Position. 

 FTB8000B and FTB8000HW Series meters should 

be installed horizontally with the register up. Vertical mount-

ing  will  result  in  some  degree  of  under-measurement  and 

shortened life of the bearings. No upstream straight pipe is 

required.

Couplings. 

 Male NPT threaded couplings are included with 

each  meter.  The  threads  on  the  end  of  the  meter  are  IPS 

straight threads one size bigger than the meter size. Though 

it is possible to thread a standard pipe coupling directly onto 

the meter for close coupling, the included couplings are much 

preferable because they provide a union connection for meter 

service. Be sure to use the included gasket between the end 

of the meter and the coupling.

Connections. 

 PR and PT sensors are supplied with a color 

coded output cable (see diagram, page 4). Optional connec-

tors can be ordered to plug directly into an Omega control or 

LMI metering pump. 

WARNING

DO NOT INSTALL

meTeR IN OveRHeAD

INDOOR PIPING OR 

WHeRe LeAkAGe 

mAy CAuSe DAmAGe

GeNeRAL INFORmATION, INSTALLATION and mAINTeNANCe

Page 2

GeNeRAL INFORmATION

 

FTB8000B (cold water) and FTB8000HW Series (hot water) 

meters use the internationally-accepted multi-jet principle. A 

gear train drives the register totalizer dials. For pulse output, 

one of the pointers is replaced by a magnet arm, which is 

detected by an encapsulated sensor attached to the outside 

of the lens.

PR

 meters use a solid-state, long-lasting Hall-effect sensor, 

which requires power. They are suited for use with Omega 

controls and metering pumps (LMI for instance) that have 

sensor power.

PT

 meters use a reed switch. They provide a dry contact clo-

sure and do not require power.

Standard

  meters  do  not  have  a  sensor,  and  they  totalize 

only. 

SPeCIFICATIONS*

6 mA at 12 Vdc (PR only)

105˚ F (40˚ C) max (8000B version)

194˚ F (90˚ C) max (8000HW version)

150 psi operating

Cast bronze, epoxy powder coated inside and out

Engineered thermoplastic

Alnico

+/-  1.5% of reading

 

PR 

PT 

Standard

  Hall-effect 

Reed switch  Totalizer only

 

20 mA 

20 mA 

n/a

 

24 Vdc 

24 Vdc or Vac 

n/a

12’ (4 m) standard (2000’ maximum run)

  3/4” 

1” 

1-1/2” 

2”

  0.22 

0.44 

0.88 

1.98

 

22 

52 

88 

132

Power

Temperature

 

Cold Water

 

Hot Water

Pressure

materials Body

 

Internals

 

magnet

Accuracy

Pulse Output
 

Sensor

 

max Current

 

max voltage

Cable Length

Flow Rates (GPm)

 

minimum

           **maximum

INSTALLATION

Pulse  Output.

    Both  PR  and  PT  sensors  respond  to 

a  magnet  that  rotates  on  the  face  of  the  meter  under 

the  lens.  The  sensor  turns  on  and  off  once  each  time  

the magnet passes under it. Sensors are designed for elec-

tronic control loads, and should not be used to switch power 

loads  or  line  voltages.  See  maximum  current  and  voltage 

ratings, under Specifications.

mAINTeNANCe

Omega recommends all service to be performed by an autho-

rized distributor or the factory to maintain the integrity of the 

protective tamper-proof wire-and-seal. 

Inlet Strainer.

  Clean the strainer yearly, or as required, de

-

pending on water condition. Pull out the strainer or backflush 

the meter to loosen trapped particulates.

Calibration.

    Meters  used  for  billing  or  billing  exemp

-

tion  may  be  regulated  by  state  or  local  authorities.    New 

meters  are  factory-tested  to  meet  the  AWWA  C-708 

Multi-Jet  Meter  accuracy  specification.  Some  states  

require retesting at various intervals, typically eight years for 

3/4" meters, six for 1", and four for 1-1/2" and 2".  Meters 

used for control should be tested every 5-10 years. Testing 

can be done by the factory or local meter shops authorized 

for this purpose.  

Please  contact  Omega  before  sending 

meter in for calibration or servicing.

**CAuTION: 

Excessive flow can cause breakage.

 

Do not exceed recommended maximums.

Caution: 

These water meters are 

not recommended for installation 

in  uninsulated  suspended  ceil-

ings where freezing is possible, 

or in any overhead indoor piping 

configuration where leakage may 

cause damage.

*Specifications subject to change.

Содержание FTB8000B

Страница 1: ...FTB8000B FTB8000HW Pulse Meter User sGuide Shop online at omega com email Info omega com For latest product manuals omegamanual Info Hot Water Cold Water ...

Страница 2: ... 78280 Guyancourt France TEL 33 0 1 61 37 2900 FAX 33 0 1 30 57 5427 Toll Free in France 0800 466 342 e mail sales omega fr Germany Austria Daimlerstrasse 26 D 75392 Deckenpfronn Germany TEL 49 0 7056 9398 0 FAX 49 0 7056 9398 29 Toll Free in Germany 0800 639 7678 e mail info omega de United Kingdom One Omega Drive River Bend Technology Centre ISO 9002 Certified Northbank Irlam Manchester M44 5BD ...

Страница 3: ...Cast bronze epoxy powder coated inside and out Engineered thermoplastic Alnico 1 5 of reading PR PT Standard Hall effect Reed switch Totalizer only 20 mA 20 mA n a 24 Vdc 24 Vdc or Vac n a 12 4 m standard 2000 maximum run 3 4 1 1 1 2 2 0 22 0 44 0 88 1 98 22 52 88 132 Power Temperature Cold Water Hot Water Pressure Materials Body Internals Magnet Accuracy Pulse Output Sensor Max Current Max Voltag...

Страница 4: ...et pointer off its shaft and remove the plain pointer from the target dial Reverse their positions and press them firmly into place Securely seat the sealing ring and replace the lens matching the tab on the lens to the notch on the meter to align the sensor with the magnetic pointer dial Thread the meter top on and tighten NOTE A special magnet available from the factory is required to achieve a ...

Страница 5: ...1476 10 Internal Strainer 31518 31518 11 Tubular Strainer 31498 31499 Internal Parts Replacement All of the internal parts of an FTB8000B or FTB8000HW Series meter lift out as a unit after the top has been unscrewed The lens can then be removed and the internal assembly lifted out If neces sary turn the meter upside down and tap one end lightly on a countertop to loosen the internals The assembly ...

Страница 6: ...nge Pin Assembly 32243 32243 2 Lens Gasket Assembly 32221 32221 3 a Internal Assembly gallons 32239 32240 b Internal Assembly cubic feet 32235 32236 4 Coupling Assembly incl 2 sets 32217 32218 5 Coupling Gasket Assembly incl 2 32213 32214 6 Lens 31471 31471 7 Sensor Screw 31519 31519 a Single Reed Switch Sensor PT 31444 31444 b Double Reed Switch Sensor PT 31457 31457 8 c Single Hall Effect Sensor...

Страница 7: ... otherwise shall not exceed the purchase price of the component upon which liability is based In no event shall OMEGA be liable for consequential incidental or special damages CONDITIONS Equipment sold by OMEGA is not intended to be used nor shall it be used 1 as a Basic Component under 10 CFR 21 NRC used in or with any nuclear installation or activity or 2 in medical applications or used on human...

Страница 8: ...bine Paddlewheel Systems Totalizers Batch Controllers pH CONDUCTIVITY pH Electrodes Testers Accessories Benchtop Laboratory Meters Controllers Calibrators Simulators Pumps Industrial pH Conductivity Equipment DATA ACQUISITION Data Acquisition Engineering Software Communications Based Acquisition Systems Plug in Cards for Apple IBM Compatibles Datalogging Systems Recorders Printers Plotters HEATERS...

Отзывы: