![Omron CS1W-ETN01 Скачать руководство пользователя страница 223](http://html1.mh-extra.com/html/omron/cs1w-etn01/cs1w-etn01_operation-manuals_742528223.webp)
11-3
Section
Command/Response Reference
213
11-3-20
IP ADDRESS TABLE READ
Reads the IP address table.
Command Block
60
27
Command
code
Number of
records
Response Block
60
27
6 bytes
Command
code
Maximum
number
of stored
records
IP address table records
6 bytes
Response
code
Number
of
stored
records
Number
of
records
Parameters
The number of records to read is specified between 0000 and 0020 (0 to 32 deci-
mal) in the command. If this value is set to 0, the number of stored records is
returned but the IP address table records are not returned. The response returns
the actual number of records read.
The maximum number of records that can be stored in the IP address table is
returned. The maximum number of stored records is fixed at 32.
The number of IP address table records stored at the time the command is
executed is returned as a hexadecimal number.
The number of IP address table records specified in the number of records pa-
rameter is returned. The total number of bytes in the IP address table records is
calculated as the number of records x 6 bytes/record. The configuration of the
6 bytes of data in each record is as shown in the following diagram.
00
FINS node
number
IP address
1
6 bytes
FINS Node Number
Node number for communications via the FINS command.
IP Address
IP number used by TCP/IP protocol.
Precautions
If the IP address table contains fewer records than the number specified in the
number of records parameter, all the records contained in the IP address table
when the command is executed will be returned and the command execution will
end normally.
An error response will be returned if the IP address conversion method in the
system mode settings is set to the automatic generation method.
Response Codes
Response code
Description
0000
Normal
1001
Command too large
1002
Command too small
2307
IP address conversion method is set to the automatic
generation method.
Number of Records
(Command, Response)
Maximum Number of Stored
Records (Response)
Number of Stored Records
(Response)
IP Address Table Records
(Response)