OMEGA-VSHPe.F-IOM-2205

 

 

 

6

 

 

 

 

 

rior insulation becoming wet and cause the growth 
of mold which is known to cause odors and serious 
indoor air quality problems and health issues.

 

• 

Chassis units must be stored in the upright position 
to keep oil in the compressor. 

 

• 

Riser ends should be capped if being stored on site 
to prevent contamination from foreign objects and 
debris.

 

 

Wet insulation can cause the growth of mold. 
Any sign of mold growth in the interior insula-
tion should be removed, cabinet interior disin-
fected  with  anti

-

microbial  cleaner  and  re-

placed prior to operating the unit.

 

Do  not  store  cabinets  on  their  side  when 
chassis units are inside. Chassis units should 
always  be  stored  and  transported  in  the  up-
right  position  otherwise  damage  to  chassis 
may occur.

 

The  refrigeration  system  of  these  units  con-
tains  POE  oil.  PVC/CPVC  piping  is  prone  to 
failure  when  in  contact  with  POE  oil.  PVC/
CPVC  piping  should  not  be  used  for  water 
supply  and  return  with  any  heat  pump  prod-

ucts as this may result in failure of the system 
and serious property damage.

 

Do not rest or lean the unit on the risers. Do not use 
the risers or stub

-

outs to pick up the unit. Only des-

ignated lift points should be used when moving or 
lifting cabinets. Do not drop the risers.

 

5. CABINET & RISER INSTALLATION

 

Risers are designed to have slight adjust-
ments for riser system expansion and aligning 
the stub

-

outs in the cabinet opening.  When 

installing risers, do not let riser stubs bottom 
out in the riser swage. 

 

Risers are designed to allow for 1

-

1/2 inches 

of movement due to expansion and contrac-
tion. If the total calculated riser expansion ex-
ceeds ±1

-

1/2 inches the field must provide 

expansion compensators.

 

Riser stub

-

outs should be located as centrally 

as possible in the cabinet opening. Do not 
allow stub

-

outs to rest or contact the sheet 

metal opening.

 

 

Do not allow the risers to bottom out when 
installing into the swage.

 

 

FOR SHIPPED LOOSE RISER SHUT

-

OFF VALVES

 

Visually inspect riser stub

-

outs and shut

-

off 

valves for debris or damage.

 

 

 

Follow industry standard soldering practices 
when soldering shut

-

off valves to riser stub

-

outs. 

 

 

Ensure riser stub

-

out surface is cleaned of any 

residue, soot or oils. Failure to adequately 
clean soldering surfaces can result in water 
leaks, property damage and physical injury.

 

 

When soldering shut

-

off valves to riser stub 

outs, adequately protect cabinet, insulation 
and any other equipment from exposure to 
flames and heat.

 

 

CABINET INSTALL

 

1.  When cabinets are shipped with risers attached, 
place cabinets in a horizontal position on the floor (do 
not rest cabinet on the risers).

 

2.  If required, install any field or factory supplied riser 
extensions to the unit mounted risers.

 

3.  Raise the entire cabinet slowly upright while at the 
same time lowering the risers through the floor cut

-

out 

opening. Align the risers to the matching swaged 
(optional) section of the riser on the floor below.

 

4.  Optional swaged sections are approximately 3 inch-
es deep. Risers should be inserted at a depth of ap-
proximately 2 inches into the 3 inch deep swage. Con-
firm risers penetrate at a minimum of 1 inch into the 
swage. Do not allow the riser tailpiece to bottom out 
fully into the 3 inch deep swage.  This will allow for mi-
nor floor to floor variations, otherwise riser overlap may 
not be sufficient on upper floors.

 

5.  Align and center riser positions in the pipe chase 
and level cabinet as necessary.

 

6.  Secure the cabinet to the floor. Cabinet base comes 
with factory mounted pads.

 

7.  Center the riser stub

-

outs in the cabinet openings to 

allow for riser expansion and prevent contact with cabi-
net sheet metal. Prevent riser stub

-

outs from contacting 

sheet metal pass through otherwise damage to stub

-

outs may occur, resulting in property damage. 

 

 

 

 

 

 

 

 

 

 

 

 

Содержание VSHPe Series

Страница 1: ...at Pumps w Integrated ERV MODEL VSHPe SE VSHPe G HE FAN CABINET DEV F CHASSIS DEV F DEV G CONTROL BOARD V3 DOCUMENT RELEASE OMEGA VSHPe F IOM 2205 Supersedes document OMEGA VSHPe F IOM 2108 Revision N...

Страница 2: ...Heating Season 7 Operating Limits 7 6 Chassis Installation 8 Installation of Fittings and Hoses 8 Chassis Install 8 7 Unit Start Up 9 Checklist 9 Initial Start Up 10 8 Controls 11 Microprocessor Cont...

Страница 3: ...result in death of serious injury ALL FIELD WIRING MUST BE PER FORMED ONLY BY A QUALIFIED ELECTRICIAN All wiring must be in accord ance of with the manufacturer s specifications Wiring that is improp...

Страница 4: ...x 8 8 x 14 10 x 14 12 x 12 VSHPe 050 1 1 4 14 x 8 8 x 14 10 x 16 14 x 12 VSHPe 060 1 1 2 14 x 8 8 x 14 10 x 16 14 x 12 VSHPe 080 2 18 x 8 8 x 18 14 x 18 14 x 14 VSHPe 100 2 1 2 18 x 8 8 x 18 14 x 20 1...

Страница 5: ...the front of the unit Unit includes hose kits and manual shut off valves Optional risers are furnished with type L M copper Available 3 inch deep swage connections on same size piping Contractor to p...

Страница 6: ...1 1 2 duct flange 3 ERV Ports Bathroom Exhaust Exhaust Air Outside Air 4 Removable ERV core 5 Heat pump chassis 6 Chassis service cover panel 7 1 air filter 8 Acoustic return air R A panel for chassis...

Страница 7: ...on nect switch The panel is removed by swinging out and lifting it off the support pegs The middle panel is a removable swing panel for ac cessing and servicing the ERV core sensors and fans The upper...

Страница 8: ...o not allow stub outs to rest or contact the sheet metal opening Do not allow the risers to bottom out when installing into the swage FOR SHIPPED LOOSE RISER SHUT OFF VALVES Visually inspect riser stu...

Страница 9: ...ng solution Chassis installation is permitted once the riser system is thoroughly flushed cleaned and water loop is chemical ly treated and commissioned by the riser treatment com pany and contractor...

Страница 10: ...ale NPSM riser shut off valves Do not apply pipe dope or pipe sealant to NPSM fittings Always use a back up wrench Fin ger tighten hose and tighten with back up wrench approximately 1 6 turn DO NOT OV...

Страница 11: ...nsure the building fluid loop system has been cleaned flushed re filled chemically treated and commissioned by the water treatment company Verify that the main system strainers or mechanical filtratio...

Страница 12: ...line is cool and no frosting is forming in the refrigeration circuit 4 Set thermostat to the OFF position Unit compressor and fan should stop running 5 Allow the system to equalize for approximately 5...

Страница 13: ...ing HEAT COOL thermostat set DIP 1 set to the OFF position See table below for connecting thermostat to unit termi nal blocks Thermostat Cable Field wire thermostat cable pigtail to the control board...

Страница 14: ...com pressor contactor will then be energized so long as none of the following fault conditions are present High Pressure Alarm Low Pressure Alarm Optional High Pressure Water Alarm Optional Condensate...

Страница 15: ...oning for both high speed mode P1 and low speed mode P2 Use the ERV board mounted low LO SPD and high speed HI SPD potentiometers to adjust the fan speed and static to meet site conditions SW2 toggle...

Страница 16: ...28 22 18 12 37 Speed 13 Watts 11 O clock 70 54 43 34 27 15 7 45 Speed 18 Watts 12 O clock 85 67 55 44 35 23 15 57 Speed 30 Watts 1 O clock 111 95 83 74 68 54 45 37 30 21 15 69 Speed 43 Watts 2 O cloc...

Страница 17: ...laptop Wireless router is the preferred method for fewer configuration steps and works with Tablets or Smartphones Wireless Router Method 1 To connect to the controller you will need the follow ing E...

Страница 18: ...nge the IP address to 192 168 0 99 and Subnet mask to 255 255 255 0 as shown below Then click OK 7 Open up your internet browser i e Explorer Google Chrome and type in the following address 192 168 0...

Страница 19: ...minal was ener gized Y 1 when the Cooling CLG 1 and tripped on Low Pressure fault LP 0 Captured unit controller details indicate a binary value 0 or 1 to signify if there was a call or not for that pa...

Страница 20: ...eration 4 Visually inspect the air coil for signs of dirt accumu lation Use a mild detergent or coil cleaning agent DO NOT use any cleaning solutions that contain an acid including acetic acid vinegar...

Страница 21: ...ing supply voltage setting at Transformer Check that the line voltage is matched to 208V or 240V transformer taps Heating Cooling Defective compressor capacitor Med Check capacitor and replace if requ...

Страница 22: ...REV HPS High Pressure Switch Check continuity between that switch is Normally Closed LPS Low Pressure Switch Check continuity between that switch is Normally Closed RST Refrigerant Suction Temperature...

Страница 23: ...rm Soft Lock Out Red Solid Leaving water temperature too hot Non latching alarm Red Blinking Sensor open missing or close shorted Non latching alarm replace sensor Red Solid Entering water temperature...

Страница 24: ...or RS return condensate supply Risers can be ordered from factory with 3 inch deep swage Contractor to provide riser transition pieces when joining dissimilar riser sizes All handing s determined by...

Страница 25: ...earance Height Slab Thickness 2 inch overlap Rounded up to 120 or 144 Omega supplies two standard riser lengths 120 10 and 144 12 to be field cut on site Omega does not supply extension tailpieces or...

Страница 26: ...e 060 1 2 24 VSHPe 080 3 4 30 VSHPe 100 3 4 30 VSHPe 120 3 4 30 Model Hose Kit Isolation Valve Notes Standard NPSM sweat connected isolation valves are provided for Factory or Field Supplied Copper Ri...

Страница 27: ...RA panels with supply grille apply gasket tape to supply grille throat to insert into unit sup ply discharge flange Acoustic ERV RA Panel Dimensional Drawing Acoustic ERV RA Panel Sizes A B C VSHPe 03...

Страница 28: ...Cabinet Base Height Min 5 1 increments B BH G 1 Note Include flooring thickness underlayment and any concrete leveling as part of calculation Example If using a 6 baseboard with 1 Finished Flooring h...

Страница 29: ...y Grille Removable core with door Notes Perimeter Panel shown above with Optional Supply Grille Panel is lined with acoustic insulation for enhanced sound attenuation Return air panel supplied in stan...

Страница 30: ...ir opening Optionally insulate the drywall enclosure with plenum rated acoustical insulation for additional sound attenuation Acoustic RA Panel shown Perimeter Panel rough in dimensions are equivalent...

Страница 31: ...shown as 3 Supply and Return and 1 25 Condensate Risers can be positioned on any side Back Left Right RA Panel Furring Details Stud Furring EA OA BE BE OA EA OA OA BE BE EA EA EA EA EA EA OA OA OA OA...

Страница 32: ...120 Y 18 21 1 2 20 1 8 78 1 2 Model Cabinet Size Cabinet Dimensions in Rough In in Z 22 25 1 2 24 1 8 78 1 2 B Cabinet Base Height Min 5 increases in 1 increments C Panel Flange Height from Base of C...

Страница 33: ...OMEGA VSHPe F IOM 2205 31 VHSPe Electrical Schematic ECM Fan...

Страница 34: ...actory supplied 6 wire thermostat cable shown Whisper Mode standard on VSHPe units Jumper between R and G1 factory installed Heat Pump Thermostat R 24VAC G1 Whisper Mode Cont Fan On G2 Fan Speed 2 Med...

Страница 35: ...0 1140 1120 1100 External Static Pressure in w g 900 750 600 450 375 300 220 1200 1010 820 630 530 460 350 Unit Size EC Motor Speed Minimum SCFM Rated SCFM 030 050 040 080 060 120 100 Note All airflow...

Страница 36: ...al balancing valve see name plate for GPM rating Air Temperature Measure the difference in tem perature across air coil for measuring sensible capacity T LAT EAT Sensible Capacity Btuh T x CFM x 1 08...

Страница 37: ...ctory Set confirm that settings have not been adjusted to non standard settings SW1 ERV Board Power Switch Set to ON ____ Yes No SW2 ERV Toggle Switch Set to Neutral Middle Position _____ Yes No Fan E...

Страница 38: ...______ __________________________________________________________________________________________________________________ ______________________________________________________________________________...

Отзывы: