These  devices  are  used  indoors 

(

ta  40 C

)

  in 

places  where  emergency  light  is  needed.  Each 
device  must  be  permanently  connected  to 
mains  power  supply

.

  In  normal  operation  the 

battery  is  charging.  In  case    of  a  mains  power 
supply  failure,  the  device  enters  emergency 
mode and the illumination LED turns on. When 
the  mains  power  supply is restored the device 
turns to normal operation.

Battery Charging

The  battery  charging  is  completely  controlled 
by  microprocessor  and  is  protected  from 
complete discharge and overcharge

.

Battery Cut-off

The  luminaire  enters  in  this  mode  when  the 
mains power supply fails

 

and battery has lost its 

energy

During  this  mode  the  luminaire  enters 

the  idle  state

 

and  battery  consumption  is 

negligible,  in  order  to  be  protected  from  deep 
discharge.

Automatic Operational Test

T

his  test  is  conducted  automatically  every  15 

days  and  lasts  3  seconds.  In  order  to  be 
performed,  the  mains  power  supply  and  the 
battery  should  be  connected.  The  light  source 
and  the  emergency  circuit  of  the  device  are 
tested.

Automatic Autonomy Test

T

he Automatic Autonomy Test tests the device’s 

back  up  operation  and  emergency  duration. 
This  test  is  conducted  automatically  every  6 
months and its duration is the stated autonomy 
duration  of  the  luminaire

In  order  to  be 

performed,  the  mains  power  supply  should  be 
connected  and  the  battery  must  be  fully 
charged

If the battery is not fully charged

the 

test is postponed

 

until the battery is completely 

charged. If during this test, the autonomy is less 
than  nominal  then  the  battery  fault  LED  will 
permanently  be  on  and  the  battery  must  be 
replaced. 

B

ack Up Operation

T

he  autonomy  duration  of  battery  during 

emergency  mode  must  be  at  least  as  the  one 
stated in the list of the technical characteristics. 
During  emergency  mode,  a  light  source  test  is 
also performed.

ΑΤΤΕΝΤΙΟΝ!

!!

1.  Operations  for  installation,  maintainance  or 

testing  must  be  done  by  authorized 
personnel only

.

2.  The device must be connected to the mains 

power  supply  through  a  fuse  that  is 
dependent on the total line’s  power load.

3.  In  case  of  battery  replacement,  it  must  be 

replaced  by  the  same  type,  by  the 
manufacturer or a competent person.

                

4.  In  case  of  inactive  use  for  a  period  greater 

than  2  months,  disconnect  the  battery  by 
pulling out the battery’s connector. 

5. 

The  control  gear  within  this  luminaire  is  a 

built  in  control  gear  which  relies  on  the 
luminaire  for  protection  against  electric 
shock.

6.  The  control  gear  is  proof  against  supply 

voltage polarity reversal.

7.  This  control  gear  has  mains  connected 

primary windings.

8. 

I

s  not  allowed  to  discard  batteries  into 

t  i

common  trash  bins,  they  must  be 
discarded  only 

in  battery  recycling 

points. Do not incinerate.

Connectors
KL1:

  Power connector

KL2:

  Non user terminal

CN4:

  Battery connector

CN5:

  LED connector

CN6:

  Non user connector

CN7:

  Non user terminal

General

Mounting Methods

Sky  Line  luminaries  can  be  surface  mounted  on  walls  or  ceilings.  For  these  mounted  installations,   
special accessories are included.

Wall

bottom

view

Wall installation

Ceiling installation

Ceiling

*  ATTENTION!!!  The  below  mounting  methods  and  markings  can  be  done  after  request  of  the 

necessary accessories!!

Extra Mounting and Marking Methods *

Suspended ceiling installation 

with

 

mounting accessory

A-1000

Suspended installation with A-1000 accessory

The  luminary  can  be  installed  in  a  suspended 
ceiling.

A marking panel (

SP-1000

) can be installed on the luminary pointing the desired direction.

Suspended ceiling installation 

with

 

mounting accessories  

and marking panel

Ceiling installation 

with marking panel

It can be done only by a competent person and after the mains interruption

.

1.  Follow step 1 of the installation instructions and remove the diffusor.
2.  Follow step 2 of the installation instructions and remove the reflector.
3.  Remove the old battery and place a new one of the same type and characteristics.
4.  Replace the removed parts (previous steps 1 and 2).

Battery Replacement

Package Contents

Commissioning

After installation, a 24 hours charging cycle must be completed, in order to achieve the nominal autonomy.

During commissioning of the luminaire write the commissioning date on the battery.

When  power  is  applied  to  the  unit  inspect  that  the  CHARGE  indicator  is  either  blinking  or  steady,  all  other 

indicators are OFF and that the led lamp is lit (maintained operation) or OFF (non-maintained operation)

A full duration test should be conducted after verifying that the CHARGE indicator is continuously ON. Test is 

initiated by isolating the mains power supply. Verify that the LED lamp is lit during the test period for at least 
the stated duration.

923

100300

_0

9

_010

2

Installation Instructions

Always  use  in  any  case  round  mains  cable

,

 

with  a  diameter

 

of  5

-

10mm  (H05RN-F  type 

2x1mm² 

or 

any 

other  type

,

 

at  least 

equal 

to 

it’s  mechanical  and  electrical  properties). 
ATTENTION!! The cable must not be deformed 
in  any  way  (This  requirement  is  important  to 
ensure the 

ΙΡ 

rating).

3

5

7

9

4

6

8

10

B

N L L1

A

Attention!!

  The  plastic  latches  (A)  must  be 

secured  (click  sound).  This  requirement  is 
important to ensure the IP65 rating. P

ower on 

the luminar

y

.

Install  the  included  tie  (if  needed)  to  fasten 
securely the power cables.

Ν

  for  neutral, 

L

  for  live  wire  and 

L1

  for  the 

maintained operation.

A

A

A

A

A

A

B

N L L1

A

2

1

N
L

Link

Permanent maintained operation

b)

N
L

External

switch

Controlled operation of the lamp

a)

Power Connections

Battery Connection

This unit has replaceable batteries that can be replaced or changed by the manufacturer or a competent person.

Description

Indications

 

LED Status

BATT.

FAULT

(

yellow

)

LAMP
FAULT

(

red

)

CHARGE

(

green

)

Fully charged

Charging

Battery fault or
emergency mode

Operational test

Light source fault

Autonomy test

Duration fault

Note

:

Permanently

ON

Blink

Indifferent

Off