C1477B User Manual (UMC1477BR04) 

- 15 - 

Copyright Omniflex 

 

6.3.4 

Manually invoking the Circuit Test Function. 

As a confidence measure, the unit may be placed in the full “marching sequence” Circuit 
Test  Mode  at  any  time  by  holding  down  the  Silence  button  and  then  pressing  the  Test 
Button. See section 6.3.5 

6.3.5 

The “Marching Sequence” Circuit Test Display 

This routine is entered upon the following conditions: 

  Upon power up. 

  If the Test button is pressed and a fault is detected in the unit. 

  By holding down the Silence button and then pressing the Test button manually enters 

this function. 

  Any time during normal operation, if the unit during its regular self-test routines detects 

a fault. 

 

This test routine begins by activating the horn output circuit for approximately one second. 

The operator should therefore check that the horn sounds for this short period. 

Immediately  after  this  half-second  period,  if  the  Omni8

  is  functioning  correctly,  the 

following visual indication will occur: 
The display will begin a “marching light” sequence, with each display window illuminating 
and  then  extinguishing,  one  at  a  time,  starting  with  the  display  point  1  (top  left-hand 
window)  and  ending  with  the  display  point  8  (bottom  right-hand  window).    All  display 
windows will then remain extinguished for a brief moment.  
The  “marching”  sequence  will  then  begin  again,  and  this  procedure  of  “marching” 
sequence followed by the brief  “blank” display period  will be repeated continuously until 
the ACKNOWLEDGE pushbutton is depressed, or until an input changes state. 

This  marching  sequence  indicates  that  the  alarm  annunciator  has  passed  all  its  own 
internal tests and is functioning correctly. If the lamp display exhibits any other pattern then 
a fault has been detected, and the unit should be returned for repair. 

To  exit  the  test  mode  and  begin  normal  operation,  the  ACKNOWLEDGE  pushbutton 
should be pressed. 

The pushbuttons may also be tested in this mode: 

If the SILENCE button is depressed - lamp No. 1 flashes continuously. 

If the ACK button is depressed  - the annunciator reverts to normal operation. 

If the RESET button is depressed - lamp No. 3 flashes continuously. 

If the TEST button is depressed - lamp No. 4 flashes continuously. 

If  any  other  lamp  flashes  continuously,  then  the  unit  has  detected  a  fault  and  must  be 
returned to the factory for repair. 

If  a  new  alarm  occurs  while  the  Omni8

  is  in  this  test  routine,  the  unit  will  immediately 

revert  to  its  normal mode  of  operation  and  will  deal  with  the  alarm  state  according  to  the 
pre-selected alarm sequence. 

 

6.4  Use of the inhibit input 

When SW1-8 is off, then input 8 operates in the normal fashion. When SW1-8 is switched on, 
then input 8 is converted into an inhibit input as operates as follows: 

If input 8 is in the abnormal condition all of the other alarm inputs will be disabled from causing a 
new alarm. All other functions of the unit will remain unaffected. 

Содержание Omni8m C1477B Series

Страница 1: ...Omni8 Alarm Annunciator C1477B x...

Страница 2: ...in any form or by any means electronically photocopying mechanical or otherwise nor its contents disclosed either wholly or in part without the consent in writing of or in accordance with the conditi...

Страница 3: ...m annunciator systems Available in a range of power supply options the rugged Omni8 is designed to fit directly into local electrical panels without the need for external power conditioning or interfa...

Страница 4: ...ATION 11 3 1 Installing the Omni8 in a panel 11 4 ELECTRICAL INSTALLATION 12 4 1 Introduction 12 4 2 Connection Table 12 4 3 Connecting the alarm inputs 12 4 4 Connecting the Relay 13 4 5 Connecting t...

Страница 5: ...nt monitoring Integral audible device and control pushbuttons for ease of installation and use Relay output for common group alarm or external audible device control Removable terminals for easy insta...

Страница 6: ...ction Figure 1 3 Side View showing 8 way Set up Switches 1 5 Installation and Set up Procedure The following steps should be implemented in the order shown to configure and install an Omni8 alarm annu...

Страница 7: ...witch of SW2 e g SW2 1 sets the contact sense for input 1 and SW2 8 sets the contact sense for input 8 When the switch is OFF up then the input is set to NORMALLY OPEN i e the input will enter the ala...

Страница 8: ...12 0 0 1 1 0 MOMENTARY ALARM AUTO RESET TIME DELAY ON RETURN TO NORMAL 16 60 seconds 13 1 0 1 1 0 PULSE MONITORING ALARM MANUAL RESET 17 17 1 1 1 1 0 INPUTS 1 4 SEQUENCE 1 INPUTS 5 8 SEQUENCE 27 FOR...

Страница 9: ...d normally by pressing the Silence or Acknowledge Pushbutton This is useful in environments where the local internal audible will not be heard 4 Relay acts in Multiple Reflash Mode The relay is normal...

Страница 10: ...C1477B User Manual UMC1477BR04 10 Copyright Omniflex...

Страница 11: ...CKNESS 8mm MAXIMUM PANEL 42 44 92 180 48 Location of DIP switches Mounting bracket Figure 3 1 Mounting an Omni8 3 1 Installing the Omni8 in a panel Remove the metal bracket from the unit by removing t...

Страница 12: ...wetting 10 Relay Change over Contact Normally Open Connection 11 Relay Change over Contact Common Connection 12 Relay Change over Contact Normally Closed Connection 13 No Connection 14 Earth 15 dc Pow...

Страница 13: ...ported by all operating systems There is also a README TXT file on this disk Run this first to see which version of program you must run to use the supplied templates 5 2 Creating the Legend Film To c...

Страница 14: ...sequence When the Omni8 is put into its test routine by depressing the TEST pushbutton any existing alarm states are remembered and the alarm annunciator will revert to its previous state when it ret...

Страница 15: ...this procedure of marching sequence followed by the brief blank display period will be repeated continuously until the ACKNOWLEDGE pushbutton is depressed or until an input changes state This marchin...

Страница 16: ...C selectable by DIP switch Max open cct voltage 15V dc between Common positive and all input terminals Max closed cct current 2 mA per input Max loop resistance to detect closed circuit 200 ohms Min...

Страница 17: ...haracters 2 5mm Fast Flash Rate 140 flashes per minute Slow Flash Rate 35 flashes per minute TEMPERATURE RANGE Operating Relative Humidity 0 C to 60 C 32 F to 140 F Up to 90 RH non condensing Storage...

Страница 18: ...nts IEC 61000 4 4 1995 2 kV DC power port 1 kV input output lines Supply Variations IEC 61000 4 7 1991 24 V dc 15 10 RoHS Compliance 2011 65 EU RoHS2 ORDERING INFORMATION C1477B 1 Omni8 with PSU 10 15...

Страница 19: ...P ON 1 2 3 4 5 6 7 8 ON SEQUENCE SWITCH SETTING STATE 1 LAMP OFF HORN OFF HORN OFF Sequence 2 Momentary Fleeting Alarm Manual Reset Timer option off STATE 4 STATE 3 RESET WHILE NORMAL ABNORMAL LAMP ON...

Страница 20: ...Only No Lock in Auto Reset Timer option off STATE 4 STATE 3 RETURN TO NORMAL ABNORMAL LAMP ON HORN OFF 1 2 3 4 5 6 7 8 ON SEQUENCE SWITCH SETTING STATE 2 STATE 1 LAMP OFF HORN OFF SIL ACK LAMP FAST FL...

Страница 21: ...RETURN TO NORMAL ABNORMAL ACK WHILE NORMAL Sequence 4 Momentary Fleeting Alarm Manual Reset with Ringback Timer Delay on inputs RESET ABNORMAL 1 2 3 4 5 6 7 8 ON SEQUENCE SWITCH SETTING STATE 1 STATE...

Страница 22: ...FAST FLASH HORN ON FIRST OUT ACTIVE LAMP ON FIRST OUT INACTIVE RESET WHILE NORMAL Sequence 5 Momentary Fleeting Alarm First Out Manual Reset Auto Reset on subsequent Alarms RETURN TO NORMAL ABNORMAL S...

Страница 23: ...TIVE FIRST OUT INACTIVE FIRST OUT INACTIVE HORN ON FIRST OUT ACTIVE LAMP ON FIRST OUT INACTIVE RESET WHILE NORMAL ACK ACK WHILE ABNORMAL LAMP SLOW FLASH FIRST OUT ACTIVE LAMP ON LAMP ON LAMP FAST FLAS...

Страница 24: ...et Re alarm after time out if still abnormal RESET WHILE NORMAL ABNORMAL LAMP ON 1 2 3 4 5 6 7 8 ON SEQUENCE SWITCH SETTING HORN OFF STATE 1 STATE 2 STATE 3 STATE 4 LAMP OFF HORN OFF LAMP FAST FLASH H...

Страница 25: ...TIMER RUNNING TIME OUT LAMP FAST FLASH HORN ON TIMER OFF SIL LAMP FAST FLASH HORN OFF TIMER OFF ACK HORN OFF TIMER OFF T ACK LAMP SLOW FLASH Sequence 12 Momentary Fleeting Alarm Auto Reset with Time D...

Страница 26: ...TIMER OFF TIMER OFF LAMP OFF HORN OFF TIMER OFF TIMER OFF ABNORMAL RETURN TO NORMAL ABNORMAL RETURN TO NORMAL TIME OUT TIME OUT ACK WHILE ABNORMAL SIL ACK WHILE NORMAL ACK WHILE ABNORMAL ACK WHILE NOR...

Страница 27: ...L LAMP ON Sequence 21 Momentary Fleeting Alarm First Out Multiple Groups Auto Reset RETURN TO NORMAL ABNORMAL SUBSEQUENT 1 2 3 4 5 6 7 8 ON SEQUENCE SWITCH SETTING STATE 1 STATE 2 LAMP OFF HORN OFF SI...

Страница 28: ...INACTIVE HORN ON FIRST OUT ACTIVE LAMP ON FIRST OUT INACTIVE RETURN TO NORMAL ACK WHILE NORMAL ACK WHILE NORMAL ACK WHILE ABNORMAL ACK WHILE NORMAL LAMP ON LAMP ON LAMP FAST FLASH LAMP FAST FLASH LAM...

Страница 29: ...larm after time out if still abnormal RETURN TO NORMAL ABNORMAL LAMP ON 1 2 3 4 5 6 7 8 ON SEQUENCE SWITCH SETTING HORN OFF STATE 1 STATE 2 STATE 3 STATE 4 LAMP OFF HORN OFF LAMP FAST FLASH HORN ON SI...

Страница 30: ...OFF ACK HORN OFF TIMER OFF T ACK WHILE ABNORMAL LAMP SLOW FLASH ACK WHILE NORMAL Sequence 29 Pulse Monitoring Alarm Auto Reset 1 2 3 4 5 6 7 8 ON SEQUENCE SWITCH SETTING STATE 1 STATE 2 LAMP OFF HORN...

Отзывы: