Omniguard 760 series Скачать руководство пользователя страница 11

11

©Firefly AB (Oktober 2016)

Maintenance and troubleshooting

Note: 

 It is recommended that when cleaning or servicing the Flame 

Detector, that any suppression or alarm systems be disabled . 

Omniguard® 760 Series Flame Detector is designed for years of 

trouble-free operation with minimal attention .  Periodic cleaning of 

the optical surfaces is essential, however, for maintaining reliable fire 

protection .  The frequency of required cleaning will be determined 

by the environmental conditions in and around the installation .  The 

detectors should be regularly inspected for a build-up of dust or other 

contaminants on the optical surfaces .

The detection specifications presented in this manual are predicated 

on performance with clean sensor windows .  Contaminants such as 

dust, oil and paint will reduce sensitivity .  Severe contamination on the 

light guides or sensor windows will cause a failure of the self-test .  A 

detector that fails self-test due to dirty optical surfaces may be capable 

of detecting fire, but its effectiveness will be limited to 30 to 50% of its 

specified range .

Cleaning Procedure:

Locate the following optical surfaces: (Figure 9)

1 .  Fire IR Window
2 .  Fire Light Guide End
3 .  Reference IR Window
4 .  Reference Light Guide End

Clean the optical surfaces with a cotton swab wetted with commercial 

liquid glass cleaner, ammonia, methanol, or isopropyl alcohol .  

Rinse with clean water and dry with lens quality cloth .  Repeat with 

methanol if needed to remove smudges .

Caution: 

 Wiping with excessive force or inappropriate materials may 

scratch the optical surfaces and impair performance .

Troubleshooting:

*WARNING*

 Do not attempt to repair a detector .  Study these 

troubleshooting guidelines and review the referenced sections of the 

manual prior to performing maintenance on the fire detection system .

New Installations:

When the detectors are in operational mode, a green LED will be 

visible for one second approximately every ten seconds .  If any or 

all the detectors fail to operate, check the system wiring and power 

supply .  Tight, reliable wiring connections are essential, as are low-

resistance connections from every detector housing to earth ground .  

Measure the voltage between terminals 8 and 10 at the detector 

locations to verify that the supply voltage is within range .

Note: 

Voltage at detectors installed farthest from power source will be 

lower than the no-load supply voltage due to line losses .  Maximum 

load condition occurs during manual test .

The Omniguard® 760 Series Flame Detectors employ sensitive and 

sophisticated electronic circuitry .  Power line transients or excessive 

power supply ripple may therefore cause erratic or intermittent 

operation .  DC-powered detectors function best with ripple-free 

(less than 1 percent) supply voltage; power supply filtering may be 

necessary to improve performance .  In areas that are unprotected from 

shielding and have the potential for conducted RFI/EMI directly into 

the power lines, it is highly recommended to use a Corcom Filter P/N 

15DCB6F or equivalent on the power lines .

Note:

 For reliable operation, the instantaneous supply voltage at the 

input to any detector must not fall below 20 Vdc or exceed 30 Vdc .

Failure To Alarm:

Upon detection of fire, the fire outputs will activate and the red LED, 

visible through the LED window, will turn “ON” .

If during testing a detector fails to alarm, inspect the sensor windows 

for cleanliness .  Clean sensor windows are essential for effective 

optical fire detection .  Clean all the optical surfaces per the cleaning 

procedures previously described and retest the detector .

Should the detector continue to be inoperative, check the supply 

voltage and all associated wiring .  Incorrect power supply voltage or 

loose connections will cause marginal or intermittent performance .

Alarm Condition – No Fire Present:

A detector in alarm condition when no fire is present may be caused 

by an inadvertent actuation of the manual test .  The Series 760 

Flame Detectors feature a manually initiated self-test feature of the 

optical and electronic systems .  If the light guides are continuously 

illuminated, check the manual test wiring and the test switch for 

broken, loose, or intermittent connections .  Repair or tighten any faulty 

connections .  If the light guides are not illuminated, then contact your 

Firefly AB representative .

Confidence Condition:

The Model 760 Flame Detectors are equipped with a fault relay to 

annunciate a change in the operational status of the detector .  When 

power is applied to the detector, the fault relay will energize within 8 

seconds under normal environmental conditions .  A loss of power will 

cause the relay to de-energize .

If the fault relay output fails to change state within 8 seconds after 

power-up and the amber LED fails to illuminate, then there may be no 

power reaching the detector’s electronic module .  Check the supply 

voltage, the condition of the fuse located at F1 on the PCB and the 

wiring to terminals 8 and 10 .  Also, inspect the wiring to the fault relay 

terminals 6 and 7 and the jumper JP1 that sets the fault relay option .

Note: 

 Model 760 Flame Detectors are equipped with a 0 to 20 mA 

option .  A loss of power will result in a constant 0 mA output .

If the fault relay output continues to be inoperative, isolate the relay 

contacts by disconnecting the external wiring to the fault relay 

terminals .  Connect an Ohmmeter across the fault relay terminals and 

monitor for an actuation of the relay .  Repair the external wiring if 

necessary .

Fault Condition:

Note: 

 During environmental conditions that cause a large thermal 

transient such as moving a detector from inside a warm building to 

outside in the cold, the detector will be inoperable until it stabilizes 

to the new thermal condition .  The fault relay will remain off and the 

Amber LED will flash at a 2 Hz rate due to the exceedance until the 

detector acclimates to the environment . This will be an indication of an 

Exceedance Fault .

Model 760 Flame Detectors are equipped with a 0 to 20 mA output .  

When the 0 to 20 mA option is not used, make sure that the 0 to 20 

mA option is “OFF” on the USI .  If the 0 to 20 mA option is “ON” and at 

any time the driveline opens or the current sense is not at the proper 

level, it will cause the activation of the fault outputs .  Check the 

wire terminal 15 and insure that a good signal ground is present at 

terminal 10 or 11 .  To insure that the 0 to 20 mA option causes the fault 

(Fig 9) Optical Surfaces

Содержание 760 series

Страница 1: ...760 SERIES OPTICAL FLAME DETECTORS Installation and operating service manual ...

Страница 2: ...scharge of static electricity from an ungrounded source including the human body may damage the electronic circuitry of the Omniguard Series 760 Flame Detectors Use one or more of the following methods when handling or installing electrostatic sensitive parts A wrist strap connected by a ground cord to an earth ground source Heel straps toe straps or boot straps at standing workstations Conductive...

Страница 3: ...ted under the conditions outlined in the fire detetion performance false alarm immunity and fire detection in the presence of false alarm sources sections of this manual Exposing a 760 detector to any IR sources within the specified field of view at distances less than 3 5 feet may cause the detector to either false alarm or alter the detector s abiltiy to meet other stated performance parameters ...

Страница 4: ...sence of False Alarm Sources All tests were performed outside and third party certified for response to a 1 ft2 Propane fire at 75 ft for the Normal setting at 100 ft for the Enhanced setting and at 200 ft for the Long Distance setting with the false alarm sources at the recommended distances In all cases the detector response was less then 1 second These distances should be used as a guide when i...

Страница 5: ...alse alarm immunity The automatic self test feature of the Model 760 flame detector verifies the proper function of the electronics sensors and optical surfaces This self interrogation process is implemented a minimum of four times per hour thereby providing vital fire detection reliability This is accomplished by channeling the calibrated output of an internally mounted incandescent lamp through ...

Страница 6: ...30Vdc Standby Alarm Manual Test Auto Test 80 mA 100 mA 160 mA 160 mA Relay Contact rating 2 Amps 30 Vdc Resistive Note The detector contains two relays 1 Fire 1 Fault Current Loop Output 0 to 20 mA For details see Table 2 RS485 Half duplex Addressable User Interface Baud Rate 9600 bits per second 1 start bit 8 data bits and 2 stop bits Maximum Power consumption 30 Vdc Standby Alarm Manual Test Aut...

Страница 7: ...dirt will not accumulate on the optical surfaces of the detector As a general rule mount the detector so that it will view the base of the area to be protected The aiming of the detectors becomes increasingly critical the greater the detection distance becomes There should be few if any obstructions between the detector and the area to be protected 5 Complete the installation by wiring the detecto...

Страница 8: ...cuit board PCB in the housing assembly Using these jumpers the relays may be configured as normally open or closed The factory will ship the detectors with the following settings 1 Fire relay K2 normally open will close when there is a fire continuously present beyond the fire time delay setting will close when manual test is activated beyond the length of time for the fire delay time setting Note...

Страница 9: ...etector address number in the following manner the detector will flash the hundreds digit pause 2 seconds flash the tens digit pause 2 seconds and then flash the ones digit Then it will hold the amber LED ON constantly for about 10 seconds Next the detector will repeat this sequence This process will continue for up to 5 minutes Once you are sure that the proper number is programmed then shut the ...

Страница 10: ...f the delay time is 25 3 seconds the two bytes transmitted would be 0x25 and 0x30 As shown in Table 12 the status word has seven alarm bits and one valid transmission bit When bits 0 through 6 are at a logic zero the alarms are OFF When bits 0 through 6 are at a logic one the alarms are ON Bit 7 is always ON If bits 4 through 7 are set to logic one then the relay coil is open If bits 3 through 7 a...

Страница 11: ...ut to any detector must not fall below 20 Vdc or exceed 30 Vdc Failure To Alarm Upon detection of fire the fire outputs will activate and the red LED visible through the LED window will turn ON If during testing a detector fails to alarm inspect the sensor windows for cleanliness Clean sensor windows are essential for effective optical fire detection Clean all the optical surfaces per the cleaning...

Страница 12: ... is connected Warning In addition to detecting fire the Omniguard 760 Series Flame Detector will annunciate a warning of potentially hazardous conditions that could cause a fire When the detector senses a persistent source of infrared radiation from heat sources the Warning Outputs will change state To enable the Warning Outputs for the relay the Warning option switch position 5 must be ON When th...

Страница 13: ...te 2 Stainless Steel 3 4 14 NPT 3 Aluminium M20 1 5 white 5 Stainless Steel M20 1 5 Test feature 1 Auto self test Type Omniguard model 760 Ordering number 760 X X X X X Approval 0 FM SIL2 CSA Russian Fire Certificate IECEx ATEX EMC LVD CSFM 3 SIL2 IECEx ATEX EMC LVD Fire relay configuration 0 Latching 1 Non Latching Designation Multi spectrum infrared flame detector To order please specify ...

Страница 14: ...14 Firefly AB Oktober 2016 Notes ...

Страница 15: ...15 Firefly AB Oktober 2016 ...

Страница 16: ...Firefly AB Phone 46 0 8 449 25 00 Fax 46 0 8 449 25 01 E mail omniguardsales firefly se www omniguardbyfirefly se Address Heliosgatan 3 120 30 Stockholm Sweden Publication No 1031231 Rev D ...

Отзывы: