background image

M1260F Revised 12.05.06 Ver. 2 

Data subject to change without notice  

                     

© 

Copyright OMNIFLEX 

IGM1260FR02                                                             Part Number 8.0101.036  

 

INSTALLATION  GUIDE  

Maxiflex P3 CPU 

M1260F 

 

Introduction 

This Installation Guide is intended to aid the fitment of the M1260F CPU in the field.  For 
operating details of this product, refer to the Users’ Manual. Please read this Installation Guide 
first before installing this unit. 

 
The Maxiflex P3 CPU is designed specifically for applications requiring PLC programming, 
offering industry standard IEC61131 programming capabilities combined with powerful 
industrial network communications features.  
It is always fitted into the CPU slot of a Maxiflex master base, next to the PSU module. See 
figure 1. It has one port which is a configurable serial port. This port has a DIP switch for 
address and parameter settings.  
RAM is battery backed so that application program variables are not lost on power down, the 
battery  will  be  connected  if  you  have  an  Omniflex  application  loaded  already.    If  you  are 
starting with a fresh CPU from stock the battery will need to be connected. 
 

Figure 1 : Module Positions 

 

 
 

Hardware Installation Procedure 

1.  If the BATTERY is required then connect jumper located in the front of the module, just 

above the DB-9 serial port connector. Remove paper strip which says PULL TO 
CONNECT BATTERY. The Real time clock must then be set. 

2.  If the CPU is going to be programmed use Programming port cable M1831 which is 

available as an accessory (Model No. M1831).  

3.  Plug the CPU into the CPU slot (as per Figure 1). 
 

 

Содержание Maxiflex P3

Страница 1: ...x master base next to the PSU module See figure 1 It has one port which is a configurable serial port This port has a DIP switch for address and parameter settings RAM is battery backed so that application program variables are not lost on power down the battery will be connected if you have an Omniflex application loaded already If you are starting with a fresh CPU from stock the battery will nee...

Страница 2: ...ouse to the ITEM you wish to change and clicking on the right mouse button and selecting the New Value option that pops up Enter you new setting when prompted Refer to screen grab below Table 1 P3 CPU Front Panel Diagnostics LED Legend LED Colour Description CPU OK Green ON CPU is healthy OFF or Flashing No power applied or CPU Faulty I O OK Green ON I O Module status healthy and I O Manifest is c...

Страница 3: ...l Transmission Mode RTU Baud rate 19200 Data bits 8 Parity none Stop bits 1 Address see dipswitch Switches 1 5 Conet ID Switches 6 8 Protocol Switch 7 ON Conet s default The default operation is to use the serial port for standard communications allowing the user to get the CPU up and running quickly and easily both on the test bench and in the field In this case the Serial Port Dipswitch beneath ...

Страница 4: ...p Bit 6 The default DTR CTS Handshaking is Off 7 The default DTR CTS Timeout ms is 0 Changing Serial Port Settings 1 Assemble the Maxiflex base as shown in Figure 1 with the M1260 fitted into the CPU slot and a suitable Maxiflex PSU in the PSU slot 2 Connect power to your system 3 Connect the M1831 programming cable between the COM port of your PC laptop and the programming port of the Maxiflex CP...

Отзывы: