FLOW CHART

CONFIGURATION

MENU 

Mode:

Flashing display in MENU Mode means you can make your
selection by pressing 

b

button. If the flashing display is not

a four digit value, pressing 

c

button will always direct the

instrument one step backward of the top menu item. The
second push on the 

c

button will reset the instrument

except after the setpoint and the alarms, that will go to the
RUN Mode without resetting the instrument. The 

a

button

will always sequence the instrument thru the menu items.

The 

d

button has two functions:

1.

To save a selected flashing display

2.

To direct the instrument to the next submenu level

RUN 

Mode:

b

causes the display to flash the PEAK with the 
corresponding value. Press again to go back to RUN 
Mode.

c

causes the display to flash VALLEY with the 
corresponding value. Press again to go back to RUN 
Mode.

d

causes flashing PEAK or VALLEY to reset corresponding
values. Press 

d

one more time to go back to RUN Mode.

OPERATION - (For Thermocouple Input)

Step 1. Apply Power to the Instrument

When your device is first powered up it will display the
ambient temperature (assume 75°F).

Step 2. Enter Setpoint 1 Menu

Press 

a

one time from run mode to get to 

SP1

Setpoint 1. 

Step 3. Enter the Setpoint 1 Value Submenu

Press 

d

. Display shows the previous selection of Setpoint 1.

Step 4. Change the Setpoint 1 Value 

Press 

b

or 

c

until desired value is displayed.

Step 5. Store the Setpoint 1 Value 

Set the Setpoint 1 to 10 degree higher than Process value
(SP1 = 85) and press 

d

to store, display flashes 

STRD

message and advances to 

SP2

Setpoint 2 Menu.

Step 6. Store the Setpoint 2 value

Repeat steps 3 and 4. Set the Setpoint 2 to 5 degree higher
than Process value (SP2 =  80) and press 

d

to store,

display flashes 

STRD

message and advances to 

CNFG

Configuration Menu.

Step 7. Enter the Input Type Menu

Press 

d

to enter 

INPT

Input Type Menu.

Step 8. Enter to the submenu items of Input Menu

Press 

d

to display Input: Process, RTD or Thermocouple. 

If flashing 

T.ç

is displayed press 

a

and proceed to step 11.

Step 9. Scroll through available selection of Input Menu

Press 

b

until a flashing 

T.ç

for Thermocouple is displayed.

Disassembly instruction:

If necessary, the unit may be removed from the panel and
opened.

Warning: Disconnect all ac power from the unit
before proceeding.

1.

Make sure the AC power is disconnected.

2.

Remove all wiring connections from the rear of the meter.
To remove power and input connectors squeeze top and
bottom of the case near the connector site for release,
then pull connectors from the meter.

3.

To remove meter from the case, squeeze top and bottom
of the bezel to release, then pull from case.

WIRING

Wire the instrument according to the figure shown below.

Warning: Do not connect ac power to your
device until you have completed all input and
output connections. This device must only be
installed by a specially trained electrician with
corresponding qualifications. Failure to follow
all instructions and warnings may result in injury!

Connect the main power connections as shown in the figure below.

FUSEConnector Output Type For 115Vac  For 230Vac

DC

FUSE 1

Output 1

Relay

3 A(T)

3 A(T)

FUSE 2

Output 2 

Relay 

3 A(T) 

3 A(T) 

-

FUSE 3

Power 

N/A

100 mA(T) 

100 mA(T)  100 mA(T)

FUSE 4

Power

N/A

N/A

N/A

400 mA(T)

Output 1 and 2 are for -AL Alarm Option only.

8

1

7

6

5

4

3

2

4     5     6

1/4  2/5  3/6

1/4  2/5  3/6

1/4  2/5  3/6

This Quick Start Reference provides information 
on setting up your instrument for basic operation. 
The latest complete Communication and Operational
Manual as well as free Software and ActiveX Controls
are available at 

www.omega.com/specs/iseries or on

the CD-ROM enclosed with your shipment

.

SAFETY CONSIDERATION

This device is marked with the international
Caution symbol.

The instrument is a panel mount device protected in
accordance with EN61010-1:2001. Remember that the unit
has no power-on switch. Building installation should include
a switch or circuit-breaker that must be compliant to IEC
947-1 and 947-3.

SAFETY:

• Do not exceed voltage rating on the label located on 

the top of the instrument housing.

• Always disconnect power before changing signal and 

power connections.

• Do not use this instrument on a work bench without 

its case for safety reason.

• Do not operate this instrument in flammable or 

explosive atmospheres.

• Do not expose this instrument to rain or moisture.

EMC:

• Whenever EMC is an issue, always use shielded cables. 
• Never run signal and power wires in the same conduit.
• Use signal wire connections with twisted-pair cables.
• Install Ferrite Bead(s) on signal wire close to the 

instrument if EMC problems persist. 

MOUNTING

Panel Mounting Instruction:

1.

Using the dimensions from the panel cutout diagram 
shown above, cut an opening in the panel.

2.

Insert the unit into the opening from the front of the panel,
so the gasket seals between the bezel and the front of the
panel.

3.

Slide the retainer over the rear of the case and tighten 
against the backside of the mounting panel.

C

F

2

1

C

F

2

1

_____

Underline denotes factory default setup

START HERE

ANLG

Only if unit

has 52, 53

or 54 

Analog Opt.

Only if unit

does not have

52, 53 or 54 

Analog Option.

DEAD

020.0

DEAD

020.0