IMPORTANT SAFETY INSTRUCTIONS 

 

Repair to sealed components 

•  During repairs to sealed components, all electrical supplies shall be disconnected from the 

equipment being worked upon prior to any removal of sealed covers, etc. If it is absolutely necessary 

to have an electrical supply to equipment during servicing, then a permanently operating form of 

leak detection shall be located at the most critical point to warn of a potentially hazardous situation. 

•  Particular attention shall be paid to the following to ensure that by working on electrical 

components, the casing is not altered in such a way that the level of protection is affected. This shall 

include damage to cables, excessive number of connections, terminals not made to original 

specification, damage to seals, incorrect fitting of glands, etc. 

•  Ensure that seals or sealing materials have not degraded to the point that they no longer serve 

the purpose of preventing the ingress of flammable atmospheres. Replacement parts shall be in 

accordance with the manufacturer’s specifications. 

 

Repair to intrinsically safe components 

•  Do not apply any permanent inductive or capacitance loads to the circuit without ensuring that 

this will not exceed the permissible voltage and current permitted for the equipment in use. 

•  Intrinsically safe components are the only types that can be worked on while live in the presence 

of a flammable atmosphere. The test apparatus shall be at the correct rating. 

•  Replace components only with parts specified by the manufacturer. Other parts may result in the 

ignition of refrigerant in the atmosphere from a leak. 

 

Cabling 

•  Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, sharp 

edges or any other adverse environmental effects.  

•  The check shall also take into account the effects of aging or continual vibration from sources 

such as compressors or fans. 

 

Detection of flammable refrigerants 

•  Under no circumstances shall potential sources of ignition be used in the searching for or 

detection of refrigerant leaks. A halide torch (or any other detector using a naked flame) shall not be 

used. 

•  Electronic leak detectors may be used to detect refrigerant leaks but, in the case of flammable 

refrigerants, the sensitivity may not be adequate, or may need re-calibration. 

•  Ensure that the detector is not a potential source of ignition and is suitable for the refrigerant used. 

Leak detection equipment shall be set at a percentage of the LFL of the refrigerant and shall be 

calibrated to the refrigerant employed, and the appropriate percentage of gas (25 % maximum) is 

confirmed. 

•  Leak detection fluids are also suitable for use with most refrigerants but the use of detergents 

containing chlorine shall be avoided as the chlorine may react with the refrigerant and corrode the 

copper pipework. 

•  If a leak is suspected, all naked flames shall be removed/extinguished. 

•  If a leakage of refrigerant is found which requires brazing, all of the refrigerants shall be recovered 

from the system, or isolated (by means of shut off valves) in a part of the system remote from the leak. 

 

Removal and evacuation 

•  When breaking into the refrigerant circuit to make repairs – or for any other purpose – 

conventional procedures shall be used. However, for flammable refrigerants it is important that best 

practice is followed since flammability is a consideration. The following procedure shall be adhered 

to: 

 

 

Содержание OAPC26W

Страница 1: ...OMEGA ALTISE OPERATION MAINTENANCE AND SAFETY INSTRUCTIONS FOR OMEGA ALTISE AIR CONDITIONER Model OAPC26W...

Страница 2: ...LTISE Contents IMPORTANT SAFETY INSTRUCTIONS 3 TECHNICAL DETAILS 8 FEATURES 9 PRODUCT OVERVIEW 9 INSTALLATION INSTRUCTIONS 10 OPERATING INSTRUCTIONS 14 CLEANING 18 SERVICING 20 TROUBLESHOOTING 22 WARR...

Страница 3: ...inum fins of the unit Do not operate the unit if it is dropped damaged or showing signs of product malfunction Do not clean the appliance with any chemicals Ensure the unit is far away from fire infla...

Страница 4: ...e shall be stored in a well ventilated area where the room size corresponds to the room area as specified for operation WARNING Do not use means to accelerate the defrosting process or to clean other...

Страница 5: ...om a leak Cabling Check that cabling will not be subject to wear corrosion excessive pressure vibration sharp edges or any other adverse environmental effects The check shall also take into account th...

Страница 6: ...tamination of different refrigerants does not occur when using charging equipment Hoses or lines shall be as short as possible to minimize the amount of refrigerant contained in them Cylinders shall b...

Страница 7: ...relief valve and associated shut off valves in good working order Empty recovery cylinders are evacuated and if possible cooled before recovery occurs The recovery equipment shall be in good working...

Страница 8: ...ion systems or contact the retailer where the product was purchased They can take this product for environmentally safe recycling TECHNICAL DETAILS Model OAPC26W Fan Speeds 2 settings Cooling Capacity...

Страница 9: ...efficient Auto shut off when tank full Automatic restart in the event of power outage Auto defrosting function at low ambient temperatures Remote control 2 speed fan Casters for easy mobility PRODUCT...

Страница 10: ...S Unpacking Unpack the carton and take the appliance and accessories out Check the device after unpacking for any damage or scratches on it Accessories 1 Exhaust hose 2 Hose connector 3 Window kit ada...

Страница 11: ...radiators heat registers stoves or other products that produce heat II Direct sunlight III Mechanical vibration or shock IV Excessive dust V Lack of ventilation such as cabinet or bookcase VI Uneven...

Страница 12: ...kit the length of your window Connect the exhaust hose to the window kit Step 4 Close your window to secure the kit in place It needs to hold the windows kit firmly in place secure the window kit wit...

Страница 13: ...the hose connector to the exhaust air outlet of unit Step 6 Adjusting the length of the flexible exhaust hose and avoid bends in the hose Then place AC near an electrical outlet Step 7 Adjust the lou...

Страница 14: ...ween HIGH and LOW 4 Fan Speed Display This display the High and Low fan speed 5 Down Decreasing the desired temperature or timer setting 6 Mode Display The Mode Display between fan cooling and dehumid...

Страница 15: ...cool mode to lower the temperature in your room Press MODE button repeatedly until the LED of COOL operation lights up Press ADD MINUS button to adjust the temperature which is displayed on the screen...

Страница 16: ...ol the LED of DRY operation lights up The fan speed is unable to select User should connect the hose to the drain outlet at the bottom of the unit Note In this mode the fan speed switches over to low...

Страница 17: ...e self evaporating system uses the collected water to cool the condenser coils for better efficient performance There is no need to empty the drainage tank in cooling operation except in drying operat...

Страница 18: ...cleaning The air filter is removable for easy cleaning Do not operate the unit without an air filter or the evaporator may be contaminated 1 Press POWER button to switch off the unit and unplug the po...

Страница 19: ...on equipment PPE 4 Evacuate unnecessary personnel isolate and ventilate area 5 Do not get in eyes on skin or on clothing Do not breathe vapours or gas 6 Prevent entry to sewers and public waters 7 Sto...

Страница 20: ...n system which involves exposing any pipe work that contains or has contained flammable refrigerant shall use any sources of ignition in such a manner that it may lead to the risk of fire or explosion...

Страница 21: ...e safety then no electrical supply shall be connected to the circuit until it is satisfactorily dealt with If the fault cannot be corrected immediately but it is necessary to continue operation an ade...

Страница 22: ...re transport Check if the drain hose is kinked or bends Straighten the hose to avoid a trap existing Excessive Noise Check if the unit is securely positioned Place the unit on horizontal and firm grou...

Страница 23: ...ed to a warranty of Twelve 12 months covering all parts with Three 3 months on any labour cost of service or repair WHAT IS COVERED By Our Warranty During the warranty period Omega Altise or its autho...

Страница 24: ...OMEGA ALTISE A division of Shriro Australia Pty Ltd 2 34 Davidson Street Chullora NSW 2190 In Australia 1300 795 572 In New Zealand 09 415 6000 www omegaaltise com IM Ref OAPC26W 2021 09 03 24...

Отзывы: