CND3 Series Temperature Controller

 

 

Warning

 

DANGER! Caution! Electric Shock!

 When the power is on, DO NOT touch the AC terminals in case 

an electric shock may occur. Make sure the power is disconnected when you check the input power 
supply. 

1. 

Prevent dust or metallic debris from falling into the controller and cause malfunctions. DO NOT modify or uninstall 
the controller. 

2. 

CND3 controller is an open-type device. Make sure it is installed in an enclosure free of dust and humidity in case of 
an electric shock. 

3. 

Wait for one minute after the power is switched off to allow the capacitor to discharge. DO NOT touch the internal 
wiring within this period of time. 

 

Display, LED & Keys

 

 Ordering Information

 

Series 

Omega CND3 series temperature controller

 

Panel size 

04: 1/4 DIN 
08: 1/8 DIN 

16: 1/16 DIN 

  Output 1 

R: Relay 

  M: Linear mA 

S: Voltage Pulse 

  L: Linear voltage 

  Output 2 

R: Relay 

  M: Linear mA 

  blank: none 

S: Voltage Pulse 

  L: Linear voltage 

  Option 1 

1U: 1 User input   
2U: 2 User inputs 
1C: 1 CT input 
2C: 2 CT inputs 
RT: Retransmission output 
RS: Remote Setup Input 
UC: User input + CT input 

RR: Retrainsm Remote 
Setup input 
UR: User input + Retransmission 
output 
US: User input + Remote Setup 
input 
CR: CT input + Retrainsmission 
output 
CS: CT input + Remote Setup input 
blank: none 

  Option 2 

CM: RS-485 Communication    blank: none 

  Power 

AC: AC 100 to 240V 

  DC: DC 24V 

 

Specifications

 

Input power supply 

AC 100 to 240 V, 50/60Hz, DC 24 V ±10% 

Display method 

LCD. Present temperature: yellow, Set temperature: green 

Input sensors 

Thermocouple: K, J, T, E, N, R, S, B, L, U, TXK 
Platinum RTD: Pt100, JPt100 
Resistance: Cu50, Ni120 
Analog input: 0 to 5 V, 0 to 10 V, 0 to 20 mA, 4 to 20 mA, 0 to 50 mV 

Control modes 

PID, PID programmable, Fuzzy, Self-tuning, manual, ON/OFF 

Display accuracy 

0 or 1 digit to the right of the decimal point 

Sampling rate 

Analog input: 0.1s, Thermocouple or platinum RTD: 0.1s 

Ambient temperature 

0 to +50°C 

Ambient humidity 

35 to 80% RH (non-condensing) 

 

Parameters Operation

 

Regulation Mode 

Operation Mode 

Initial Setting Mode 

  Auto-tuning (Set in PID 

control and RUN mode)     
Press 

 

 

  Use 

  to set up target 

temperature 

  Press 

  Set up input type 

Press 

  Self-tuning switch (set 

when in PID control and the 
TUNE parameter = ST) 

  Control loop RUN or 

STOP 

  Set up temperature unit 

(not displayed when in analog 
input)     

Regulation Mode 

Operation Mode 

Initial Setting Mode 

  Select the n

th

 (n = 0 ~ 5) 

PID. When n = AUTO, PID is 
auto-selected. 

  Set up start pattern (when in 

PID programmable control and 

  Set up upper temperature 

limit 

  Set up PID control offset 

  Set up start step (when in 

programmable control) 

  Set up lower temperature 

limit 

  Set up Fuzzy gain value 

  Set up the position of 

decimal point 

  Select control modes 

  Set up Fuzzy Deadband 

  Lock the keys 

  Select SV control modes 

  Adjust Output 1 hysteresis 

(when in ON/OFF control) 

  Set up upper limit of Alarm 1 

  Set up waiting 

temperature (when in 
programmable control) 

  Adjust Output 2 hysteresis 

(when in ON/OFF control) 

  Set up lower limit of Alarm 1 

  Set up waiting time (when 

in programmable control) 

  Control cycle for 

Output 1 (except in ON/OFF 
control)

 

  Set up upper limit of Alarm 2 

  Set up start slope (when 

in programmable control) 

  Control cycle for 

Output 2 

(except in ON/OFF control) 

  Set up lower limit of Alarm 2 

  Select pattern to be edited 

  Ratio of Output 1 against 

Output 2 when in dual output 
control (set when in PID and dual 
output control) 

  Set up upper limit of Alarm 3 

  Select AT or ST 

  Set up deadband 

(when in dual output)   

  Set up lower limit of Alarm 3 

  Select heating, cooling or 

dual output heating and cooling 

  Set up input filter factor 

  Record highest 

temperature of Alarm 1 

  Set up Alarm 

1 mode 

  Set up input filter range 

  Record lowest 

temperature of Alarm 1 

  Set up Alarm 

1 options 

  Adjust input compensation 

  Record highest 

temperature of Alarm 2 

  Set up Alarm 

1 delay 

  Adjust input gain 

  Record lowest 

temperature of Alarm 2 

  PV color change 

  Set up rising slope (when 

CRTS = SLOP) 

  Record highest 

temperature of Alarm 3 

  2PID Switch temperature 

  Adjust upper limit 

compensation for analog Output 
1* 

  Record lowest 

temperature of Alarm 3 

  2PID Reset temperature 

  Adjust lower limit 

compensation for analog Output 
1* 

  Display and adjust Output 1 

volume 

  Set up Remote type 

  Adjust upper limit 

compensation for analog Output 
2* 

  Display and adjust Output 2 

volume 

  Select auxiliary function 1 

  Adjust lower limit 

compensation for analog Output 
2* 

  Set up percentage of upper 

limit for Output 1 

  Select auxiliary function 2 

  Adjust upper limit 

compensation for Retransmission* 

  Set up percentage of lower 

limit for Output 1 

  Enable/disable 

communication write-in 

  Adjust lower limit 

compensation for Retransmission* 

  Set up percentage of upper 

limit for Output 2 

  Select ASCII or RTU 

format 

  Adjust Remote gain 

  Set up percentage of lower 

limit for Output 2 

  Set up communication 

address 

  Adjust Remote 

compensation 

  Display current measured at 

CT1 

  Set up baudrate 

  Remote lower limit 

adjustment 

  Display current measured at 

CT2 
Press 

  to return to set up 

target 

temperature 

  Set up data length 

  Remote higher limit 

adjustment 

  Set up stop bit 

  Set up EVENT1 function 

  Set up parity bit 

Press 

  to return to set up 

input type 

  Set up EVENT2 function 
  Set up EVENT3 function 

Press 

  to return to auto-tuning 

*

1 scale = 2μA; 1scale = 1mV 

PID mode: Any of the 6 PID groups can be selected. When n = AUTO, the program will automatically select 
the PID group that is the closest to the target temperature. 

  Select the n

th

 PID (n = 0 ~ 

5) 

Press 

0 ~ 5

th

 PID 

  Set up the 0

th

 PID 

temperature value     
Press 

  Set up the 5

th

 PID 

temperature value     
Press 

  Set up the 0

th

 proportional 

  band value 

  Set up the 5

th

 proportional 

band value 

  Set up the 0

th

 Ti value 

  Set up the 5

th

 Ti value 

  Set up the 0

th

 Td value 

  Set up the 5

th

 Td value 

  Set up the 0

th

 PID integral 

deviation 

Press 

  to return to PID 

deviation 

  Set up the 5

th

 PID integral 

deviation 

Press 

  to return to PID 

deviation 

 

Alarm Outputs

 

CND3 offers 3 alarm outputs, and each alarm output has 20 alarm modes to choose from in the initial setting mode. 
When the target temperature exceeds or falls below the set point, the alarm output will be enabled. 

SV 

Alarm mode 

Alarm output operation 

No alarm 

Alarm output will be enabled when the temperature reaches upper or 
lower limit: The alarm will be enable when the PV exceeds SV + AL-H 
or falls below SV – AL-L. 

Alarm output will be enabled when the temperature reaches the upper 
limit: The alarm will be enabled when the PV exceeds SV + AL-H. 

ON

OFF

SV

 

SV+(AL-H)

Alarm output will be enabled when the temperature reaches the lower 
limit: The alarm will be enabled when the PV falls below SV – AL-L. 

ON

OFF

SV-(AL-L)

SV

Alarm output will be enabled when the temperature reaches the 
absolute value of the upper or lower limit: The alarm will be enabled 
when the PV exceeds AL-H or falls below AL-L. 

ON

OFF

AL-L

AL-H

Alarm output will be enabled when the temperature reaches the 
absolute value of the upper limit: The alarm will be enabled when the 
PV exceeds AL-H. 

ON

OFF

AL-H

Alarm output will be enabled when the temperature reaches the 
absolute value of the lower limit: The alarm will be enabled when the 
PV falls below AL-L. 

ON

OFF

AL-L

Upper limit hysteresis alarm: The alarm will be enabled when the PV 
exceeds SV + AL-H. The alarm will be disabled when the PV falls 
below SV + AL-L. 

Lower limit hysteresis alarm: The alarm will be enabled when the PV 
falls below SV – AL-H. The alarm will be disabled when the PV 
exceeds SV – AL-L. 

Offline alarm: The alarm will be enabled when the input sensor is not 
correct or offline. 

10 

Timing alarm 

11 

CT1 alarm: The alarm will be enabled when the CT1 value falls below 
AL-L or exceeds AL-H. 

ON

OFF

AL-L

AL-H

12 

CT2 alarm: The alarm will be enabled when the CT2 value falls below 
AL-L or exceeds AL-H. 

¾

 

RS485 Communication

 

CND3 supports baudrate 2,400 to 38,400 bps, Modbus ASCII/RTU protocol, function code 03H and reads 
maximum 8 words from the register. 

Address 

Content 

Definition 

1000H  Present value (PV) 

Measuring unit: 0.1 scale. The following values read mean 
error occurs. 
8002H: Temperature not yet acquired 
8003H: Not connected to sensor 
8004H: Incorrect sensor 

1001H  Set value (SV) 

Measuring unit: 0.1 scale. 

1002H 

Upper limit of temp. 
range 

Cannot exceed the default value 

1003H 

Lower limit of temp. 
range 

Cannot fall below the default value 

1005H  Control mode 

0: PID, 1: ON/OFF, 2: Manual, 3: FUZZY 

1006H 

Heating/cooling control 

0: Heating/ Heating, 1: Cooling/ Heating, 2: Heating/cooling, 3: 
Cooling/ Cooling 

1007H 

1

st

 heating/cooling control 

cycle 

0.1 ~ 99.0 sec. 

1008H 

2

nd

 heating/cooling control 

cycle 

0.1 ~ 99.0 sec. 

1009H  Proportional band (PB) 

0.1 ~ 999.9 

100AH  Ti value 

0 ~ 9,999 

100BH  Td value 

0 ~ 9,999 

1012H 

Read/write Output 1 
volume 

Unit: 0.1%, only valid in manual control mode 

1013H 

Read/write Output 2 
volume 

Unit: 0.1%, only valid in manual control mode 

1016H  Regulated temp. value 

-99.9 ~ +99.9, Unit: 0.1 

102AH  Read/write LED status 

b0: ALM3, b1: ALM2, b2: °F, b3: °C, b4: ALM1, b5: OUT2, b6: 
OUT1, b7: AT 

102BH  Read/write key status 

b0: Set, b1: Select, b2: Up, b3: Down, 0: Press it 

102CH  Panel lockup status 

0: Normal, 1: Fully locked, 2: SV adjustable 

102DH  CT value 

Unit: 0.1A 

103BH  AT setting 

0

OFF(default), 1

ON 

103CH  Control RUN/STOP 

setting 

0 : STOP, 1

RUN (default), 2 : END (program), 3 : HOLD 

(program) 

 Panel Cutout

 

Model 

Panel cutout ( W × H ) 

1/16 DIN 

45mm × 45mm 

1/8 DIN 

44.5mm × 91.5mm 

1/4 DIN 

91mm × 91mm 

ON

OFF

 

SV    SV+(AL-L)   SV+(AL-H)

ON

OFF

 SV-(AL-H)     SV-(AL-L)   SV

ON

OFF

SV-(AL-L)       SV      SV+(AL-H)