107
Capacitance and DF Measurement on High-Voltage Bushings
General guidelines for evaluating the C
1
capacitance data are as follows:
7.9
References
Table 7-2
General guidelines for evaluating the C1 capacitance data
Δ
C = C
measured
- C
ref
*
Evaluation:
Δ
C < 5%
Acceptable
5% <
Δ
C < 10%
Should be investigated
Δ
C > 10%
Critical
* with C
ref
= nameplate value or value for new bushing
Evaluation:
DF
meas
< 2 x DF
ref
Acceptable
DF
meas
< 3 x DF
ref
Should be investigated
DF
meas
> 3 x DF
ref
Critical
* with DF
ref
= nameplate value or value for new bushing
[4.1]
ANSI Standard 62-1995: "IEEE Guide for Diagnostic Field
testing of Electric Power Apparatus - Part 1: Oil Filled Power
Transformers, Regulators, and Reactors", IEEE New York,
1995
[4.2]
CIGRE-WG 12-05: An international survey on failures in large
power transformers in service, Electra No. 88 1983, S. 21-48
[4.3]
US Bureau of Reclamation: "Testing and Maintenance of High
Voltage Bushings", Facility instructions, standards and
techniques - Vol. 3-2, Denver, 1991
[4.4]
Schurman, D.: Testing and maintenance of high voltage
bushings, Western Area Power administration, Golden
(Colorado), 1999
[4.5]
Sundermann, U.: "Transformer life cycle management"
1.Symposium Geriatrie des Transformators, Regensburg 2002
Содержание CP TD1
Страница 1: ...CP TD1 Reference Manual...
Страница 14: ...CP TD1 Reference Manual V 1 44 14...
Страница 20: ...CP TD1 Reference Manual V 1 44 20...
Страница 32: ...CP TD1 Reference Manual V 1 44 32...
Страница 38: ...CP TD1 Reference Manual V 1 44 38...
Страница 84: ...CP TD1 Reference Manual V 1 44 84 Figure 6 14 Frequency scan for H L f 5 kV...
Страница 114: ...CP TD1 Reference Manual V 1 44 114...
Страница 128: ...CP TD1 Reference Manual V 1 44 128...
Страница 154: ...CP TD1 Reference Manual V 1 44 154 Figure 12 12 Diverter switch for 110 kV 40 MVA...
Страница 184: ...CP TD1 Reference Manual V 1 44 184...