101
PC Setup
Section 4-6
Note
The startup operating mode will be as shown in the following table if bits 08 to
15 of DM 6600 are set to 00.
DM 6608
00 to 07
DeviceNet I/O Link Read
(IN) area settings
(CPM2C-S
→
Master)
Data area
01 (Hex): I/O area 1 (IR 000 to IR 049)
02 (Hex): I/O area 2 (IR 200 to IR 227)
03 (Hex): DM area (DM 0000 to DM 2047)
04 (Hex): LR area (LR 00 to LR 15)
05 (Hex): HR area (HR 00 to HR 19)
06 (Hex): AR area (AR 00 to 23)
07 (Hex): Timer/counter area (TC 000 to TC 255)
08 to 15
Number of bytes
01 to 40 (Hex) (equivalent to 0 to 64 decimal)
DM 6609
00 to 15
Starting word address
0000 to 07FF (Hex) (equivalent to 0000 to 2047 decimal)
DM 6610 to
DM 6614
00 to 15
Not used.
Not used.
Connected
Programming Device
Startup operating mode
DIP switch pin 4 ON
DIP switch pin 4 OFF
None
PROGRAM
RUN
Programming Console
Mode set on Programming Console mode switch
Other Device
PROGRAM
Word(s)
Bit(s)
Function
Word(s)
Bit(s)
Function
Cycle Time Settings (DM 6615 to DM 6619)
The following settings are read by the CPU when program execution is started.
DM 6615
00 to 15
Not used.
DM 6616
00 to 07
Servicing time for RS-232C port (Effective when bits 08 to 15 are set to 01.)
00 to 99 (BCD): Percentage of cycle time used to service RS-232C port.
08 to 15
RS-232C port servicing setting enable
00 (Hex): 5% of the cycle time
01 (Hex): Use time in bits 00 to 07.
DM 6617
00 to 07
Servicing time for peripheral port (Effective when bits 08 to 15 are set to 01.)
00 to 99 (BCD): Percentage of cycle time used to service peripheral.
08 to 15
Peripheral port servicing setting enable
00 (Hex): 5% of the cycle time
01 (Hex): Use time in bits 00 to 07.
DM 6618
00 to 07
Cycle monitor time (Effective when bits 08 to 15 are set to 01, 02, or 03.)
00 to 99 (BCD): Setting (See bits 08 to 15, below.)
A fatal error will be generated and PC operation will stop if the cycle time exceeds the cycle
monitor time set here.
08 to 15
Cycle monitor enable (Setting in 00 to 07
×
units; 99 s max.)
00 (Hex): 120 ms (setting in bits 00 to 07 disabled)
01 (Hex): Setting units: 10 ms
02 (Hex): Setting units: 100 ms
03 (Hex): Setting units: 1 s
DM 6619
00 to 15
Minimum cycle time
0000: Variable (no minimum)
0001 to 9999 (BCD): Minimum time in ms
Содержание CPM2C-S100C
Страница 2: ......
Страница 3: ...CPM2C S Programmable Controller Operation Manual Revised September 2009 ...
Страница 4: ...iv ...
Страница 6: ...vi ...
Страница 10: ......
Страница 14: ...xiv ...
Страница 180: ...158 One to one PC Link I O Response Time Section 7 4 ...
Страница 222: ...200 Programming Example Section 8 3 ...
Страница 250: ......
Страница 256: ......
Страница 258: ......
Страница 260: ...238 Support Software Appendix C ...
Страница 268: ......