3

Ordering Information

International Standards

The standards are abbreviated as follows: U: UL, U1: UL(Class I Division 2 Products for Hazardous Locations), C: CSA, UC: cULus, UC1: cULus 
(Class I Division 2 Products for Hazardous Locations), CU: cUL, N: NK, L: Lloyd, and CE: EC Directives.

Contact your OMRON representative for further details and applicable conditions for these standards.

*

Multi licenses (3, 10, 30, or 50 licenses) and DVD media without licenses are also available for the CX-One.

Specifications

*1.

Refer to the DeviceNet Operation Manual (W267) for the communications power supply specifications.

*2.

The Device Unit uses a node, and so connection is possible to 63 slaves only.

*3.

When the DeviceNet is used as a slave, "input" and "output" respectively refer to input from the slave to the master and output from the master 
to the slave.

*4.

The maximum message length includes the command code when using the CMND instruction

Product

Appearance

Specifications

Model

Standards

Number of 

licenses

Media

DeviceNet 

Unit

For CS Series
Functions as either a master or a slave.
2,048 I/O points

CS1W-DRM21-V1

UC1, N, L, 
CE

CX-One FA 

Integrated

Tool Package

Ver.4.

@

The CX-One is a package that integrates the 
Support Software for OMRON PLCs and 
components. CX-One runs on the following OS.
OS: Windows XP (Service Pack 3 or higher, 32-bit 

version) / Windows Vista (32-bit/64-bit version) 
/ Windows 7 (32-bit/64-bit version) / Windows 8 
(32-bit/64-bit version) / Windows 8.1 (32-bit/64-
bit version) / Windows 10 (32-bit/64-bit version)

CX-One Ver.4.

@

 includes CX-Integrator Ver.2.

@

.

For details, refer to the CX-One catalog (Cat. No. 
R134).

1 license

 *

DVD

CXONE-AL01D-V4

Communications power supply voltage

11 to 25 VDC 

*

1

Current consumption

Communications: 30 mA max.
Internal circuit:

290 mA max.

Max. number of 

connectable slaves

Remote I/O, explicit message service

63 

*

2

Max. number of I/O 

points

Fixed allocations

When used as 

a master

2,048 points

When used as 

a slave

32 points

User-set 

allocations

Using 

allocated DM 

Area words

When used as 

a master

16,000 points

When used as 

a slave

3,200 points

Using 

Configurator

When used as 

a master

32,000 points

When used as 

a slave

4,800 points

Number of allocated 

words

Fixed allocations

When used as 

a master

64 input and 64 output words
Software switch/status area: 25 words

When used as 

a slave

1 input word, 1 output word 

*

3

User-set 

allocations

Using 

allocated DM 

Area words

When used as 

a master

500 input and 500 output words
Software switch/status area: 25 words

When used as 

a slave

100 input and 100 output words 

*

3

Software switch/status area: 25 words

Using 

Configurator

When used as 

a master

500 input words x 2 blocks, 500 output words x 2 blocks
Software switch/Status area: 25 words

When used as 

a slave

100 input words x 1 blocks, 100 output words x 2 blocks
Software switch/Status area: 25 words

Max. message length

542 bytes 

*

4

Max. number of 

Units mountable to 

PLC

Fixed allocations

3

User-set allocations

16

Weight

172 g max.

Содержание CS1W-DRM21-V1

Страница 1: ...it comments function Connected device comments function I O power supply monitor function Sensor power supply short circuit detection function External load short circuit detection function Disconnected sensor detection function Reduce Setup Time Network power supply monitor function Input filter function Power ON inrush current protection function Communications speed auto detect function Scaling...

Страница 2: ...ranch line length Total branch line length 500 kbps 100 m max 6 m max 39 m max 250 kbps 250 m max 2 6 m max 78 m max 125 kbps 500 m max 2 6 m max 156 m max Communications distancesfor special 4 wire flat cables Baud rate Network length Branch line length Total branch line length 500 kbps 75 m max 6 m max 35 m max 250 kbps 150 m max 6 m max 48 m max 125 kbps 265 m max 6 m max 135 m max Communicatio...

Страница 3: ...Windows 7 32 bit 64 bit version Windows 8 32 bit 64 bit version Windows 8 1 32 bit 64 bit version Windows 10 32 bit 64 bit version CX One Ver 4 includes CX Integrator Ver 2 For details refer to the CX One catalog Cat No R134 1 license DVD CXONE AL01D V4 Communications power supply voltage 11 to 25 VDC 1 Current consumption Communications 30 mA max Internal circuit 290 mA max Max number of connecta...

Страница 4: ...s Unit No switch This switch sets the unit number of the DeviceNet Unit as a one digit hexadecimal value Node address switches These switches set the node address as a two digit decimal value DIP switch The pins have the following functions Pins 1 and 2 Baud rate Pin 3 Continue Stop communications for error when used as a Master Pin 4 Hold clear I O for communications error when used as a Slave Co...

Страница 5: ...0H series CVM1 and CV series DeviceNet Units as well as general DeviceNet communications specifications and wiring methods W404 DRT2 Series DeviceNet Slaves Operation Manual DRT2 ID OD MD32SL H 1 DRT2 MD16S DRT2 Series Information on DRT2 series DeviceNet Slaves W382 DeviceNet Configurator Ver 2 Operation Manual WS02 CFDC1 E DeviceNet Configurator 3G8F5 DRM21 ISA Board 3G8E2 DRM21 PCMCIA Board Inf...

Страница 6: ...rther in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted Suitability of Use Omron Companies shall not be responsible for conformity with any standards codes or regulations which apply to the combination of the Product in the Buyer s application or use of the Product At Buyer s request Omron will provide applicable third party ce...