9-43
9 Troubleshooting and Maintenance
CJ-series DeviceNet Units Operation Manual for NJ-series CPU Unit(W497)
9-4 Even
t L
ogs
9
9-4-3 Error De
scr
iptio
ns
Event name
Invalid Scan List Data
Event code
148D 0000 hex
Meaning
There is an error in the contents of the slave scan list or master scan list stored in non-volatile memory.
Source
PLC Function Module
Source details
CJ-series Unit
Detection
timing
At power ON or
Controller reset
Error attributes
Level
Minor fault
Recovery
Error reset
Log category
System
Effects
User program
Continues.
Operation
The DeviceNet Unit will stop remote I/O communications
for the master or slaves. Data exchange processing with
the CPU Unit and message processing will continue. Nor-
mal operation will be recovered if writing is performed nor-
mally.
System-defined
variables
Variable
Data type
Name
None
---
---
Cause and
correction
Assumed cause
Correction
Prevention
The power was interrupted during
writing the scan list to the non-volatile
memory.
If there is an error in the slave scan
list, disable the slave function, reset
the allocations, and then enable the
slave function. Or, reset the slave
scan list with the CX-Integrator. If
there is an error in the master scan
list, clear the scan list, and then regis-
ter the scan list again. Or, reset the
master scan list with the CX-Integra-
tor.
Do not turn OFF the power supply
while the system is writing the set-
tings.
Attached
information
None
Precautions/
Remarks
None
Event name
Invalid Setup Data
Event code
148E 0000 hex
Meaning
There is illegal data in the settings for the slave function.
Source
PLC Function Module
Source details
CJ-series Unit
Detection
timing
At power ON or
Controller reset
Error attributes
Level
Minor fault
Recovery
Automatic recov-
ery, cycle power
supply, or reset
controller
Log category
System
Effects
User program
Continues.
Operation
The DeviceNet Unit will stop the slave function. Remote
I/O communications and message communications will
continue.
System-defined
variables
Variable
Data type
Name
None
---
---
Cause and
correction
Assumed cause
Correction
Prevention
The power was interrupted while the
system was writing the parameters.
Write the parameters again.
Do not turn OFF the power supply
while the system is writing the param-
eters.
Non-volatile memory life
Replace the Unit.
None
Attached
information
None
Precautions/
Remarks
None
Содержание CJ1W-DRM21
Страница 12: ...Manual Structure 10 CJ series DeviceNet Units Operation Manual for NJ series CPU Unit W497 ...
Страница 42: ...Revision History 40 CJ series DeviceNet Units Operation Manual for NJ series CPU Unit W497 ...
Страница 214: ...6 Message Communications 6 26 CJ series DeviceNet Units Operation Manual for NJ series CPU Unit W497 ...
Страница 345: ...Index 1 CJ series DeviceNet Units Operation Manual for NJ series CPU Unit W497 I Index ...
Страница 349: ......