Luminaire

Mounting accessories
Manual

Pictograms

1

2

3

Surface mounting on a Wall with A-1134 base (Included in the package)

Single sided luminaire

o

These devices are used indoors 

(

ta 40 C

)

 in 

places  where  emergency  light  is  needed. 
Each  device  must  be  permanently 
connected  to  mains  power  supply

.

  In 

normal operation the battery is charging. In 
case    of  a  mains  power  supply  failure,  the 
device  enters  emergency  mode  and  the 
illumination LED turns on. When the  mains  
power    supply  is  restored  the  device  turns 
to normal operation.

If  the  luminaire  is  not  connected  to  the 
panel,  the  following  automatic  tests 
executed:

Manual

 

Operational 

Test

The  illumination  source  and  the  autonomy 
tests  are  programed  by  the  control  panel. 
The  tests  results  are  send  to  the  control 
panel.

Automatic Operational Test

The Automatic Autonomy Test is conducted 
every  6  months  and  measures  the  device’s 
back up operation and emergency duration.

 

In order to be performed, the mains power 
supply and the battery should be connected 
and fully charged

If the battery is not fully 

charged

the  test  is  postponed

 

until  the 

battery is completely charged. If during this 
test,  the  autonomy  is  less  than  nominal 
then  the  battery  fault  led  turned  on 
continuously  and  the  battery  must  be 
replaced. 

T

his test includes all the operations that are 

provided  in  manual  operational  test  and  is 
conducted automatically every 15 days and 
lasts 3 seconds.

By  pressing  the  test  button  an  operation 
test  is  initiated.  The  light  source  and  the 
emergency circuit of the device are tested. 
The  manual  test  can  be  conducted  only  if 
the mains power supply and the battery are 
connected.  During  this  test  period  all 
indications LED are OFF.

Automatic Autonomy Test

Tests

3.  The  device  must  be  connected  to  the 

mains  power  supply  through  a  circuit 
breaker    that  is  depends  on  the  total 
line’s  power load.

2.  Always  use  in  any  case  round  mains 

cable

,

  with  a  diameter

 

of  5

-

10mm 

(H05RN-F  type  2x1mm² 

or 

any 

other 

type

,

 

at  least 

equal 

to  it’s  mechanical 

and  electrical  properties).  ATTENTION!! 
The  cable  must  not  be  deformed  in  any 
way  (This  requirement  is  important  to 
ensure the 

ΙΡ 

rating).

Resetting Errors

ΑΤΤΕΝΤΙΟΝ!

!!

4.  In  case  of  battery  replacement,  it  must 

be  replaced  by  the  same  type,  by  the 
manufacturer or a competent person.

                

Press  and  hold  the  TEST  button  for  more 
than  5  seconds.  The  luminaire  will  erase 
first the errors (3 LED indicators will light in 
succession)  and  after  2  seconds  the  LED 
Lamp  Fault  will  remain  lit  steadily.  When 
the  TEST  button  is  released,  the  luminaire 
will  change  between  maintained  or  non  -
maintained  mode.  The  change  is  recorded 
permanently in it’s memory.

Changing The Operating Mode

The  luminaires  can  be  connected  to  the 
addressable  panels  of  Olympia  Electronics. 
For  address  operations  refer  to  the 
installation  manual  of  the  panel.  For 
address connections see page 2. 

1.  Operations for installation, maintainance 

or  testing  must  be  done  by  authorized 
personnel only

.

Push  the  Test  button  for  more  than  5 
seconds,  to  delete  all  the  indicated  LED 
errors.  Then    the  device  enters  regular

 

operation mode.

Addressable Communication

6. 

It  is  not  allowed  to  discard  batteries 

into common trash bins, they must be 
discarded  only  in  battery  recycling 
points. Do not incinerate.

5.  In  case  of  inactive  use  for  a  period 

greater  than  2  months,  disconnect  the 
battery  by  pulling  out  the  battery’s 
connector. 

Οptional Mounting Methods (Upon Request)

General

Package Contents

922502862_09_009

922502862_09_009

922502862_09_009

Description

Indications

 

LED Status

BATT.

FAULT

(

red

)

LAMP
FAULT

(

red

)

CHARGE

(

green

)

Charging

Lamp Fault

Battery fault

No charging current or disconnected battery

Permanently ON

Blink

Indifferent

Off

1

1

1

1

1

1

1

1

1

1

1

2

3

5

3

4

4

2

Installation Instructions

A

A

A

A

B

Signal Cable

Power Cable

N

L

+L

-L

-L

N

N

L

L

-L

L

L

Power Connection

Communication Connection

From 

Panel

A

A

B

B

LOCK

B

B

LOCK

Make the connections
Follow step 4 of installation on page 2

Α-1130
Α-1131
Α-1132

Tube

Α=1

m

Α=0

.

5

m

Α=0

.

25

m

Flag mounting 

A-1133 SET

(only for 

ZLD-28/EM/ADR, ZLD-34/EM/ADR)

Hanging mounting

A-1130, A-1131, A-1132 SET

CHANGE ADDRESS POINT

CHOOSE FROM 1 TO 250

ENTER TO CHANGE

- - -

006

NEW

OLD

Programming the address of a luminaire

3) You must go to the menu: 

4) Set the new address using the    UP and    DOWN keys and press enter when done.

TECHNICIAN MENU => SETTINGS=> CHANGE ADDRESS POINT

 

1) The luminaire must not be connected with the mains power supply not with the battery.
2) One end of the cable is connented to the luminaire and the other end to the panel.

To program or change the address of a luminaire you must connect the luminaire to the panel 
alone and do the following steps: