Omni30 User Manual
- 49 -
© Omniflex
UMC1620AR04
Holding/
Input
Register
No.
Coil/
Input
Status.
DIT No.
DESCRIPTION
Read/
Write
be recognised, otherwise the DIP switch setting is used. If an invalid setting is written into these registers, the
relevant sequence is set to Sequence 1.
202
N/A
201
Setup Sequence Number: Input 4 (high byte) : Input 3 (low byte)
R/W
203
N/A
202
Setup Sequence Num ber: Input 6 (high byte) : Input 5 (low byte)
R/W
204
N/A
203
Setup Sequence Number: Input 8 (high byte) : Input 7 (low byte)
R/W
205
N/A
204
Not Used
R/W
206
N/A
205
Not Used
R/W
207
N/A
206
Not Used
R/W
208
N/A
207
Not Used
R/W
209
N/A
208
Setup Timer Setting: Input 2 (high byte) : Input 1 (low byte)
Input delay timer set per input. One input per byte. The data format for an input is as follows:
Most significant bit:
1 = Use the slow timer, 0 = Use the fast timer (1/10 s)
Least significant 7 bits: time delay in multiples
The fast timer counts time in units of tenths of a second (i.e. 1/10 s).
The slow timer counts in multiples of the fast timer and is programmable. Refer to DIT 135 to configure it. The
default setting is 10 which makes is a seconds counter.
Fast timer example:
To delay Input 1 by 20 seconds, enter 200 (or C8 hex)
Slow timer example:
If DIT 135 is set to 10 then to delay Input 1 by 20
seconds, enter 148 (94hex)
Set to
255
to use timer setting set by SW2.
R/W
210
N/A
209
Setup Timer Setting: Input 4 (high byte) : Input 3 (low byte)
R/W
211
N/A
210
Setup Timer Setting: Input 6 (high byte) : Input 5 (low byte)
R/W
212
N/A
211
Setup Timer Setting: Input 8 (high byte) : Input 7 (low byte)
R/W
213
N/A
212
Not Used
R/W
214
N/A
213
Not Used
R/W
215
N/A
214
Not Used
R/W
216
N/A
215
Not Used
R/W
217-219
N/A
216-218
Reserved