Preface
11
Before performing tests using high voltage, observe the following instructions:
•
Do not use the test equipment without a good connection to substation
ground.
• Do not insert objects (for example screwdrivers, etc.) into any input/output
socket.
• Do not operate the
CP TD1
under ambient conditions that exceed the
temperature and humidity limits listed in 11.2 "Environmental Conditions" on
page 123.
• Make sure to position the test equipment on dry, solid ground.
• Do not operate the
CP TD1
in the presence of explosives, gas or vapors.
• Opening the
CP TD1
invalidates all warranty claims.
• Do not use an extension cable on a cable reel to prevent an overheating of
the cord; run out the extension cord.
• If the
CP TD1
does not seem to function properly, do not use it anymore.
Please call the OMICRON electronics technical support.
Handling Cables
• Always turn off the
CP TD1
completely before you connect or disconnect any
cable (disconnect the
CPC 100
from mains or press its Emergency Stop
button).
• The high-voltage cable must always be well attached and tightly connected
to both the
CP TD1
and the test object. A loose or even falling off connector
at the test object carrying high-voltage is life-hazardous. Make sure the
connectors are clean and dry before connecting.
At the
CP TD1
, press the high-voltage cable’s plug to the connector tightly
and turn the screw cap until you feel a mechanical stop. If you notice a rough-
running of the screw-cap, clean the screw thread and use a lubricant
(vaseline recommended).
At the test object, insert the high-voltage cables’ plugs carefully until you feel
a "click" position. Now they are locked. Confirm this by trying to pull them out.
This should not be possible now.
Note:
Tighten the plugs manually. Do not use any tools for that because that
can damage the plugs or connectors.
Insert the yellow banana plug (the high-voltage cable’s grounding) into the
respective plug socket.
Содержание CP TD1
Страница 1: ...CP TD1 Reference Manual...
Страница 14: ...CP TD1 Reference Manual V 1 44 14...
Страница 20: ...CP TD1 Reference Manual V 1 44 20...
Страница 32: ...CP TD1 Reference Manual V 1 44 32...
Страница 38: ...CP TD1 Reference Manual V 1 44 38...
Страница 84: ...CP TD1 Reference Manual V 1 44 84 Figure 6 14 Frequency scan for H L f 5 kV...
Страница 114: ...CP TD1 Reference Manual V 1 44 114...
Страница 128: ...CP TD1 Reference Manual V 1 44 128...
Страница 154: ...CP TD1 Reference Manual V 1 44 154 Figure 12 12 Diverter switch for 110 kV 40 MVA...
Страница 184: ...CP TD1 Reference Manual V 1 44 184...
Страница 186: ...CP TD1 Reference Manual V 1 44 186...