Troubleshooting
EE4
Overheating probe starts
protecting program (58°C
/ 136.4°F)
Too much dust on condenser, clean the condenser.
Condenser motor stops working, repair or change the
motor.
The unit is too close to the wall, keep product at least
50cm from the wall.
Ambient temperature is too high, ensure the ambient
temperature stays between the specified range.
GENERAL TROUBLESHOOTING
Problem
Causes
Solutions
Strange noise under the bottom
shelf.
Fan blade broken.
Power off and fix the blade.
Not refrigerating in spite of normal
operation.
Unit is off.
Power on.
Melting process.
Stop the melting process.
Refrigerant leaking.
Patch the leak and refill refrigerant.
Unit failure.
Call Omcan.
Weak air from air curtain, and
higher cabinet temperature.
Evaporator blocked by frost.
Increase melting frequency.
Inside fan damaged.
Replace the fan.
Too low set point of temperature
controller.
Adjust the set point.
Vent blocked by storage.
Remove the storage.
Normal air curtain, but higher
cabinet temperature.
Insufficient refrigerant.
Refill the refrigerant.
Too high set point of temperature
controllers.
Adjust the set point for the
temperature controller.
The wind curtain disturbed by
strong air flow.
Removing the disturbing factors.
Ambient temperature or humidity
beyond standards.
Improve the conditions.
Melting water overflown.
Heating pipe for melting water
damaged.
Replace the heating pipe.
Water level controller failure.
Replace the water level controller.
Ambient temperature or humidity
beyond standards.
Improve the conditions.
Содержание 47106
Страница 13: ...13 Model RS CN 0348 47106 Parts Breakdown ...
Страница 14: ...14 Model RS CN 0348 47106 Parts Breakdown ...
Страница 16: ...16 Model RS CN 0468 47277 Parts Breakdown ...
Страница 17: ...17 Model RS CN 0468 47277 Parts Breakdown ...
Страница 19: ...19 Model RS CN 0348 47106 Electrical Schematics ...
Страница 20: ...20 Model RS CN 0468 47277 Electrical Schematics ...
Страница 21: ...21 Notes ...
Страница 22: ...22 Notes ...