FMG490 INSTRUCTIONS

Page 21 

OPERATION

The FMG490 has a passcode system for restricting access 

to the menus. The meter comes  from the factory with the 

passcode set to 000000. When a user attempts to enter the 

menu system (see details on page 20), the passcode entry 

screen will be displayed.

The default passcode is 000000. If a different passcode has 

previously been set, then the user must enter that passcode 

at this time. After entering the passcode, or leaving it at 

000000 if using the default passcode, the user does the tap 

and hold sequence to move into the menu system.

To change the passcode

, you must use the 

THIRD MENU

 

screen. Access the 

THIRD MENU

 screen as follows:

• Enter the main menu system, as described above.

• On the main menu, tab over to the EXIT tab and tap

the 

 five times. A 

SUBMENU screen will display.

• On the SUBMENU screen tab over to the EXIT tab and

tap the 

 five times. The THIRD MENU screen will

display.

• To set the passcode, hold and tap and then use the

 and   to enter the new code. 

• Hold and tap again to return to the THIRD MENU

screen

• Tab to EXIT, and then hold and tap to return to the

SUBMENU.

To change the number of decimal places in the total

• To set the decimal point, hold and tap on SETD and then

use the   to move the decimal point.

• Hold and tap again to return to the THIRD MENU screen.
• Tab to EXIT, and then hold and tap to return to the

SUBMENU.

000000

ENTER PASSCODE

PRESS     AND    TO CHANGE

1.2345678

100

TOTAL

CU FT

X1000

RATE

GPM

T UNIT

R UNIT SET  P DAMP

SET  4

SET  4 SET 20

SET 20 SET  F

SET  F

EXIT

TOTAL = GALLONS

PRESS       +

TO SET TOTAL

UNITS FOR DISPLAY

T UNIT R UNIT SET  P DAMP

SET  4

SET  4

SET 20

SET 20

SET  F

SET  F

EXIT

TOTAL:

        PRESS      TO CHANGE

GALLONS

0.0000000

     SET    ID

TOTAL

ACRE

FEET

RATE

GPM

OK

FORWARD TOTAL

FORWARD TOTAL

 

INFO

 COMM MBID

FL DIR

SAMP

HPOLL

FOUT

EXIT

PRESS 

+

 TO VIEW INFO

ABOUT METER

 

SETCD

PRESS 

+

 TO SET

SAMP

FOUT

EXIT

000000

PASSCODE

 SETD  PDAMP TEST

To Change a Passcode and Decimal Places

PDAMP

PDAMP is used to view or change the number of samples 

for rolling average of pulse output.

TEST

TEST allows the user to initiate a fully functional, artificial flow 

rate for the purpose of testing other connected equipment. 

When TEST is applied, all features of the meter will function at 

the stated flow rate (in gallons per second).  
For TEST to function, the meter must be filled (not EMPTY 

PIPE).  
To enter a value into the TEST feature, navigate to the TEST 

tab and enter a flow rate value in the VAL screen (in gallons 

per second only,) then 

 

to the VAL box and   to the ON 

screen.  This will initiate the TEST feature.  The next   would 

bring you to the OFF screen, but you can ‘hold and tap’ 

the arrows to return you to the sub menu while the feature 

operates.
 

After use, the TEST feature must be turned OFF. 

If the TEST 

feature is not turned OFF, the stated static flow rate (in gallons 

per second) will be shown any time the meter is full or in a 

flowing condition. Flow values recorded by the meter while 

the TEST feature is operating are permanently recorded in the 

displayed TOTAL.  It may be useful to note that these values 

are only written to permanent memory every 15 minutes and 

cycling all power within this 15 minute time frame will return 

the meter to its previous total.

Power Indicators

A power indicator is displayed in the lower left of the main 

display window.
Any meter powered from an external power source will 

display a power plug icon when running on external power. 

If the connection to external power is lost, the meter will 

switch to the backup battery and the power icon will switch 

to a battery symbol.

OK

 on the battery indicator means battery voltage is above 

6.4 volts.

LO

 on the battery indicator means the battery is low and 

should be replaced soon.

OK

LO

P

OK

LO

Being powered by external 

DC or AC

Being powered by battery -

voltage is sufficient

Being powered by battery - 

voltage is low

1.2345678

   

   100

TOTAL

CU FT

X1000

RATE

GPM

T UNIT

R UNIT SET  P DAMP

SET  4

SET  4

SET 20

SET 20

SET  F

SET  F

EXIT

TOTAL = GALLONS

PRESS       +       TO SET TOTAL

UNITS FOR DISPLAY

T UNIT R UNIT SET  P DAMP

SET  4

SET  4

SET 20

SET 20

SET  F

SET  F

EXIT

TOTAL:

        PRESS      TO CHANGE

GALLONS

0.0000000

     SET    ID

TOTAL

ACRE

FEET

RATE

GPM

OK

FORWARD TOTAL

FORWARD TOTAL

P

If display reads,  ‘BATT END’

 replace battery immediately.

Содержание FMG490 Series

Страница 1: ...e mail info omega com For latest product manuals omega com en us pdf manuals XXXXXX Xxxxx Xxxxxxxx Shop online at omega com User sGuide TM FMG490 SERIES Municipal Industrial Magmeter...

Страница 2: ...ns without notice omega com info omega com Servicing North America U S A Omega Engineering Inc 800 Connecticut Ave Suite 5N01 Norwalk CT 06854 Headquarters Toll Free 1 800 826 6342 USA Canada only Cus...

Страница 3: ...onfiguration Sourcing Mode Output Application Page 16 Sinking Mode Output Application Page 16 Analog 4 20mA Current Loop Output Application Page 16 Cable Shield Page 17 Pulse Output Page 17 Analog 4 2...

Страница 4: ...t flow batch forward flow and batch reverse flow Batch totals can be reset Built in data logging is available as an option for secure flow logging Scaled pulse output is standard and one additional ou...

Страница 5: ...gal Cubic Meters Cubic Meters x 1000 Cubic Feet Cubic Feet x 1000 Second Foot Day Million Cubic Feet Acre Feet Acre Inches Imperial Gallons Imperial Gallons x 1000 Million Imperial Gallons Fluid Ounce...

Страница 6: ...ter Size L H T ID Shipping Weight inch mm inch mm inch mm inch mm lbs Kg 3 12 25 311 7 08 179 8 68 17 25 2 6 66 04 40 18 4 10 12 257 8 3 211 62 15 7 3 12 79 43 19 5 6 12 09 307 9 1 231 69 17 5 5 05 12...

Страница 7: ...0 6 8 10 FMG490 Accuracy Pipe Size Inches in diameter 3 4 6 8 10 12 Max Flow Rate Gallons Minute 723 1285 2891 5140 8031 11565 Cut off min Flow Rate Gallons Minute 3 62 6 43 14 46 25 70 40 15 57 82 M...

Страница 8: ...ing Flow Propeller Meter Partially Open Butterfly Valve 1X 1X 1X 1X Swirling Flow NOTE These configurations are to be used as general guidelines and do not cover every possible installation A combinat...

Страница 9: ...ent on the electrodes can affect accuracy Recommended Improved accuracy results from unimpeded electrodes Electrode moved from top by rotating meter Intermittent air bubbles miss electrode Electrodes...

Страница 10: ...er ANSI 150 lb flanges See table on page 11 for flange bolt tightening torque specifications Calibration The FMG490 meters are factory calibrated and will not require any form of field calibration Che...

Страница 11: ...tem must be grounded to meet national and local electrical safety codes Failure to do so can result in electrocution Equalization Lug Meter Flange Pipe Flange Gasket Pipe Flange Flange Plate Lockwashe...

Страница 12: ...e 1 Cable Gland Opening and Sealing The display is available in either DC or AC versions DC version AC Version If the meter is configured with AC power one of the additional Power Output cable ports m...

Страница 13: ...latory agency approval If installed outdoors or less than 33ft 10m from a utility power service entrance AC power should be supplied via a properly grounded surge suppression device 10 Remove the plug...

Страница 14: ...sensor cable inside the internal strain relief clip and tighten the cable gland sealing nut securely torque strain relief sealing gland dome nut to 22 in lbs A lose nut could cause moisture ingress an...

Страница 15: ...ange R Remote B pn11 Blue R Remote A pn12 Black C1 DC pn14 Red C1 DC pn15 WARNING BACKUP BATTERIES ARE NOT INTENDED AS A PRIMARY POWER SOURCE OF A MAINS DC or AC CONFIGURED METER Remove the 3 screws h...

Страница 16: ...D5L D6L RED C1 BLACK C1 BLUE R ORNG R BLACK R RED R BLUE C1 ORNG C1 GREEN C1 WHITE C1 A5N A6N RED INT BLACK INT BLUE R ORNG R BLACK R RED R GREEN C1 WHITE C1 A5L A6L RED INT BLACK INT BLUE R ORNG R BL...

Страница 17: ...pplication Sinking Mode Recommended for Rin 30k Analog 4 20mA Current Loop Output Application Minimum resistor value is 100 x Vs ohms Higher resistances maybe used depending on frequency and cable len...

Страница 18: ...units totaled per pulse all sizes of meters can be configured with the same SETP values For example if your rate is chosen as gallons per minute GPM the table below applies If your rate is different...

Страница 19: ...perform the hold and tap sequence When finished making changes When you are finished making changes move to the EXIT tab using the right button To return to the HOME screen perform the hold and tap s...

Страница 20: ...g average SET 4 View or change flow rate corresponding to 4mA SET 20 View or change flow rate corresponding to 20mA EXIT Return to HOME SCREEN or enter SUBMENU T UNIT R UNIT SET P DAMP SET 4 SET 20 SE...

Страница 21: ...the number of samples for rolling average of pulse output TEST TEST allows the user to initiate a fully functional artificial flow rate for the purpose of testing other connected equipment When TEST i...

Страница 22: ...correct but pulse frequency output is low erratic or absent Wiring incorrect Compare wiring with appropriate wiring recommendations External device input impedance too low Use sourcing rather than sin...

Страница 23: ...nation by OMEGA if the unit is found to be defective it will be repaired or replaced at no charge OMEGA s WARRANTY does not apply to defects resulting from any action of the purchaser including but no...

Страница 24: ...as Mass Flowmeters Flow Computers Air Velocity Indicators Turbine Paddlewheel Systems Totalizers Batch Controllers pH CONDUCTIVITY pH Electrodes Testers Accessories Benchtop Laboratory Meters Controll...

Отзывы: