7
Section 2.5 - UL Installation Requirements
Use 60/75°C copper conducters only
For use only in pollution degree 2 or better
Max. ambient temperature - 60°C
Max. wire size - AWG 26-14
UL file number - E231911
Section 2.6 - Calibration and Adjustment
During calibration and adjustment, the measuring and connection of external
voltages must be carried out according to the specifications of this manual. The
technician must use tools and instruments that are safe to use.
Section 2.7 - Normal Operation
Operators are only allowed to adjust and operate devices that are safely fixed in
panels, etc., thus avoiding the danger of personal injury and damage. This means there
is no electrical shock hazard, and the device is easily accessible.
Instructions
2
Section 2.8 - Cleaning
When disconnected, the device may be cleaned with a cloth moistened with distilled
water.
Section 2.9 - Liability
To the extent that the instructions in this manual are not strictly observed, the custom -
er cannot advance a demand against PR electronics A/S that would otherwise exist
according to the concluded sales agreement.