Luminaire
Set of Pictograms
Mounting accessories
Manual
1
2
Pictogram Installation
3
Mounting Methods
1
1
These devices are used indoors and outdoors
o
(
ta 40 C
)
in places where emergency light is needed.
Each device must be permanently connected to
mains power supply
.
In normal operation the battery
is charging. The light source can be either on or off,
depending on user’s choice. In case of a mains
power supply failure, the device enters emergency
mode and the illumination LED turns on. When the
mains power supply is restored the device turns to
normal operation.
Autonomy duration selection
T
he user can select one of the 3 available minimum
autonomy durations 1 hour, 3 hours and 8 hours. The
selection must be done while the luminaire is
disconnected from AC and battery supplies. The
selection is achieved through Switches 2 & 3 of DS1
as shown below.
T
echnical label installation
T
wo additional labels are included in the package.
one for 3 hours duration (180) and one for 8 hour
duration (480). Depending on the selected duration,
the installer must cover the default 1 hour (60)
printing with one label that has the required
duration. Please take notice of the orientation of the
label.
Manual
Operational
Test
Remove the diffusor and then by pressing the test
button briefly an operation test is initiated. The light
source and the emergency circuit of the device are
tested. The manual test can be conducted only if the
mains power supply and the battery are connected.
During this test period the LAMP TEST LED will blink.
The battery must have adequate charge. This test
lasts for 3 seconds.
Manual
Autonomy
Test
A
duration test can be conducted by
pushing the
button
steadily for 5 to 10 seconds.
In order to be
performed, the mains power supply
should be
connected and the battery should be fully charged.
The luminaire enters emergency mode, the CHARGE
LED is turned OFF and the BATTERY FAULT LED starts
blink
ing
.
Its duration is the stated autonomy duration
of the luminaire
.
If at the end of the test the autonomy
is low
er than the nominal,
the BATTERY FAULT LED will
lit and battery needs to be replaced.
If the result of the
test is good then the luminaire enters charging mode
and the CHARGE LED starts
blinking
until the batter
y
is
fully charged.
Automatic Operational Test
T
his test includes all the operations that are provided
in manual test and is conducted automatically every
15 days and lasts 3 seconds.
Automatic Autonomy Test
The Automatic Autonomy Test is conducted every 6
months and measures the device’s back up operation
and emergency duration. This test includes all
functions of the Manual Autonomy Test.
Addressable Communication
T
he luminaire has the ability to be connected to
GR-6500 panel. In order to do so, the luminaire’s
address has to be unique in the same bus. For
more details see the extra leaflet.
Lens Removal
When the luminaire is used without the pictograms
or the SP-1100 and you require more light output
then remove the lens that covers the LEDs.
ΑΤΤΕΝΤΙΟΝ!
!!
1. Operations for installation, maintainance or
testing must be done by authorized personnel
only
.
2. Always use in any case round mains cable
,
with a
diameter
of 5
-
10mm (H05RN-F type 2x1mm²
or
any
other type
,
at least
equal
to it’s mechanical
and electrical properties). ATTENTION!! The cable
must not be deformed in any way (This
requirement is important to ensure the
ΙΡ
rating).
3. The device must be connected to the mains
power supply through a circuit breaker that is
depends on the total line’s power load.
4. In case of battery replacement, it must be
replaced by the same type, by the manufacturer
or a competent person.
5. In case of inactive use for a period greater than 2
months, disconnect the battery by pulling out the
battery’s connector.
6.
I
s not allowed to discard batteries into
t i
common trash bins, they must be discarded
only
in battery recycling points. Do not
incinerate.
Oly luminaires can be surface mounted on walls or ceilings. For these mounted installations, special
accessories are included.
Wall
bottom
view
Wall installation
Ceiling installation
Ceiling
* ATTENTION!!! The below mounting methods can be done after request of the necessary
mounting accessories!!
Extra Mounting Methods *
Suspended ceiling installation
with
mounting accessory
A-3018
Suspended installation with A-3018 accessory
The luminary can be installed in a suspended
ceiling.
A marking panel (
SP-1100
) can be installed on the luminary pointing the desired direction.
Suspended ceiling installation
with
mounting accessories
and marking panel
Ceiling installation
with marking panel
General
5
6
7
7
8
8
9
10
NOTE!!
After finishing the installation you must power the luminaire for at least 24 hours in order to
completely charge the battery. The rated autonomy duration can be achieved after that time.
Package Contents
2
923
100401
_0
9
_
002
923
100401
_0
9
_
002
923
100401
_0
9
_
002
Drill one of the 5 available holes with a 16-18mm drill bit. Install the included rubber gasket and pass
through the power cables. Install the included tie (if needed) to fasten and securely the power cables.
3
4
1h
(default position)
3h
8h
Battery Connection
Attention!!
The 6 plastic
latches (A) must be secured
(click
sound).
This
requirement is important to
ensure the IP65 rating.
P
ower on the luminar
y
.
ON
1 2 3 4
ON
1 2 3 4
ON
1 2 3 4
6) Autonomy Duration Selection
(Read on General Informations, Page 1)
7 a) Pernament Maintained Operation
7 b) Non-Maintained Operation
7 c) Controlled Maintained Operation of the lamp
ON
1 2 3 4
12
11
WARNING!!
Isolate the mains power supply before making the connections.
Ν
for neutral,
L
for live wire
Ν
for neutral,
L
for live wire
WARNING!!
Isolate the mains power supply before making the connections.
Description
Indications
LED Status
BATT.
FAULT
(
yellow
)
LAMP
FAULT
(
red
)
CHARGE
(
green
)
Fully charged
Charging
Battery fault or
emergency mode
Operational test
Light source fault
Autonomy test
Duration fault
Note
:
Permanently
ON
Blink
Indifferent
Off
N
L
Link
N
L
1
Installation Instructions
or
Switch number 4 of DS1
must be in ON position.
ON
1 2 3 4
Switch number 4 of DS1
must be in OFF position.
and
ON
1 2 3 4
Switch number 4 of DS1
must be in OFF position.
and
N
L
External
switch
8) Communication Connection
A
B
Communication Connection
A
B
From
GR-6500 Panel
Drill another hole (according to step 5). Install the included rubber
gasket and pass 2 signal cables and connect them on the A, B
terminals minding the correct polarity. These cables are used to
connect the luminaire to GR-6500 panel.
1
2
2
2
1. Fit the pictogram you need to the diffuser, be careful to
secure it on the 3 plastic holders.
2. Refit the diffusor with the pictogram.