11 |
P a g e
4.5
ON/OFF Control
To configure ON/OFF Control on a device, navigate to the
Output Configuration Tab
in SYNC and click on the
icon
located to the right of the available outputs. Clicking the icon will open
Define ON/OFF Control
dialog box as seen below.
Choose the input with the active alarm that you would like to control and set your preferred parameters.
5
Appendix: SP-010 Registers
The following Appendix provides the registers and list index for the SP-010. This information is intended to aid users who
will be making configurations and adjustments to their Layer N SP-010 Load Cell Smart Probe through the Command Line
Interface or other custom interfaces.
Smart Probe devices share a common platform architecture that provides extensive monitoring and control capabilities thru
a set of platform generic registers. These registers may be accessed using I2C based commands directly to the Smart Probe
devices or thru a set of Modbus based registers when using Omega Interface devices. Refer to the
Smart Sensor Device
Interface
manual for further information.
When powered on or after a device reset each Smart Sensor based device will enumerate 1 or more sensor instances which
are described by the device specific Sensor Descriptors which include configuration options, measurement type and units of
measure for the corresponding sensor values. Additional sensor information is provided in sensor specific IPSO object
descriptions which include extended measurement type, precision and tracking of minimum/maximum readings.
5.1
Load Cell Descriptor
The SP-010 Load Cell descriptor is at base address 0x0060 (Modbus 0xf030).
Offset
Name
Value
Description
0x00
Measurement Type
0x27
Mass (kg)
0x01
Data Type/Format
0x26
Float
0x02
Configuration
0x4?
Lock and Scaling bits only
0x03
Sensor Device
0x??
Enables DIO TARE signals
0x04..0x08
UOMR
“kg”
Units of measure
5.1.1
Load Cell Measurement Type
The Load Cell interface provides a measurement of weight in
kg
.
Sensor Type
SI Derived Units
Measurement
0x27
kg
Mass
5.1.2
Load Cell Input Data Type/Format
All data values are returned as 32-bit floating point values.
Load Cell Input Data Type
7
6
5
4
3
2
1
0
Smart Sensor
Sensor Writable Factory Calibrate
Reserved
Data Type
0
0
?
0
0x06 == FLOAT
5.1.2.1
Data Type
The 4-bit Data Type field determines the type of data of the specific sensor.