8+(*2-C#">(*%<-/<)$7-8*('+-?('5-3$"#?I'#">(*%<+
Appendix B
Appendix B
Using Terminal Block Units with Screw-terminals
The following table shows the numbering of the Screw-terminals when you use Terminal Block Units (XW2B-40G4
or XW2B-40G5) to connect the external signals (Power Supply, Digital I/O and Counter Input Signals) to the
CS1W-CT021/CT041 High-speed Counter Unit.
* CS1W-CT041 High-speed Counter Unit only.
Note
1. The top row of the Terminal Block Unit (numbered 1 to 39) corresponds to the
pins numbered A1 to A20 of the associated connector (CN1 or CN2) on the
High-speed Counter Unit. The bottom row of the Terminal Block Unit (num-
bered 2 to 40) corresponds to the pins numbered B1 to B20 of the associated
connector (CN1 or CN2) on the Unit.
2. When you connect the signal wires to the Terminal Block Units you should
avoid mixing up between BLOCK1 and BLOCK2. Make sure that the connec-
tors CN1 and CN2 of the High-speed Counter Unit are connected to the corre-
sponding Terminal Block Units (BLOCK1 and BLOCK2 respectively). Make
indications on the Terminal Block Units in order to differentiate between
BLOCK1 (connected to CN1) and BLOCK2 (connected to CN2).
Item
Connector 2 (CN2)
Connector 1 (CN1)
Terminal Block Unit 2 (BLOCK2):
Screw-terminal Number
Terminal Block Unit 1 (BLOCK1):
Screw-terminal Number
Power Supply (to
feed the outputs)
-PS: 0V
1
+PS: 10 to
24V
2
-PS: 0V
1
+PS:10 to
24V
2
Digital Outputs
[0-3] (NPN/PNP)
O2: NPN
3
O2: PNP
4
O0: NPN
3
O0: PNP
4
O3: NPN
5
O3: PNP
6
O1: NPN
5
O1: PNP
6
Spare
7
8
7
8
Digital Inputs
[0-3]
I2: 0V
9
I2: 24V
10
I0: 0V
9
I0: 24V
10
I3: 0V
11
I3: 24V
12
I1: 0V
11
I1: 24V
12
Spare
13
14
13
14
Counter 1 &
Counter 2
A
CH2: LD- / 0V
15
CH2: LD+
16
CH1: LD- / 0V
15
CH1: LD+
16
CH2: 12V
17
CH2: 24V
18
CH1: 5V
17
CH1: 24V
18
B
CH2: LD- / 0V
19
CH2: LD+
20
CH1: LD- / 0V
19
CH1: LD+
20
CH2: 12V
21
CH2: 24V
22
CH1: 5V
21
CH1: 24V
22
Z
CH2: LD- / 0V
23
CH2: LD+
24
CH1: LD- / 0V
23
CH1: LD+
24
CH2: 12V
25
CH2: 24V
26
CH1: 5V
25
CH1: 24V
26
Spare
27
28
27
28
Counter 3 &
Counter 4*
A
CH4: LD- / 0V
29
CH4: LD+
30
CH3: LD- / 0V
29
CH3: LD+
30
CH4: 12V
31
CH4: 24V
32
CH3: 5V
31
CH3: 24V
32
B
CH4: LD- / 0V
33
CH4: LD+
34
CH3: LD- / 0V
33
CH3: LD+
34
CH4:12V
35
CH4: 24V
36
CH3: 5V
35
CH3: 24V
36
Z
CH4: LD- / 0V
37
CH4: LD+
38
CH3: LD- / 0V
37
CH3: LD+
38
CH4:12V
39
CH4: 24V
40
CH3: 5V
39
CH3: 24V
40
W902-E2-03.book Seite 175 Donnerstag, 7. Oktober 2004 2:06 14
Содержание CS1W-CT021
Страница 1: ...OPERATION MANUAL High speed Counter Units CS1W CT021 CS1W CT041 Cat No W902 E2 03...
Страница 3: ...W902 E2 03 book Seite iv Donnerstag 7 Oktober 2004 2 06 14...
Страница 5: ...W902 E2 03 book Seite vi Donnerstag 7 Oktober 2004 2 06 14...
Страница 39: ...W902 E2 03 book Seite 24 Donnerstag 7 Oktober 2004 2 06 14...
Страница 59: ...A 2 Section 2 3 W902 E2 03 book Seite 44 Donnerstag 7 Oktober 2004 2 06 14...
Страница 155: ...4 Section 4 6 W902 E2 03 book Seite 140 Donnerstag 7 Oktober 2004 2 06 14...
Страница 199: ...G W902 E2 03 book Seite 184 Donnerstag 7 Oktober 2004 2 06 14...