30
Performance Specifications
Section 2-1
■
CS1W-HCA22-V1 (Pulse Inputs and Analog Outputs)
Pulse Inputs (High-speed Counters)
same as CS1W-HCP22-V1
Analog Outputs
Item
Contents
Number of outputs
2 outputs
Output signal ranges Each output can be set to any one of the following: 1 to 5 V,
0 to 5 V, 0 to 10 V, or –10 to 10 V
Accuracy
±
0.3%
Resolution
–10 to 10 V: 1/10,000
0 to 10 V, 0 to 5 V, or 1 to 5 V: 1/4,000
D/A conversion time
0.05 ms max.
Output function
validity
Each analog output can be set whether output is valid or
invalid.
Output hold mode
Analog output values can be held. (Analog values can be
output at their peak, held, or cleared values when the Con-
version Enable Flag is OFF, a fatal error occurs, or an ana-
log output error occurs.)
Analog output
refresh method
Refreshing of analog outputs is set to one of the following:
END refresh
Immediate refresh via instructions
Offset/gain adjust-
ment
The offset or gain can be specified and changed.
Applicable Instruc-
tions
Analog output can be controlled directly with SPED and
ACC.
Содержание CS1W-HCA12-V1
Страница 2: ......
Страница 6: ...vi...
Страница 20: ...xx Conformance to EC Directives 7...
Страница 38: ...18 Models and System Configurations Section 1 2...
Страница 78: ...58 Fail safe Circuits Section 3 5...
Страница 138: ...118 AR Area Section 6 4...
Страница 204: ...184 Improved Instructions Section 7 14...
Страница 222: ...202 Cycle Time Section 8 3...
Страница 240: ...220 Troubleshooting Flowcharts Section 9 5...
Страница 244: ...224 Precautions when Using the CX Programmer Appendix A...
Страница 252: ......
Страница 253: ......