Restore Factory Settings
Lock all buttons by adjusting parameter
to
in
【
Operation Mode
】
. At the same time press
and
keys for 3
seconds to display
, and enter Password-1357. The screen displays
(Parameter reset), selecting
will
overwrite all user settings with factory settings.
Key Lock Function
Adjusting parameter
to
in
【
Operation Mode
】
will lock all keys; adjusting the parameter to
allows adjustment
of SV setting values and F1/F2 function keys.
Unlock the key:
Press
and
keys at the same time in LOCK mode to display
parameter, enter the password to unlock the key. Default
password is 0000.
For altering key-lock password:
1.
Press
key in
screen to enter change-password screen
.
2.
Enter the current password in
screen. If the password is correct, you will be prompted to Set-New-Password
screen
. If the password is incorrect, the screen will return to PV/SV display mode.
3.
Enter the new password two times in the
screen. The screen will return to PV/SV display mode with the keys
unlocked. If the two entries of password are not the same, the screen will go back to the state of step 2.
Cannot remember the password:
Restore factory settings to release the locking.
Alarm Outputs
Two alarm outputs are provided in the machine, a maximum of 3 alarm outputs can be expanded. A total of 19 Independent alarm settings
can be made as listed in the table. Additional settings are provided, such as alarm delay, alarm standby, alarm output hold, alarm reverse
output, and alarm peak record, as described as follows:
a
、
Alarm Delay Setting: Sets alarm delay time. When the movement conforms to the alarm setting mode, controller will delay the
generation of an alarm signal; an alarm will only be activated when the alarm conditions remains confirmed within the delayed period
of time.
b
、
Alarm Standby Setting: An alarm detection will only be activated when the measured value falls within the ±5 range of the specified
input value, so as to prevent an alarm activation on the start-up if the condition conforms to the alarm setting.
c
、
Alarm Output Hold Setting: The alarm message will be held when the alarm activates, unless the control switches off the alarm.