70
Error Log
Section 6-2
6-1-4
Error Identification by StateStatus
The errors monitored by NS Indicator lighting or flashing are identifiable by
StateStatus of the Basic status group.
In the Windows operation systems, use the function CPNT_GetStatus to
access the Basic status group.
In other environment, access to the shared memory area directly.
6-2
Error Log
The Error log keeps record of the errors and occurrence time when the
CompoNet Master Board detects an error. The records (or error log) can be
read or cleared by the Detailed status group.
6-2-1
Error Log Table
Error Log Table
Errors are saved in the Error Log Table in the CompoNet Master Board RAM.
One error is counted as one record in the table. A maximum of 64 records can
be saved. When the table is full with 64 records, the oldest error record is
discarded to replace it with the next coming error.
The Error Log Table saves the following information:
• Error code,
• Detailed code, and
• Date when the error occurred (this data uses the time information notified
by the user application)
LED
StateStatus
How to identify the errors
Bit
Error
NS Red light
3
Slave duplication error
occurred
Identify the erroneous Slave or Repeater Unit by the
Duplication error flag of Detailed status group.
Note : This error occurs not only due to a duplication but also
when a Slave Unit stops because of unstable
communications. If the address duplication is not the
cause, check the wiring or the terminators around the
erroneous Slave Unit.
5
Repeater duplication error
occurred
NS Red flash
0
Communications error
occurred on a Slave Unit
Identify the erroneous Slave or Repeater Unit by the
Communications error flag of the Basic status group.
4
Communications error
occurred on a Repeater Unit
1
Registration Table
comparison error occurred
Identify the erroneous Slave Unit by the Registration error
(Registered Slave not participating) flag or the Registration
error (Non-registered Slave participating) flag in the Detailed
status group.
2
Communications stop due to
communications error
occurred
Identify the erroneous Slave Unit by the Node causing a
communications stop of the Master status in the Detailed
status group.
Содержание 3G8F7-CRM21
Страница 4: ...iv...
Страница 10: ...x TABLE OF CONTENTS...
Страница 30: ...10 Specifications Section 1 7 1 7 3 Dimensions 3G8F7 CRM21 PCI unit mm 3G8F8 CRM21 CompactPCI unit mm...
Страница 46: ...26 Connecting the Communications Power Supply Cables Section 2 4...
Страница 74: ...54 Board Hardware Error Notification Section 4 8...
Страница 173: ...153 APPENDIX D Sample Program D 1 Sample Program 154...
Страница 230: ...210 Wiring for Power Supply Section E 5...
Страница 234: ...214 Index...
Страница 236: ...216 Revision History...
Страница 237: ......