1
Specifications
Specifications
Digital DC Inputs
XLE103
XLE104
Digital DC
Outputs
XLE103
XLE104
Inputs per Module
12 including 4
configurable
HSC inputs
24 including
4
configurable
HSC inputs
Outputs per
Module
12 including
2
configurable
PWM
outputs
16 including
2
configurable
PWM
outputs
Commons per
Module
1
Commons per
Module
1
Input Voltage
Range
12 VDC / 24 VDC
Output Type
Sourcing / 10 K Pull-Down
Absolute Max.
Voltage
35 VDC Max.
Absolute Max.
Voltage
28 VDC Max.
Input Impedance
10 k
Ω
Output
Protection
Short Circuit
Input Current
Positive
Logic
Negative Logic
Max. Output
Current per
point
0.5 A
Upper Threshold
0.8 mA
-1.6 mA
Max. Total
Current
4 A Continuous
Lower Threshold
0.3 mA
-2.1 mA
Max. Output
Supply Voltage
30 VDC
Max Upper
Threshold
8 VDC
Minimum Output
Supply Voltage
10 VDC
Min Lower
Threshold
3 VDC
Max. Voltage
Drop at Rated
Current
0.25 VDC
OFF to ON
Response
1 ms
Max. Inrush
Current
650 mA per channel
ON to OFF
Response
1 ms
Min. Load
None
HSC Max.
Switching Rate
10 kHz Totalizer/Pulse,Edges
5 kHz Frequency/Pulse,Width
2.5 kHz Quadrature
OFF to ON
Response
1 ms
Analog Inputs,
Medium
Resolution
XLE103
XLE104
ON to OFF
Response
1 ms
Number of
Channels
2
2
Output
Characteristics
Current Sourcing (Pos logic)
General Specifications
Input Ranges
Safe input voltage
range
Input Impedance
(Clamped @ -0.5
VDC to 12 VDC)
0 - 10 VDC
0 – 20 mA
4 – 20 mA
-0.5 V to +12V
Current Mode:
100
Ω
Voltage Mode:
500 k
Ω
Required Power
(Steady State)
130 mA @ 24 VDC
Required Power
(Inrush)
30 A for 1 ms @ 24 VDC
Nominal Resolution
%AI full scale
Max. Over-Current
10 Bits
32,000 counts
35 mA
Primary Power
Range
10 – 30 VDC
Conversion Speed
All channels converted once
per ladder scan
Relative Humidity
5 to 95% Non-
condensing
Max. Error at 25
°
C
(excluding zero)
4-20 mA 1.00%
0-20 mA 1.00%
0-10 VDC 0.50%
Operating
Temperature
0
°
C to +50
°
C
Terminal Type
Screw Type,5 mm
Removable
Additional error for
temperatures other
than 25
°
C
TBD
CE
UL
Filtering
160 Hz hash (noise) filter
1-128 scan digital running
average filter
Weight
12.5 oz. (354.36 g)
y
c
a
r
u
c
c
A
k
c
o
l
C
+/- Seven
Minutes/Month at 20C
Note: Highest usable frequency for PWM output is 65 KHz
2
Panel Cut-Out and Dimensions
Note: Max. panel thickness: 5 mm.
3
Ports / Connectors / Cables
Note:
The case of the XLe is black, but for clarity, it is shown in a
lighter gray color.
3.
62
2"
[9
2m
m
]
3.622" [92mm]
001XLE002
Note:
The tolerance to meet
NEMA
standards is
±
0.005" (0.1 mm).
To Remove Back Cover:
Unscrew 4 screws located on
the back of the unit and remove
back cover.
CAUTION:
Do not over tighten
screws when replacing the back
cover.
001ACC009
Power Connector
Power Up:
Connect to Earth Ground.
Apply 10 – 30 VDC.
Screen lights up.
Torque rating 4.5 - 7 Lb-In
(0.50 – 0.78 N-m)
CAN Connector
Use the CAN Connector
when using CsCAN network.
Torque rating 4.5 – 7 Lb-In
(0.50 – 0.78 N-m)
I/O Jumpers (Not Shown):
I/O Jumpers (
JP
) are located
internally. To access, remove back cover of unit.
Wiring Connectors
(
J1 – J4
),
I/O Jumpers
(
JP1-3
), and
External Jumpers
(
RS-485
) are described in the
Wiring and
Jumpers
section of this document.
MJ1
(RS-232 / RS-485)
MJ2
(RS-232 / RS-485)
J1
I/O
Jumper
Memory Slot
001XLE029-R2
J2
I/O
Jumper
NET 1
(CsCAN)
Power
DIP
Switch
If you require a Compliance Table: