Run Omnicomm Configurator. In the window (Figure 13) select equipment — “Sensor”.
If the message “Equipment not found” is displayed in the main window, try changing
connection configuration or operation mode.
Empty/Full Calibration
Perform calibration with fuel which the fuel level sensor will operate in.
1) Pour fuel into the measuring container
2) Immerse the sensor in fuel, to the full length of the measuring probe
3) Wait for the green indicator “Stable” to appear. Press “Full” to set the value
corresponding to a full tank
4) Take the sensor out of the container and wait while fuel will be flowing off the
measuring probe for 1 minute. Press “Empty” to set the value corresponding to an
empty tank
5) Press “Save”