manualshive.com logo in svg
background image

Temperature & Process

Simplified Menu (-SM) Manual

CNi8, CNi8C, CNi8D, CNi16, CNi16D, CNi32

e-mail: [email protected]

 

For latest product manuals:

 

www.omegamanual.info

TM

Shop online at

 

omega.com

User

s Guide

Содержание i-SERIES

Страница 1: ...Temperature Process Simplified Menu SM Manual CNi8 CNi8C CNi8D CNi16 CNi16D CNi32 e mail info omega com For latest product manuals www omegamanual info TM Shop online at omega com User sGuide...

Страница 2: ...tice Servicing North America U S A Omega Engineering Inc Headquarters 800 Connecticut Ave Suite 5N01 Norwalk CT 06854 Toll Free 1 800 826 6342 USA Canada only Customer Service 1 800 622 2378 USA Canad...

Страница 3: ...roduction 12 Turning your Instrument On for the First Time Buttons Functions in Configuration Mode 3 2 Menu Configuration 13 3 2 1 ID Number 14 3 2 2 Setpoints 15 3 2 3 Configuration Menu 16 3 2 4 Inp...

Страница 4: ...11 Excitation Output 11 Figure 3 1 Flow Chart for ID and Setpoints 13 Figure 3 2 Flow Chart for Configuration Menu 16 Figure 3 3 Flow Chart for Input Type Menu 17 Figure 3 4 Flow Chart for Reading Con...

Страница 5: ...es you with information that is important to successfully setup and use the Programmable Digital Meter CAUTION or WARNING Tells you about the risk of electrical shock CAUTION WARNING or IMPORTANT Tell...

Страница 6: ...voltage or DC current The voltage current inputs are fully scalable to virtually all engineering units with selectable decimal point perfect for use with pressure flow or other process input The iSer...

Страница 7: ...shall not be incorporated in the main supply cord Furthermore to provide protection against excessive energy being drawn from the main supply in case of a fault in the equipment an overcurrent protect...

Страница 8: ...the nearest Customer Service Department listed in this manual Manuals Software The latest Operation and Communication Manual as well as free configuration software and ActiveX controls are available...

Страница 9: ...indicator F F unit indicator a Changes display to Configuration Mode and advances through menu items b Used in Program Mode and peak recall c Used in Program Mode and valley recall d Accesses submenu...

Страница 10: ...AC DC Power Connector All models INPUT Input Connector All models TC PR Process RTD OUTPUT 1 Based on one of the following models Relay SPDT Solid State Relay Pulse Analog Output Voltage and Current...

Страница 11: ...c always use a Safety Agency Approved DC or AC source with the same Overvoltage Category and pollution degree as the standard AC unit 90 240 Vac The Safety European Standard EN61010 1 for measurement...

Страница 12: ...t Thermocouple and Thermocouple Type in the Input Type menu see Part 3 Figure 2 5 Thermocouple Wiring Hookup 8 TYPE Input Connector Jacket external insulation Terminal 1 Terminal 2 Extension Grade J R...

Страница 13: ...he lower supply current lead producing excellent lead resistance cancellation for balanced measurements The four wire RTD hookup is applicable to unbalanced lead resistance and enables the device to m...

Страница 14: ...wiring hookup for Process Voltage 0 100 mV 0 1 V 0 10 V Figure 2 8 a Process Voltage Wiring Hookup b Process Voltage Wiring Hookup with Sensor Excitation without Sensor Excitation RL Voltage limited...

Страница 15: ...uts Wiring Hookup Outputs Wiring Hookup This device may have a programmable communication output The RS 232 and RS 485 Output Connection are shown below Figure 2 10 a RS 232 Output Wiring Hookup b RS...

Страница 16: ...he up b button to scroll through flashing selections When a numerical value is displayed press this key to increase value of a parameter that is currently being modified Holding the b button down for...

Страница 17: ...3 2 Menu Configuration Figure 3 1 Flow Chart for ID and Set Points Menu 13...

Страница 18: ...e instrument will return to the Run Mode To change ID Code see ID Menu in the Configuration section ENTERING YOUR NON DEFAULT SET POINT ID SECURITY ID NUMBER Press a 5 Display shows SP1 Setpoint 1 Men...

Страница 19: ...point 1 value Press d 5 Display shows STRD stored message momentarily and then advance to SP2 only if a change was made otherwise press a to advance to SP2 Setpoint 2 Menu SETPOINT 2 Press d 6 Display...

Страница 20: ...s d 2 Display advance to INPT Input Menu Press a 3 Press and release a to scroll through all available menus of Configuration section If Analog Output Option is installed 52 53 or 54 the controller wi...

Страница 21: ...through the available selection to T flashing Press d 5 Display shows STRD stored message momentarily and then T not flashing Press d 6 Display flashes previous thermocouple type selection i e J see b...

Страница 22: ...ction i e 392 2 see below for RTD types selection Press b 7 Scroll through the available RTD types to the selection of your choice Press d 8 Display shows STRD stored message momentarily and then adva...

Страница 23: ...ows STRD stored message momentarily and then PROC not flashing Press d 6 Display flashes previous Process type selection i e 0 10 see below for Process types selection Press b 7 Scroll through the ava...

Страница 24: ...guration Menu Press d 4 Display advances to DEC Decimal Point DECIMAL POINT SUBMENU Press d 5 Display flashes previous selection for Decimal location Press b 6 Scroll though the available selections a...

Страница 25: ...ss b 12 Scroll though the available selections 0001 0002 0004 0008 0016 0032 0064 0128 Press d 13 Display shows STRD stored message momentarily only if change were made otherwise press a to advance to...

Страница 26: ...Input 1 value with 1st digit flashing Press b c 16 Use b and c buttons to enter IN1 value The IN1 value min input value conversion number Disregard the position of the decimal point 2000 counts may a...

Страница 27: ...Analog Output is available only if option board is factory installed If Analog Output Option is not installed the instrument will skip to Reading Adjust Menu Figure 3 5 Flow Chart for Analog Output R...

Страница 28: ...Display shows STRD stored message momentarily and then advances to RD1 Submenu only if it was changed otherwise press a to advance to RD1 Reading 1 Submenu READING 1 Press d 10 Display flashes 1st dig...

Страница 29: ...the Analog Output on 10 V FS scaled for 300 mV output range Rd1 0000 Out1 00 00 RD2 9999 Out2 00 30 The measured output will be as follows Rd1 0000 Out1 0 07 V Rd2 9999 Out2 0 23 V This means that for...

Страница 30: ...d message momentarily and then advances to SP DV Setpoint Deviation Menu Reading Offset Adjust allows the user to fine tune a minor error of the transducer however some applications may require a larg...

Страница 31: ...SP2 220 Moving SP1 to 300 the absolute value of SP2 becomes 320 Thermocouple Field Calibration Menu RTD and Process are perfectly calibrated This section is applicable to Thermocouple TC calibration o...

Страница 32: ...Submenu Latch Enabled Alarm remains latched until reset To reset already latched alarm select Alarm Latch Enable and press Max twice i e Disable and then go back to Latch or from a Run Mode push d twi...

Страница 33: ...es previous selection Press b to ABoV Above or BELo Below Press d 6 Display shows STRD stored message momentarily and then advances to DEAD Deadband DEADBAND SUBMENU Press d 7 Display shows 020 0 Dead...

Страница 34: ...ances to ____ with 1st under score flashing Press b c 5 Press b and c to enter your 4 digit ID Code number Press d 6 Display advances to CH ID Change ID Code Submenu If entered ID Code is incorrect di...

Страница 35: ...rity Level is Enabled and the user attempts to enter the Main Menu they will be prompted for an ID Code The ID Code should be correct to enter the instrument Menu item SETPOINT ID SECURITY LEVEL SUBME...

Страница 36: ...ed from an IBM PC compatible computer using software available at the website listed on the cover page of this manual or on the CD ROM enclosed with your shipment For complete instructions on the use...

Страница 37: ...D Baud Submenu BAUD SUBMENU Press d 6 Display flashes previous selection for BAUD value Press b 7 Scroll through the available selections 300_ 600_ 1200 2400 4800 9600 19 2K Press d 8 Display shows ST...

Страница 38: ...the available selections NO YES Press d 21 Display shows STRD stored message momentarily and then advances to _LF_ only if it was changed otherwise press a to advance to _LF_ Line Feed Submenu To sele...

Страница 39: ...he device must be accessed with an appropriate Address Value as selected in the Address Submenu described later Press d 28 Display flashes previous selection for Standard Press b 29 Scroll through the...

Страница 40: ...on about the data format At least one of the following suboptions must be enabled and hence output data to the Serial Bus This menu is applicable for Continuous Mode of RS 232 communication Press d 37...

Страница 41: ...Unit Submenu TEMPERATURE UNIT SUBMENU Includes a byte in the data string to indicate whether reading is in Celsius or Fahrenheit Press d 50 Display flashes previous selection for UNIT Press b 51 Scrol...

Страница 42: ...he RS 232 Serial Bus when the instrument is in Continuous Data Flow Mode Press d 58 Display flashes 1st digit of previous Transmit Time Value in seconds Press b c 59 Press b and c to enter new Transmi...

Страница 43: ...previous selection for Normal Color Press b 6 Scroll through the available selections GRN RED or AMBR Press d 7 Display shows STRD stored message momentarily and then advances to 1 CLR only if it was...

Страница 44: ...hat both Alarm1 SP1 and Alarm2 SP2 are triggered the Alarm values should be set in such a way that Alarm1 SP1 value is always on the top of Alarm2 SP2 value otherwise value of Alarm1 SP1 will overwrit...

Страница 45: ...TD Input ITS 68 3W VHQVRr 2 3 or 4 wire 0 00385 or 0 00392 curve Voltage Input 0 to 100 mV 0 to 1 V 0 to 10 Vdc Input Impedance 0 IRU P9 0 IRU RU 9GF Current Input 0 to 20 mA 5 ohm load Configuration...

Страница 46: ...ht i 8 Series 295 g 0 65 lb i 16 Series 159 g 0 35 lb i 32 Series 127 g 0 28 lb 42 ALARM 1 2 Programmable to display color change Relay 250 Vac or 30 Vdc 3 A Resistive Load configurable for on off PID...

Страница 47: ...4 3 2 3 04 1 04 2 0 1 0 C D 3E6F C 2 0 1 0 204 1 04 2 3 04 1 04 0 1 0 C D E6F C 0 1 0 04 1 04 3 204 1 04 2 0 1 0 3 E6F C D 2 0 1 0 E6F C 204 1 04 2 33 04 1 04 E6B GD 3 20 120 E6B G 3 2 304 1 04 0 1 0...

Страница 48: ...0 123 204 5 673 04 89 7 2 7 7 0 0 12 3 04 56 0 52 3 40 56 0 52 3 40 56 7 052 7 8 9 0 7 852 7 852 7 8 9 9 9 A 2B99 C D E D 8 9 7 8 9AC 8 9 7 8 9AC 8 9...

Страница 49: ...ive ACtV Above AbOV Deadband dEAd 020 0 ID ID Value 0000 Full ID FULL Disable dSbL Set Point ID Id SP Disable dSbL Communication Parameters Baud Rate bAUd 9600 Parity PRtY Odd Data bit dAtA 7 bit Stop...

Страница 50: ...circuits not directly connected to the Mains Supply power Maximum Line to Neutral working voltage is 50Vac dc This unit should not be used in Measurement Categories II III IV Transients Overvoltage Su...

Страница 51: ...NOTES 46...

Страница 52: ...A if the unit is found to be defective it will be repaired or replaced at no charge OMEGA s WARRANTY does not apply to defects resulting from any action of the purchaser including but not limited to m...

Страница 53: ...r Velocity Indicators Turbine Paddlewheel Systems Totalizers Batch Controllers pH CONDUCTIVITY pH Electrodes Testers Accessories Benchtop Laboratory Meters Controllers Calibrators Simulators Pumps Ind...

Отзывы: