      ex)  low  combustion  damper  open  :  2/10  open.           

              medium  combustion  damper  open  :  4/10  open.

              high  combustion  damper  open  :  6/10  open.

            ⓐ  see  each  CAM  of  the  damper  open  scale.  accord  with  marked  CAM  scale       

                according  to  the  setting  position.

            ⓑ  when  adjustment  is  over,  and  adjust  damper  plate  to  the  low  combustion         

                  damper  opening  using  the  knob  on  the  opposite  side  of  the  motor.

  ㉢  turn  on  the  power.  and  adjust  damper  again  while  reviewing  the  operating                 

          conditions  of  combustion.  in  this  case  make  it  sure  to  confirm  that  each  switch   

          turns  off  sequentially  from  the  low  combustion  damper  CAM.

  ㉣  overrun  protection  s/w

        when  low  or  high  combustion  damper  CAM  is  mistakenly  adjusted.(for  example,       

        low  combustion  damper  CAM  is  set  below  zero  in  the  damper  scale  or  high             

        combustion  damper  CAM  is  set  adove  10  in  the  damper  scale)  or  when  the  low     

        or  high  combustion  damper  s/w  is  out  of  order.  press  the  overrun  protection  s/w   

        to  stop  damper  operation.

          ⓐ  when  pressing  the  low  overrun  protection  s/w.

              readjust  the  low  combustion  damper  CAM  when  the  s/w  is  out  of  order,               

              replace  the  s/w.  when  it  is  completely  closed,  use  the  manual  adjuster  knob     

              to  set  in  ti  the  low  combustion  opening  position.

          ⓑ  when  pressing  the  high  overrun  protection  s/w.

              readjust  the  high  combustion  damper  CAM  when  the  s/w  is  out  of  order,             

                replace  the  s/w.

3)  HOW  TO  DISASSEMBLE,  CLEAN  AND  REPLACE  NOZZLE.

①  the  nozzle  sprays  fuel  through  fine  hole(㉠)

②  air  flow  rate  and  pump  pressure  are  adjustable  per  the  capacity  of  nozzle  which  is   

      specified  in  terms  of  spray  rate,  angle  and  patten.

③  capacity

      G/H  (gallon/hour):  the  capacity  id  specified  as  to  consume  3.785  liters  of                   

      kerosene  per  hour  under  the  pressure  of  7㎏/㎠.

④  80°:  fuel  is  sprayed  from  nozzle  hole  in  80  degree  angle.

⑤  when  burning  conditions  are  not  satisfactory  bue  to  inappropriate  splay  of  fuel, 

remove,  disassemble  and  clean  nozzle  using  kerosene.

a)  how  to  replace  nozzle.

ⓐ  disconnect  power.

ⓑ  pull  out  one  side  of  hinge  pin  to  open  the  burner  flame.

ⓒ  hold  nozzle  adapter  with  spanner,  and  loosen  nozzle  counter  clockwise.

ⓓ  after  changing  nozzle,  check  and  adjust  the  place  of  ignition  by  with  referring  to     

          assembling  dimension  of  combustion  head.

ⓔ  replace  nozzle  in  the  reverse  order.

Содержание LT-100

Страница 1: ...OLYMPIA BURNER OPERATING MANUAL MODEL LT 40 45 60 80 100 120 150 200 250 300 400 500 600 700 OLYMPIA INDUSTRIAL CO LTD ...

Страница 2: ...ATION SYSTEM 4 HOW TO INSTALL FUEL PIPE SYSTEM 5 TIME CHART 6 ELECTRIC CIRCUIT DIAGRAM 3 HOW TO USE MAJOR PARTS 1 COMBUSTION HEAD DIMENSION 2 HOW TO ADJUST COMBUSTION OF AIR FLOW RATE 3 HOW TO DISASSEMBLE CLEAN AND REPLACE NOZZLE 4 FLAME DETECTOR 5 GEAR PUMP 6 IGNITION TRANSFORMER 7 FUEL FILTER 4 GENERAL BURNER OPERATION 5 HOW TO CHECK BURNER CAUSE OF TROUBLE AND COUNTER MEASURE 1 CHECK OF BURNER ...

Страница 3: ... 214 HI MID LOW O FF or MODURATING 5 5 E 7 11 8 20 4 LT 300T 80 250 7 5 TA 2 PT 1 2 PT 1 2 15 8 27 3 LT 400T 108 330 11 20 4 35 5 LT 500T 136 408 11 20 4 35 5 LT 600T 194 583 15 20 4 35 5 LT 700T 167 668 18 5 20 4 35 5 1 INTRODUCTION OF PRODUCT LT Series oil Burner is also designed and manufactured upon our well experienced technique and is made of motor oil pump fan ignition equipment and automat...

Страница 4: ...2 COMBUSTION PERFORMANCE GRAPH ...

Страница 5: ...3 SIZE AND DIMENSION LT 40 45 60 DIMENSION ...

Страница 6: ...olled as follows depending on the number of nozzle two nozzle 2 position control hi low off three nozzle 3 position control hi mid low off one proportional nozzle proportional control modulating how to control air flow rate two nozzle damper motor or hydraulic cylinder type three nozzle damper motor type one proportional nozzle modulating motor type ...

Страница 7: ...4 EXPLODED DRAWING OF BURNER AND PART NAME 1 LT 40U 45U 60U BURNER EXPLODED DRAWING ...

Страница 8: ... 2 LT 40UH 45UH 60UH BURNER EXPLODED DRAWING ...

Страница 9: ... 3 LT 80U 100U 150 200 250 300 400 500 600 700 BURNER EXPLODED DRAWING LT 80T 100T 150 200 250 300 DAMPER MOTOR LT 250 300 400 500 600 700 3NOZZLE ...

Страница 10: ... 400 D 228 228 315 350 430 430 E M10 M10 M14 M14 M16 M16 2 HOW TO CONTROL BURNER 1 BURNER COMBUSTION FURNACE DIMENSION 2 HOW TO INSTALL BURNER 1 burner assembly sequence refer to above sketch insert gasket into the burner hinge insert burner to the boiler fire outlet or combustion furnace and tightly fasten after adjusting the burner in the hinge fix the burner with hinge pin ...

Страница 11: ...mbustion gas leaks after installing the hinge type burner use care so that no part of ignition bar is damaged or deformed during assembly of frame secure enough working space to check and maintain burner flange tube type burner LT 40U LT700T hinge tube type burner LT 40UH LT 60UH 3 DIAGRAM OF FUEL CIRCULATION SYSTEM ...

Страница 12: ...s plug when oil tank is below burner H its height must be less then 2 4m the inlet hole should place at 20cm higher then the floor of oil tank in order not to flow in foreign subtainces it is recommended that oil pipe be welded in order not to flow in air in case of fixing several pipes inlet and return pipe must use an enough space pipe in inside diameter return pipe had better not use valve if o...

Страница 13: ...5 TIME CHART ...

Страница 14: ... 6 ELECTRIC CIRCUIT DIAGRAM ...

Страница 15: ... MODURATING TYPE ...

Страница 16: ... 1 COMBUSTION HEAD DIMENSION in case of adjusting C size be careful not to touch the and of ignition bar with diffuser or diffuser is not stained with oil 2 HOW TO ADJUST COMBUSTION AIR FLOW RATE 1 hydraulic cylinder structure ...

Страница 17: ...bustion then fully tighten the nut A ⓑ second stage high combustion air adjustment loosen the nut D in the high combustion mode and tighten adjuster nut C to increase air flow rate until no smoke coming out from the chimney when adjustment is over fully tighten the nut D so that the adjuster nut is not loosened 2 damper motor structure ...

Страница 18: ...diagram how to adjustment damper damper gauge consists of from 0 to 10 0 indicates complete close and 10 indicates complete open disconnect power adjust each CAM by deciding the position depending on the combustion rate ...

Страница 19: ... low combustion damper CAM when the s w is out of order replace the s w when it is completely closed use the manual adjuster knob to set in ti the low combustion opening position ⓑ when pressing the high overrun protection s w readjust the high combustion damper CAM when the s w is out of order replace the s w 3 HOW TO DISASSEMBLE CLEAN AND REPLACE NOZZLE the nozzle sprays fuel through fine hole a...

Страница 20: ...lacement b how to disassemble and check nozzle separate filter clean the filter using kerosene separate the gelical support using a screwdriver clean the groove using kerosene and thin wire do not use iron wire or needle otherwise the nozzle hole may widen after the nozzle hole is clean assemble nozzle in the reverse order make it fasten it set up ...

Страница 21: ...econds after burner ignitions check whether there is a soot or dust on the flame sensor of the flame detector thoroughly remove soot or dust from the flame sensor if any if soot or dust is accumulated on the flame sensor of the flame detector burner stops operation therefore it is required to clean the flame sensor using clean dry cloth every month 5 GEAR PUMP 1 external drawing and specification ...

Страница 22: ...reasing 3 how to purge air from the pump turn the gear pump air purge bolt counterclockwise 3 to 4 times with spanner operate burner then air bubble comes through the air exhaust hole of the gear pump then clean oil discharges then stop burner operation and fully tighten the air purge bolt then operate burner if air is not completely removed within 16 seconds burner stops operation when pressing r...

Страница 23: ...r emergency operation only continue to check conditions of flame during manual operation high combustion valve on automatic operation by inter lock auction take care of the ignition transformer as high voltage is applied to the ignition transformer 7 FUEL FILTER how to handle fuel filter the fuel filter removes foreign substance from fuel when burner does not generate flame as no fuel is fed even ...

Страница 24: ...voltage and fuel meet the burner specification discharge air from the fuel pipe system check whether or not the burner nozzle corresponds the boiler or furnace capacity maintenance of burner clean the ignition bar if it is contaminated clean nozzle and nozzle adapter if soot is accumulated on the diffuser burner fails to ignite remove the soot from the diffuser check and clean oil filter if requir...

Страница 25: ...2 BURNER TROUBLE ACTION TABLE ...

Страница 26: ...r raise discharge pressure discharge air check valve and clean filter replace and repair adjust damper replace and repair replace and repair replace and repair when combustion stop immediately after ignites 1 flame sensor is contaminated 2 flame sensor is out of order 3 protector relay is out of order clean replace and repair replace and repair combustion is unstable or smoke occurs 1 hydraulic pr...

Отзывы: