AR Area
Section 6-4
Analog Inputs/Pulse Inputs/Analog Outputs (CS1W-HCA12-V1 Only)
Address
Bits
Function
Details
Controlled
by
Forced
set/reset
AR 00
00 to 15 High-speed Counter 1
PV
Rightmost
4 digits
Counter range: 8000 0000 to 7FFF
FFFF Hex (8 digits hexadecimal)
Unit
Disabled
AR 01
00 to 15
Leftmost
4 digits
AR 02
00 to 15 Analog input value
Analog input At END refresh or immediate refresh
with instructions, the value input to
analog input port 1 is stored with the
following 4-digit hexadecimal:
• With 0 to 10 V: FE70 to 20D0 Hex
• With 0 to 5 V, 1 to 5 V: FF38 to
1068 Hex
• With
-
10 to +10 V: DDA0 to 2260
Hex
AR 03
00
Analog input status
User adjust-
ment
0: No adjustment
1: Adjusted by user
01 to 07
(Reserved by system.)
08
Default
adjustment
error
0: No error
1: Error (checked at powering ON)
09
User adjust-
ment data
error
0: No error
1: Error (checked at powering ON)
10 to 15 (Reserved by system.)
AR 04 to
AR 05
00 to 15 Counting
mode
• ABS lin-
ear
(CW
-
)
• ABS
ring
• ABS lin-
ear
(CW+)
ABS No.
of rota-
tions PV
Rightmost
4 digits
Multi-turn data (PV read from
encoder) input to the counter unit is
stored here when SEN signal is
input to servo driver.
8000 0000 to 7FFF FFFF Hex
(8-digit hexadecimal)
Leftmost
4 digits
Counting
mode
• Linear
counter
• Ring
counter
High-
speed
counter
monitor
data
Rightmost
4 digits
• When monitoring (measurement
mode 1) the rate-of-change of
high-speed counter, the rate-of-
change of high-speed counter PV
within the set sampling time is
stored with 8-digit hexadecimal.
0000 0000 to 7FFF FFFF Hex
• When monitoring (measurement
mode 2) high-speed counter fre-
quency, the frequency is calcu-
lated based on the PV of high-
speed counter for measuring fre-
quency and the result is stored
here with 8-digit BCD.
0000 0000 to 0020 0000 (BCD): 0
to 200,000 Hz
Leftmost
4 digits
AR 06 to
AR 07
00 to 15 (Reserved by system.)
Содержание CS1W-HCA12-V1
Страница 2: ......
Страница 6: ...vi...
Страница 20: ...xx Conformance to EC Directives 7...
Страница 38: ...18 Models and System Configurations Section 1 2...
Страница 78: ...58 Fail safe Circuits Section 3 5...
Страница 138: ...118 AR Area Section 6 4...
Страница 204: ...184 Improved Instructions Section 7 14...
Страница 222: ...202 Cycle Time Section 8 3...
Страница 240: ...220 Troubleshooting Flowcharts Section 9 5...
Страница 244: ...224 Precautions when Using the CX Programmer Appendix A...
Страница 252: ......
Страница 253: ......