87
Power Transformers
Figures 6-17 and 6-18 show the preparation with the
CPC Editor
and the test
results in MS Excel format.
Figure 6-17
Two-winding transformer test preparation with
CPC Editor
Figure 6-18
10 kV results for a two-winding transformer (50 Hz)
6.2.3
Auto-Transformer
The auto-transformer has only one winding with a tap for the low-voltage output.
Only one measurement is made of the winding to tank and core. All high-voltage
and low-voltage terminals are connected together as they are building the high-
voltage electrode of the capacity.