![omal automation AGO DA2880 Скачать руководство пользователя страница 22](http://html1.mh-extra.com/html/omal-automation/ago-da2880/ago-da2880_instruction-manual_3891788022.webp)
Rif. UMA800081C - 06/22
IT
EN
EN -
22
OMAL S.p.A.
Headquarters
: Via Ponte Nuovo, 11 - 25050 Rodengo Saiano (BS) Italy •
Production Site:
Via Brognolo, 12 - 25050 Passirano (BS) Italy
Ph.
+39 030 8900145 •
Fax
+39 030 8900423 • [email protected] •
www.omal.com
INSTRUCTION MANUAL
AGO: SCOTCH–YOKE PART TURN PNEUMATIC ACTUATOR
DA2880 - DA8000 - SR1440 - SR4000
Internal chamber (central) supply hole
Shaft
CLOSED VALVE ADJUSTMENT
1) Pressurize the internal chamber with the least pressure enough for the movement of the internal piston (it can be noticed from the
outside due to the partial rotation of the shaft)
2) Loosen the lock nut (1)
3) Rotate the screw (2) in a clockwise direction to decrease the closing angle and in a counter clockwise direction to increase such
angle.
4) Tighten the lock nut (1)
5) Remove the power
6) Verify that the adjustment obtained is the desired one, otherwise repeat the operations from step 1.