IM-759 Rev. B 

25-MAR-2019 

 

 

 

 

TrueGuard-PRO

 Basler DGC2020 Hardwire 

 

 

  

Installation Guide 

 

1.  Unpack the monitor, antenna and the data/power cable. The 

25 pin connector plugs onto the front of the OmniMetrix

®

 

monitor. This cable includes wires to power the monitor as 
well as wires for alarm inputs, relay outputs and analog inputs. 
Take a moment to inspect all components to verify there is no 
shipping damage.  

2.  Place the antenna vertically on the roof of the generator and 

route the antenna cable into the area of the generator control. 
The antenna used for transmitting must be installed to provide 
a separation distance of at least 20 cm from all persons and 
must not transmit simultaneously with any other antenna  
transmitters. BE SURE to provide a 

drip loop

 lower than the 

monitor to keep water from running down the antenna cable  

Data/Power Cable 

 

  

into the monitor connection.  

3.  Attach the monitor via its magnetic feet, on top of the engine 

controller or other appropriate location. Horizontal surfaces 
are best, but the unit may be mounted vertically or even 
upside down if necessary.

 

Note: If mounted vertically, install 

the monitor with the cables down to prevent water from 
entering the enclosure.

  

4.  Route the data/power cable into the generator control 

enclosure.  

5.  The Monitor wires to the Basler Terminal aboard using the 

wiring definitions displayed in Table 1 (Page 2).  Also, please 
refer to the diagram on page 3 for added assistance. 

6.  Attach the antenna cable to the front of the monitor and 

tighten thumb tight.  

7.  Turn on the monitor and confirm that the LEDs light up and 

blink. If not, check for power on the terminal strip. If, after 5 
minutes, the only LED lit is the Power LED, check the 
antenna mount and cable connection.  

8.  Allow 15 minutes for the monitor to log into the network and 

then call OmniMetrix at 770-209-0012 to confirm installation. 
Access to machine data is through the OmniView

®

 web 

interface at 

www.omnimetrix.net

Contact OmniMetrix for 

login instructions and web training.  

 

 

  

 

DGC2020 Control Panel 

Hardwire Terminal Connection 