4-3
4 Troubleshooting and Maintenance
CJ-series PROFIBUS Slave Unit Operation Manual for NJ-series CPU Unit (W510)
4-
1 Error Ind
icato
rs
4
4-
1-2 Er
rors Dur
in
g Initial Processing
4-1-2
Errors During Initial Processing
RUN
ERC
ERH
Error
Probable Cause
Remedy
OFF
OFF
OFF
---
•
The CPU power is off
•
The Unit is defective
•
Apply power to the CPU
•
Replace the Unit
OFF
OFF
ON
CPU Error
•
An error was detected in the
CPU
•
Resolve the error in the CPU
and restart the system.
OFF
OFF Flashing
---
•
The unit is configured cor-
rectly. The CPU is in pro-
gram mode likely because it
has been configured to oper-
ate upon error based on the
settings of
*_SlvInFatlCont
and
*_SlvInFatlExit
. The Unit
will transmit diagnostics
to
the PROFIBUS Master for
more information.
•
The unit is configured cor-
rectly. The CPU has an error
and the Unit has been pro-
grammed to stop (Action
Fatal Error in Configuration
is set to Stop). The Unit will
transmit diagnostics to the
PROFIBUS Master.
•
Check the status of
*_SlvInFatlCont
and
*_SlvInFatlExit.
•
Check the operating mode of
the CPU.
•
Check the diagnostics sent
to the Master Unit for more
information.
OFF
ON
OFF
Unit Error
•
The Unit is defective
•
Replace the Unit
4-1-3
Errors During Normal Operation
COMM
BF
Error
Probable Cause
Remedy
OFF
OFF
Not Exchanging
I/O data with
CPU
•
The Unit is not mounted to
the CPU system properly.
•
The Master Unit or transmis-
sion line have failed.
•
The watchdog of the slave
has switched the outputs of
the slave to the fail-safe
mode.
•
I/O refresh has been dis-
abled.
•
The Slave is defective.
•
CPU is not in RUN mode.
•
Check the mounting of the system is cor-
rect.
•
Check the transmission line for proper
connection and correct wiring according to
recommended procedures (see
•
Disable the watchdog for troubleshooting
measures.
•
Check the CPU settings.
•
Replace the Unit.