Voltage Transformer
5 - 13
Voltage Withstand Test
Use the test card
VWithstand
to measure the voltage withstand capability of the
secondary winding and secondary wiring.
To do so, disconnect the burden. As shown in Figure 6, connect the 2kV output
socket without point to the transformer’s secondary (a) winding connection, and
the output socket marked with a point to earth and the transformer’s primary
connection (N).
Warning
: Be aware that the terminals connected to the transformer’s secondary
connection "a"and "n" lead life-hazardous voltage!
Figure 6:
Setup for a voltage
withstand test
Note:
Some test cards are available in more than one test mode. For
example, the test card
VWithstand
can be selected in CT, VT,
Resistance and Transformer.
This is solely related to usability. With regard to functionality, the test
card
VWithstand
is identical in all test modes.
Содержание CPC 100
Страница 12: ...CPC 100 V1 41 x...
Страница 28: ...CPC 100 V1 41 1 16...
Страница 90: ...CPC 100 V1 41 3 14...
Страница 194: ...CPC 100 V1 41 6 30...
Страница 250: ...CPC 100 V1 41 8 32 Figure 24 Settings of Amplifier test card for this example use case...
Страница 258: ...CPC 100 V1 41 9 4...
Страница 264: ...CPC 100 V1 41 10 6...
Страница 282: ...CPC 100 V1 41 12 10 Figure 9 Saving tests with the CPC Editor...
Страница 284: ...CPC 100 V1 41 12 12...
Страница 312: ...CPC 100 V1 41 14 12...
Страница 316: ...CPC 100 V1 41 15 4...
Страница 350: ...CPC 100 V1 41 16 34...
Страница 370: ...CPC 100 V1 41 17 20 7 Finish the assembly by screwing the backnut to the housing and by tightening them with wrenches...
Страница 372: ...OMICRON Contact Addresses 22...