26
Functions Listed by Usage
Section 1-4
Basic Functions
Maintenance Functions
Communications Functions
Usage
Function
Refer
to
Set the cycle time to a fixed interval.
Set a minimum (fixed) cycle time in the PC Setup.
Stop PC operation when the cycle time exceeds a max-
imum setting.
Set a maximum (watch) cycle time in the PC Setup.
Keep all outputs ON when PC operation stops.
Turn ON the IOM Hold Bit (SR 25212).
Retain the contents of I/O memory when starting opera-
tion.
Turn ON the IOM Hold Bit (SR 25212).
Retain the contents of I/O memory when the PC is
turned ON.
Turn ON the IOM Hold Bit (SR 25212) and set the PC
Setup (DM 6601) so that the status of the IOM Hold Bit
is maintained at startup.
Eliminate effects from chattering and external noise.
Set a longer input time constant in the PC Setup.
Usage
Function
Refer
to
Record data with time-stamp.
Clock/calendar function
Establish user-defined errors for desired input condi-
tions. (Fatal and non-fatal errors can be defined.)
FAL(06) defines non-fatal errors. (PC operation contin-
ues.)
FALS(07) defines fatal errors. (PC operation stops.)
W353
Read the number of power interruptions.
The number of power interruptions is stored in AR 23.
Set the startup operating mode.
Set the startup operating mode in the PC Setup
(DM 6600).
Usage
Function
Refer
to
Read/write I/O memory data and change the operating
mode from a host computer.
Host Link communications (Set the communications
mode to Host Link in the PC Setup.)
W353
Connect to a serial device such as a bar code reader or
serial printer.
No-protocol communications (Set the communications
mode to no-protocol in the PC Setup.)
Make a high-speed connection with an OMRON Pro-
grammable Terminal.
1:1 NT Link (Set the communications mode to 1:1 NT
Link in the PC Setup.)
Make a PC-PC data link connection with another
CPM2C, or a CPM1, CPM1A, CPM2A, SRM1, CQM1,
C200HS, or C200HX/HG/HE PC.
1:1 PC Link (Set the communications mode to 1:1 PC
Link in the PC Setup.)
Connect a Programming Console.
Connect the Programming Console to the peripheral
port via the communications port. (Turn OFF Communi-
cations Switch 2.)
Connect a personal computer running SYSMAC Sup-
port Software (SSS) or SYSMAC-CPT Support Soft-
ware.
The computer can be connected to the peripheral port
or RS-232C port via the communications port.
Monitor equipment with a Programmable Terminal and
program the PC with a Programming Device.
The RS-232C port and peripheral port can be used
simultaneously via the communications port.
Содержание CPM2C-S100C
Страница 2: ......
Страница 3: ...CPM2C S Programmable Controller Operation Manual Revised September 2009 ...
Страница 4: ...iv ...
Страница 6: ...vi ...
Страница 10: ......
Страница 14: ...xiv ...
Страница 180: ...158 One to one PC Link I O Response Time Section 7 4 ...
Страница 222: ...200 Programming Example Section 8 3 ...
Страница 250: ......
Страница 256: ......
Страница 258: ......
Страница 260: ...238 Support Software Appendix C ...
Страница 268: ......