Generac PowerZone Modbus TCP 

Configuration Guide 

IM-815-02 

04-MAR-2020 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The 

PowerZone Synch

 has a display 

that is rectangular, horizontally mounted, 
and with a nice touchscreen display. 

The display will typically be mounted 

into a cabinet, as shown here. 

The backside of the display, looking from 
the inside of the cabinet, is the point of 
connection for the OmniMetrix monitor. 

The OMNI CAT5 cable goes into the top RJ45 

connector, initially labeled “COMPUTER”

 

Existing Generac CAT5 connection 
to the main controller 

Содержание TrueGuard PRO

Страница 1: ...s The OMNI unit is configured for these network values IP Address 10 0 1 202 Subnet Mask 255 255 0 0 Gateway 10 0 1 1 For a single PZ control set the following Modbus Slave ID 1 IP Address 10 0 1 101 Subnet Mask 255 255 0 0 Gateway 10 0 1 1 this is not important If multiple PZ controls are to be connected such as in an MPS configuration use the following MPS Gen Modbus Slave ID IP Address Subnet M...

Страница 2: ...e Modbus TCP Configuration Guide IM 815 02 04 MAR 2020 In the case of a single PowerZone simply connect the OMNI and PZ via a CAT5 cable In the case of multiple PowerZone controls connect the system using a Hub or Switch as shown This Hub Switch should be powered by a genset battery or other uninterruptible power source ...

Страница 3: ...play that is rectangular horizontally mounted and with a nice touchscreen display The display will typically be mounted into a cabinet as shown here The backside of the display looking from the inside of the cabinet is the point of connection for the OmniMetrix monitor The OMNI CAT5 cable goes into the top RJ45 connector initially labeled COMPUTER Existing Generac CAT5 connection to the main contr...

Страница 4: ...f the cabinet or on the cabinet door The OMNI unit should be mounted so that the cables cannot drain water down and into the OMNI unit The antenna cable can route out through the louvers of the cabinet and the OMNI power wires Red and Black pick up BATTERY and DC GND from the customer connection area at the bottom of the cabinet For reference this is the PowerZone Synch Control No connection from ...

Страница 5: ...Zone Pro looks like the image below It is somewhat square and the display is small consuming only a fraction of the front face of the control There should be a small device called the Connectivity Server which allows generator techs to configure the control wirelessly This device shown to the right is also the point of data connection for the control Top view of Connectivity Server ...

Страница 6: ...518 770 209 0012 Generac PowerZone Modbus TCP Configuration Guide IM 815 02 04 MAR 2020 Attach the OMNI power wires Red and Black to generator Battery and respectively On the bottom side of the Connectivity Server is an RJ45 connector in the center Plug the OMNI CAT5 cable into this RJ45 ...

Отзывы: