страница 6: ...vi...
Страница 20: ...xx Conformance to EC Directives 7...
Страница 38: ...18 Models and System Configurations Section 1 2...
Страница 78: ...58 Fail safe Circuits Section 3 5...
Страница 138: ...118 AR Area Section 6 4...
Страница 204: ...184 Improved Instructions Section 7 14...
Страница 222: ...202 Cycle Time Section 8 3...
Страница 240: ...220 Troubleshooting Flowcharts Section 9 5...
Страница 244: ...224 Precautions when Using the CX Programmer Appendix A...
Страница 252: ......
Страница 253: ......