•  Correct maintenance is crucial to achieve maximum efficiency of your compressor, and to lengthen its operating life.  

•  It is also important to comply with the maintenance intervals recommended, but it must be remembered that such intervals 

are suggested by the manufacturer in the event that the environmental conditions of use of the compressor are optimal (see 

“Installation” chapter).   

•  The maintenance intervals can therefore be reduced depending on the environmental conditions in which the compressor 

operates. 

•  The oil used is FSN Original Oil, the use of a different oil does not guarantee perfect efficiency and compliance with the 

maintenance intervals. 

•  The maintenance operations described in the table below and on the following pages must be carried out by authorised 

staff.

Maintenance table

To verify correct machine operation, perform the followng checks 

after the first 100 hours of work

:

1) Check the oil level

: top up with the same type of oil if necessary. 

2) Check for proper screw tightening

:

 

in particular the power electric connection screws. 

3) 

Visually check that all 

fittings seal properly. 

4) 

Check the

 hours of work 

and the 

type of service selected

5)

 Check

 room temperature

BEFORE MAINTAINING THE MACHINE ALWAYS PERFORM THE FOLLOWING:

 

Press the machine automatic stop button

 (do not use the emergency button).

 

Power the machine off by means of the wall outer switch.

 

Close the line cock.

 

Make sure that no compressed air is inside the oil separator tank.

 

Remove fairing and/ or panels.

Type of maintenance

Maintenance schedule

work hours

o at least

(when MINERAL 

OIL is used)

(when SYNTHETIC 

OIL is used)

Drain condensate from air tank (if present)

50

50

weekly

Drain condensate from the oil tank

50

50

weekly

Clean cabinet pre-filter panel

50

50

weekly

Oil check and top up

500

500

once per month

Clean intake air filter cartridge 

500

500

-

Check and clean radiator

1000

1000

once a year

Replace primary intake air filter cartridge

2000

2000

once a year

Replace secondary intake air filter cartridge 

4000

4000

once a year

Replace oil filter 

2000

4000

once a year

Replace oil separator filter

2000

4000

once a year

Replace oil

2000

4000

once a year

Replace scavenge non return valve

4000

4000

once a year

Replace cabinet pre-filter

4000

4000

once a year

Condensate drainage filter cleaning

4000

4000

once a year

Intake valve service

8000

8000

Minimum pressure valve overhaul

8000

8000

Thermostatic valve service

8000

8000

Replace joint flexible

8000

8000

Screw Unit seal ring replacement

8000

8000

Solenoid valve replacement

12000

12000

Replace flexible hoses

12000

12000

Air-end overhaul/ replacement

24000

24000

Refer to the motor manual and/or to the motor data plate for electric motor bearing maintenance

NOBEL DV 22 CSA - Cod.197EE0622ML - Rev.1 03/2019

Содержание NOBEL 22 DV CSA

Страница 1: ...rew Instruction Maintenance Manual Model NOBEL 22 DV CSA Please ensure to read this manual before installation and refer back to manual when performing maintence If you require assistance or have any...

Страница 2: ...n delivered and accepted no complaints are accepted CONDITION OF THE MACHINE WHEN SUPPLIED Every compressor is shop tested and delivered ready to be installed and to be set at work The oil for first f...

Страница 3: ...5 1360 600 250 147 5 615 640 580 480 106 1365 880 535 1 1 4 50 665 EN OVERALL DIMENSIONS NOBEL DV 22 CSA Cod 197EE0622ML Rev 1 03 2019...

Страница 4: ...mbols High temperature risk Electric shock risk Risk from hot or dangerous gases in the work area Pressurised container Moving mechanical parts Maintenance in progress Machine with automatic start up...

Страница 5: ...er indicated on CE plate Always follow the maintenance schedule specified in the user s guide DO NOT Do not touch inner parts and pipes as they are very hot during compressor operation and stay hot fo...

Страница 6: ...9 1 13 11 15 1 10 14 8 7 5 6 1 17 18 2 3 10 12 4 16 20 12 9 1 19 EN INSTALLATION DESCRIPTION OF THE COMPRESSOR ON GROUND NOBEL DV 22 CSA Cod 197EE0622ML Rev 1 03 2019...

Страница 7: ...ator should be fitted CONDENSATE IS A POLLUTING MIXTURE It must not be let into the sewage The dimensions of the spaces are indicative only but it is advisable to follow them as closely as possible IN...

Страница 8: ...ambient Re claimable heat Fan type Fan flow rate Rated motor power cooling fan Oil carry over Main electric motor Main Motor speed Nominal main motor power Max power absorbed ventilation included Spe...

Страница 9: ...event of low oil level top up with FSN Original Oil Check for correspondence between the compressor plate data with the actual specifications of the electrical system A variation of 5 with respect to...

Страница 10: ...the compressor mixing with the suction air and thereby creating an air oil mixture which ensures sealing and lubrication of the moving organs of the compressor The air oil mixture goes back to tank 4...

Страница 11: ...oad delay NO LOAD is displayed Compressor loading phase the solenoid valve relay of the load is active This phase lasts until the pressure measured reaches the pressure set in the parameter No load pr...

Страница 12: ...wered Fully operational compressor start up the line relay is maintained active and also the delta relay is activated this phase lasts for the time set in the parameter Load delay NO LOAD is displayed...

Страница 13: ...rent Pressure Pressure range set functioning percentage indication Graphical representation of the motor without inverter Graphical representation of the motor with inverter indicazione percentual di...

Страница 14: ...b menu and highlight it to then open it by pressing the Enter key go back by pressing the Esc key If you go to a parameter screen you can change its value using the Arrow up and Arrow down keys or you...

Страница 15: ...s sound silence the buzzer If the cause of the alarm is resolved delete the warning Displays the counters page for hours of maintenance Back to Main screen Displays the counters page for WORKING hours...

Страница 16: ...imum pressure in the factory menu Loaded pressure Defines the pressure necessary to restart the compressor The recommended value is 1 5 bar lower than that defined in the No load pressure parameter Pr...

Страница 17: ...ote command enabling Fan extra time Defines the time in which the cooling fan stays on after the working temperature of the compressor has returned within the safety limits Inverter Sub menu for inver...

Страница 18: ...ioning percentage set Dryer Menu Dryer ON Dryer Enabling Minimum time Defines the minimum maintenance time of the deactivated dryer It serves to protect the dryer compressor from over frequent start u...

Страница 19: ...mum oil temperature If the oil temperature detected is lower an alarm sounds and the compressor is blocked Thermic drift Defines the maximum variation per second of the oil temperature If surpassed an...

Страница 20: ...sen fault When an anomaly occurs on the oil temperature sensor sensor short circuits or open the alarm BLOCKS the compressor To re start the compressor you need to replace the probe Alarm Motor therma...

Страница 21: ...temperature remains over the total of the temperatures defined in the parameters Temperature OFF and Temperature differential for the time defined in the parameter Alarms delay NOTE there is an alarm...

Страница 22: ...ic stop button do not use the emergency button Power the machine off by means of the wall outer switch Close the line cock Make sure that no compressed air is inside the oil separator tank Remove fair...

Страница 23: ...ents and the cover must be assembled carefully so as not to allow the passage of dust into the compressor unit Never allow the compressor to function without the filtering element CLEANING THE RADIATO...

Страница 24: ...rotection The oil in the original equipment is FSN Original Oil in the following list Description Type of oil RotEnergyPlus 46cST Synthetic lubricant ISO 46 for industrial use RotEnergyFood 46cST Synt...

Страница 25: ...ILTER CLEANING Fig 13 Unscrew the filter and remove it from the compartment on tap B Clean with compressed air jet Screw back on CLEAN AIR PREFILTER Fig 14 Remove prefilters A B from their seat Wash w...

Страница 26: ...cause no command is received Oil separator filter clogged Min pressure valve does not close perfectly Voltage too low Tube leaking Remedy Check voltage press Reset and then restart Check motor absorpt...

Страница 27: ...PROBE DRYER XI Morsettiera inferiore XI Lower Terminal Board 19 20 ALLARME REMOTO REMOTE ALARM 31 32 TEMPERATURE PROBE COMPRESSOR PUMP SONDA MANDATA VITE L25 L25 71 72 COMPRESSOR MOTOR THERMISTORS TE...