246
Troubleshooting for Duplex Communications Units
Section 10-5
stored in D00000 and the “node address of the disconnected node” in bits
0 to 5 is stored in D00001.
• The contents of D00000 are shifted 8 bits to the right to convert the node
address to a proper hexadecimal value.
• The hexadecimal node addresses stored in D00000 and D00001 are con-
verted to BCD.
Note When using the sample program as written above, be sure that the bits and
words in the sample program are not already being used by the program or
other Special Units.
10-5 Troubleshooting for Duplex Communications Units
Controller Link Units (CS1W-CLK12-V1 and CS1W-CLK52-V1) can be used
in duplex operation when they are mounted to a CS1D System. When using
Controller Link Units in duplex operation, if there is an error in the active Unit,
the standby Unit switches to active mode, and communications operations for
the node continue. The Unit with the error can also be replaced without turn-
ing OFF the power for the CS1D PLC (online replacement).
Note When an error occurs in the active Controller Link Unit and the standby Unit
changes to active mode, the node temporarily leaves the network before
rejoining it. For details on the time required to complete the switchover, refer
to 8-5 Switching Time for Duplex Units.
System Configuration Example
10-5-1 LED Indicators
The LED indicators on the active Controller Link Unit operate in the same way
as those for existing Units (i.e., without the “-V1” at the end). Refer to 3-1
Component Names and Functions. The operation of the LED indicators on the
standby Unit is given below.
C
P
U
C
P
U
D
P
L
C
P
U
P
S
P
S
C
L
K
C
L
K
C
P
U
C
P
U
D
P
L
C
P
U
P
S
P
S
C
L
K
C
L
K
D
P
L
C
P
U
P
S
P
S
C
L
K
C
L
K
C
P
U
P
S
C
L
K
Controller Link Unit
CS1W-CLK12-V1 or
CS1W-CLK52-V1
CS1D PLC
(Duplex System)
CS1D PLC
(Simplex System)
Controller Link Unit
CS1W-CLK12-V1 or
CS1W-CLK52-V1
H-PCF Cable or GI Cable
(ring connection)
Controller Link Unit
CVM1-CLK12-V1 or
CVM1-CLK52-V1
CS1D PLC
(Duplex
System)
PS: Power Supply Unit
CPU:CPU Unit
DPL: Duplex Unit
CLK: Controller Link Unit
The standby Unit is shaded.
PLC other
than CS1D
(no duplex
operation)
Not used.
RUN
RUN
ERC
ERC
CLK12-V1
RING
RING
INS
INS
SD
SD
ERH
ERH
M/A
M/A
LNK
LNK
RD
RD
P/S
RUN
RUN
ERC
ERC
CLK52-V1
RING
RING
INS
INS
SD
SD
ERH
ERH
M/A
M/A
LNK
LNK
RD
RD
P/S
CS1W-CLK12-V1
CS1W-CLK52-V1
Содержание CS1W-CLK12-V1
Страница 3: ...iv ...
Страница 5: ...vi ...
Страница 9: ...x TABLE OF CONTENTS ...
Страница 11: ...xii ...
Страница 59: ...42 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Страница 62: ...45 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Страница 91: ...74 CVM1 and CV series Optical Ring Controller Link Units Section 4 2 ...
Страница 108: ...91 Setting Data Links Section 5 2 Device Information Setting Data Link Tables ...
Страница 125: ...108 Checking Data Link Status Section 5 4 ...
Страница 181: ...164 Setting Routing Tables Section 7 4 ...
Страница 199: ...182 Memory Areas Related to Duplex Operation Section 8 6 ...
Страница 275: ...258 Handling Precautions Section 10 7 ...
Страница 298: ...281 CS series Optical Bus Controller Link Units Appendix C Dimensions Unit mm 101 35 130 ...
Страница 299: ...282 CS series Optical Bus Controller Link Units Appendix C ...
Страница 311: ...Authorized Distributor Cat No W370 E1 03 Note Specifications subject to change without notice Printed in Japan ...
Страница 312: ...CS1W CLK12 V1 CVM1 CLK12 CS1W CLK52 V1 CVM1 CLK52 Optical Ring Controller Link Units Cat No W370 E1 03 OPERATION MANUAL ...