40
ALARM 2 DISPLAY COLOR SUBMENU:
Press
d
11)
Display flashes previous selection for “Alarm 2 Color Display”.
Press
b
12)
Scroll through the available selections:
GRN
,
RED
or
AMBR
.
Press
d
13)
Display shows
STRD
stored message momentarily and then
momentarily shows the software version number, followed by
RST
Reset, and then proceeds to the Run Mode.
IN ORDER TO DISPLAY ONE COLOR, SET THE SAME DISPLAY
COLOR ON ALL THREE SUBMENUS ABOVE.
If user wants the display to change color every time that both Alarm1(SP1)
and Alarm2(SP2) are triggered, the Alarm values should be set in such a
way that Alarm1(SP1) value is always on the top of Alarm2(SP2) value,
otherwise value of Alarm1(SP1) will overwrite value of Alarm2(SP2) and
Display Color would not change when Alarm2(SP2) is triggered.
Example 1:
Alarm Setup: Above, SP2 Value = 200, SP1 Value = 400
"Color Display" Setup: Normal Color “N.CLR” = Green,
Alarm 1 Color “1.CLR” = Amber, Alarm 2 Color “2.CLR” = Red
Display Colors change sequences:
GREEN
RED
AMBER
•--
➤
------------------------------•-----------------------------•------------------------------
➤
0 SP2 = 200 SP1 = 400
Example 2:
Alarm Setup: Below, SP2 Value = 300, SP1 Value = 100
Color Display Setup: "N.CLR" = Green, "1.CLR" = Amber, "2.CLR" = Red
Display Colors change sequences:
AMBER
RED
GREEN
• --------------•----------------------------------•------------------------------------------- --•
0 SP1 = 100 SP2 = 300
➤
➤
Содержание i-SERIES
Страница 17: ...3 2 Menu Configuration Figure 3 1 Flow Chart for ID and Set Points Menu 13...