PROCESS CHANGE 

 

Displaying: 

 
The system will constantly monitor  the total amount of change in process variable since start or last reset. 
This change is displayable in engineering units by pushing the ‘PR CNG’ key. 
 
This function is useful in tracking the change that has taken place in the process e.g. in a tank containing 
300 gallons of water, an addition of 200 gallons will show that the total amount of water is 500 gallons. On 
pushing the ‘PR CNG’ key the display will indicate 200 gallons as the total change. Now assume that 400 
gallons of water is pumped out. The total amount of water left in the tank would now be indicated as 100 
gallons. The change that has taken place in the total volume of water from its original 300 gallons can be 
displayed by pushing the "PR CNG" key and it would be 200 gallons. 
 

Resetting: 

 
To start tracking the change from a new point, the Process change being indicated can be reset to zero . To 
do so, push the ‘PR CNG’ key twice and keep it pushed. The display will flash the present change value 
three times and then reset it to zero (keep the "PR CNG" key pushed till the display shows zero or close to 
zero). This flashing feature is provided so that if   ‘PR CNG’  key gets pushed twice accidently while trying 
to display the process change it would provide a chance to get out of reset mode without actually resetting 
the reading. Therefore, if  ‘PR CNG’   key is released any time before the three flashes, the current reading 
of "Process Change" will be retained. 
 

SCALING 

 
Scaling is useful in reading the sensor output directly in engineering units e.g. a load cell putting out 4 - 20 
ma signal can be scaled to read 0 - 4000 pounds of load. 
 
Scale  is entered as two different values i.e. High Scale and low Scale. High scale corresponds to the 
maximum output of the transducer and low scale to low output. e.g. For a 0-5V transducer if it is desired to 
read 200 units at 0VDC and 3000 units at 5VDC output then set low scale equal to 200 and high scale to 
3000. The DP3600 unit will linearly scale the transducer output. For a transducer with 4-20ma the low scale 
reading can be obtained at the programmed offset value. For instance if offset is set to 4.00, then the low 
scale reading will be obtained when the unit sees a 4.00ma signal from the transducer.  
 
Scaling is obtained during setup mode and immediately follows the setting up of decimal point. Maximum 
programmable high scale is from 1-30000 and low scale from 0-high scale value.  
 
Scaling can be programmed and displayed in SETUP mode only (look under setup). 
 
 

OFFSET 

 
The system provides the capability of programmable offset. This is useful if a certain amount of input from 
the transducer is required to read zero e.g. for a 4-20ma input , 4ma can  be made to read zero. 
 
Offset can be programmed and displayed in the SETUP mode only (look under setup). 
 
 

Содержание DP3600 SERIES

Страница 1: ...PROGRAMMABLE PROCESS MONITORS USER S MANUAL DP3600 DP3700 AND DP3800 SERIES OMEGA ENGINEERING INC ONE OMEGA DRIVE STAMFORD CT 06907 MANUAL M881 0399...

Страница 2: ...S PROCESS OR DEVIATION LIMIT 7 PROGRAMMING LIMIT 4 7 As Process Limit 7 As Deviation Limit 7 TIMERS 1 AND 2 7 RELAY DEADBAND 7 CONFIGURING LIMITS NORMALLY OPEN NORMALLY CLOSED 7 RELAY LATCHING NON LAT...

Страница 3: ...L RELAY OPTION 14 Figure 1 Electro mechanical Relays Hookup Example 14 OPEN COLLECTOR OPTION 15 Figure 2 Open Collector Hookup Example 15 HOLD FUNCTION 15 SAVING PARAMETER 15 POWER 15 FIGURE 3 REAR VI...

Страница 4: ...tage input POWER REQUIREMENTS choice of three supply ranges 120 VAC 60Hz 240 VAC 50Hz 7 5 VDC 12VDC 900 ma DIMENSIONS Case 3 60 x 1 75 x 7 Bezel size 4 40 x 2 25 x 0 45 Extruded Aluminum enclosure DIS...

Страница 5: ...r deviation falls below the limit minus the relay dead band The second one is latching mode In this mode the relays will stay energized even after the parameter falls below the programmed limit They c...

Страница 6: ...the decimal point to the next position After 9 999 the display will go to 9999 When proper decimal point position has been obtained push SETUP key to go to the next mode High Scale High scale mode is...

Страница 7: ...o the above i e for Limits 2 3 and 4 and also if Limits 3 and 4 are setup as process limits and allow you to enter process limits 2 through 4 However limits 3 and 4 can be configured to work as rate a...

Страница 8: ...lay Deadband The parameter programmed after timers is limit deadband The display will first read DEAD BD and then show the value of previously programmed dead band To change the value of flashing digi...

Страница 9: ...message which indicates the active display parameter and its value e g if the selected display option in the above step was PROCESS then the display will periodically display the message PROCESS to in...

Страница 10: ...UP key to go to the next step Input Range The following step is the last step in this process This is where you program the input range of your signal On entering this mode the display will first read...

Страница 11: ...P dEn 3 RAtE 4 Pr CnG 5 HIGH Pt 6 LO Pt 7 ELPSd t 8 SCAn INPUT RANGE IP rnGE 020 00 REMOTE TARE HOLD rt tArE rt HOLD PROGRAM SETPOINT SetPt 1 234 INPUT TYPE IP tYPE 1 CurrEnt 2 VOLtAGE 3 LO VOLT FLASH...

Страница 12: ...ble value RATE The DP3600 unit keeps track of the rate of process change and can be displayed by pushing the key labeled RATE The display first reads RATE followed by the rate value that was monitored...

Страница 13: ...eset mode without actually resetting the reading Therefore if PR CNG key is released any time before the three flashes the current reading of Process Change will be retained SCALING Scaling is useful...

Страница 14: ...y must read RT TARE LIMITS Process Limits Displaying The LIMITS key is used for displaying Process Variable limits Pushing the LIMITS key twice will briefly display PR LT1 first push displays RATE and...

Страница 15: ...are activated when the limit is achieved on each one of them The alarms can be programmed as normally open or normally closed see SETUP The status of these is indicated on the front panel by the LEDs...

Страница 16: ...in the EEPROM by pressing and holding RESET key till the display reads SAVING If the parameters are NOT saved and the power is removed from the unit any newly changed values will be lost the unit wil...

Страница 17: ...R 1 COMMON OPEN COLLECTOR POSITIVE 10 TIMER 1 NORMALLY OPEN OPEN COLLECTOR NEGATIVE 11 TIMER 2 COMMON OPEN COLLECTOR POSITIVE 12 TIMER 2 NORMALLY OPEN OPEN COLLECTOR NEGATIVE 13 GROUND RETURN FOR HOLD...

Страница 18: ...UT HIGH SCALE 20 000 10 000 100 00 LOW SCALE 0 000 0 000 0 000 OFFSET 0 00 0 00 0 00 TARE 0 000 0 000 0 000 LIMITS 1 000 1 000 1 000 Error Messages Various error messages indicated on the display are...

Страница 19: ...crews 4 Slide the open end A of the bracket onto the meter until it is flush with the panel The rear of the meter should touch the back of the bracket B Figure 5 Mounting Bracket Assembly 5 Tighten th...

Отзывы: